Responds to IE Bulletin 80-15, Possible Loss of Emergency Notification Sys W/Loss of Offsite Power. Direct Insp Revealed That Emergency Notification Sys Was Powered from non-vital Lighting Circuit Powered from Onsite Power
ML19331E243
Person / Time
Site: Maine Yankee
Issue date: 08/28/1980
From: Johnson W
Maine Yankee
To: Grier B
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
IEB-80-15, WMY-80-126, NUDOCS 8009090431
Download: ML19331E243 (2)


Text

.

MAHIE * ~ ~25ARHEE AmmmFMERC[mP.MU

  • ru,,,,,,, o, o,,,.,,

$2 N ENGINEERING OFFICE WESTBoRo, MASSACHUSETTS 01581 617-366-9011 O

B.4.1.1 T@fY 80-126 August 28, 1980 United States Nuclear Regulatory Commission Office of Inspection and Enforcement Region I 631 Park Avenue King of Prussia, Pennsylvania 19406 Attention:

Mr. Boyce H. Grier Refere nce:

(a) License No. DPR-36 (Docket No. 50-309)

(b) USNRC Letter to MYAPC dated A2ne M,1980 IE Bulletin No. 80-15

Subject:

Response to IE Bulletin 80-15, Possible Loss of Emergency Notification System (ENS) with Loss of Offsite Power

Dear Sir:

Reference (b) revealed a potential for the loss of the Emergency Notification System with a loss of offsite power. Maine Yankee has completed the requested actions and offers the following information, numbered to correspond with the bulletin.

The following information is submitted in response to your request for estimates of manpower expended in the research and subsequent performance of actions associated with this letter / bulletin / document:

Minoower Requirements Hours Bulletin Resrcase 10 Manhours Cor netive A.tions 120 Manhours i

i l

It should be clearly understood that this information is not adequate to enable a value/ impact assessment. An adequate determination of the safety i

)

improvement as a result of this document needs to be included.

(

Item 1:

Direct inspection, in conjunction with the appropriate I

telephone company representative, revealed that the ENS was powered from a non-vital lighting circuit powered from on-site power.

l Item 2:

The power supply for the Emergeny Notification System (ENS) has been changed such that it is now connected to an emergency bus through a transformer and circuit breaker.

8000000 %

f 910 i

i..

l United St_ates Nuclear Regulatory Commission August 28, 1980 Attentigd: Mr. Boyce H. Grier Page 2 Item 3:

In the event of a loss of offsite power, the emergency bus will be fed by one of two emerr,ency diesel generators.

The existing monthly test af the diesel generators demonstrates that the loads on the emergency 'ouses will have adequate power.

This test is considered sufficient to ensure that the ENS would remain operable in the event of a loss of offsite power.

Item 5:

A directive has been issued requiring operators to notify the NRC Operations Center within one hour of the time that one or more extensions of the ENS is found to be inoperable.

We trust the above information is satisfactory; however, should you desire additional information, please contact us.

Very truly yours, MAINE YANKEE ATOMIC POWER COMPANY

.1, 8 l:

J/ x n, //' G n WJ O \\,

W. P./ ohnson J

Vica President COMMONWEALTH OF MASSACHUSETTS)

)ss.

COUNTY OF WORCESTER

)

Then personally appeared before me, W. P. Johnson, who, being duly sworn did state that he is a Vice President of Maine Yankee Atomic Power Company, that he is duly authorized to execute and file the foregoing request in the name and on the behalf of Maine Yankee Atomic Power Company and that the statements therein are true to the best of his knowledge and belief.

f 4

j ' '

n j ]y " *"..f,$,..

Robert H. Groce Nothry Public m

.,$,i.

My Consnission Expires September 14, 1984

,< c.

i

-: b'

.* h m

l.nl

,... +%

r, s

4

- -