.c sq

  • ^

(

I-

[

(one' Firstptional Plan, Chicago, lltinois -

' Address Reply to: Post Offics Box 767 Chicago, Illinois 60690 -

A'ugust 29,-1980

' Mr. : James ~ G. Keppler,1 Director Direr.aate;of Ins'pection and

- En."orcement - Region III

.U.S. Nuclear: Regulatory Commission:

-799 Roosevelt Road Men Ellyn, IL 60137

Subject:

LaSalle County Station Units 1 and 2-

/

Byron _ Station Units 1 and 2 t.

- Braidwood_StatiorLUnits.1 and;2 Response to'IE Bulletin'80-16 regarding Potential Misapplication of Rosemount Inc. Pressure Trans-mitters NRC Docket Nos. 50-373/374, 50-454/455, and 50-456/457 Reference (a):

J. G..Keppler letter to C. Reed dated June 27, 1980

Dear Mr. Keppler:

Commonwealth Edison Company has performed the review

-of the subject-bulletin for.LaSalle County 1 and.2, Byron 1 and 2, and Braidwood 1 and_2.as requested in Reference (a).

In the cas.e of the Byron and.Braidwood units, no transmitters

.of thentype described in Bulletin 80-16 are in-use in safety-related applications. -The. review'for those units.is, therefore, complete.

'The review for LaSalle County is contained in the enclosure.

The review for. components employed by the.NSSS vendor (GE) has-not been' completed.

This-review will.be' completed and

-the results submitted to the NRC by September 30, 1980.

If you have any_further questions in~this regard, please_ direct them.to this office.

Very truly yours, M

Thomas J. Rausch Nuclear Licensing Administrator Special Projects cc:

U.S.: Nuclear = Regulatory Commission

-Office of Inspection ar'd Enforcement
Division' ^ of ' Reactor. Cf astruction gI ction SEE g g 5

y n

s-ENCLOSURE Response to IE Bulletin 80-16 LaSalle County Station Units 1 and 2 The LaSalle County Station Project Group has reviewed the subject document and the status of that review is discussed below.

NRC Bulletin 80-16 outlines a potential misapplication problem that occurs when Rosemount.Inc. Models 1151 and 1152 pressure transmitters with either I'A" or "D" output codes are ex-posed to excessive over or reverse pressure conditions.

General Electric (San Jose) was directed to evariate this NRC Bulletin for NSSS equipment and they have undertaken to com-plete the following actions:

1.

GE's applications of these transmitters will be analyzed to determine whether problems exist.

2.

Lists will be generated for the location of all affected transmitters.

3 Required Field Disposition Instructione (FDI's) will be issued to define required corrective actions.

Items 1 and 2 are currently in progress and are expected to be completed by September 8, 1980.

Item 3 will be completed upon review of the results of Items 1 and 2.

It is expected that any required modification will be defined and issued to the site by October 1, 1980.

Sargent & Lundy was also &sked to evaluate this NRC Bulletin for BOP equipment.

They have responded by stating that pressure transmitters of the type in question have been specified at LaSalle for safety related applications, but the problems ex-perienced will not affect any safety functions because the trans-mitters used are within the over or under range pressure' conditions.

Therefore, no further corrective action is required.

.w