ML19332D950

From kanterella
Jump to navigation Jump to search
Final & Interim Deficiency Rept CP-89-031 Re Tornado Dampers.Initially Reported on 891030.Unit 2 Tornado Dampers Will Be Inspected.Next Rept Discussing Results of Unit 2 Evaluation Will Be Submitted Prior to Unit 2 Fuel Load
ML19332D950
Person / Time
Site: Comanche Peak  
Issue date: 11/29/1989
From: William Cahill
TEXAS UTILITIES ELECTRIC CO. (TU ELECTRIC)
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
CP-89-031, CP-89-31, TXX-89822, NUDOCS 8912060070
Download: ML19332D950 (2)


Text

ty Q.

q r

iQ y

t r

M

-Log #.TXX-89822'

""" 7 File'# 10110=

LL C

903.3 C

~~'

Ref. # 10CFR50.55(e) ~

RIELECTRIC m

November 29', 1989 L

4 h;p W. J. Cablit

, f f _ "'

Executive Vice President ;

~U. S. Nuclear Regulatory Commission-Attn: Document Control Desk ji

' Washington, D. C.

20555 o

e

SUBJECT:

. COMANCHE' PEAK STEAM ELECTRIC' STATION (CPSES)

DOCKET NOS. 50-445 AND 50-446

[o

~TORNAD0'0AMPERS~

~

SDAR:

CP-89-031 (FINAL REPORT, UNIT 1) b

.(INTERIM REPORT, UNIT 2).

.4 p

r Gentlemen:

0n 0ctober 30,.1989, TV' Electric verbally notified the.NRC of. a deficiency linvolving1 tornado dampers..;After further evaluation, it has been determined

~that this-issue is not reportable for Unit I under the provisions of-

-10CFR50.55(e).

fSpecifically, nonconformance reports (NCR's) identified. two Unit I tornado dampers which could not travel.to the design full open position due to interference.from'thermolag installed on ' adjacent' fire dampers.

A walkdown of the remaining-Unit litornado dampers instrilled in tandem with fire dampers revealed one additional tornado damper whose travel was restricted.due to thermolag on the_ adjacent fire damper..An additional NCR was issued for this damper.

L A calculation of the Unit I tornado venting analysis utilizing the restricted positions of.these three tornado dampers. indicated that the change in'the m

. calculated-differential. pressures due to the as-found Unit I tornado damper

.{

louver blade positions is not significant.

Based on the results of this calculation, it was concluded that no adverse effect to the safe operation of Unit I would have resulted from this deficiency.

8912060070 891129 PDR ADOCK0500g5 p;!i s

400 North Olive Street LB81 Dallas, Texas 73201 l:

f

o &.:

?

I TXX-89822 November 29, 1989 Page 2 of 2 Upon resumption of the balance of' Unit 2 engineering activities, Unit 2 tornado dampers will be inspected to determine if a similar condition exists for Unit 2. - The next report discussing the results of the Unit 2 evaluation will be submitted' prior to Unit 2 fuel load.

L L

Sincerely, o