' APPENDIX A j

NOTICE ~0F VIOLATION Boston Edison Company Boston,. Massachusetts Docket No. 50-293 j

Based on the results of an NRC inspection conducted on April 21-25, 1980, it appears that one of your activities was not conducted in full compliance with conditions of your license no. OPR-35 as indicated below. This item is an infraction.

Technical Specification 6.8.D states that " Written procedures to implement the Fire Protection Program shall-be established, implemented and maintained."

Licensee's Procedure No. 8A.6-1, Fire Extinguisher Checks, revision 5, August 9, 1978 states in part, " Perform a fire extinguisher check on extinguishers once per month...the inspection procedure should determine that:

1.

The extinguisher is in its designated place.

2._

Access or visibility of the extinguisher is not obstructed...

6.

Maintenance record tag is up to date...."

Contrary to the above, as of April 25, 1980 fire extinguishers have been either removed from their designated places, or the extinguishers were faund to be obstructed by temporary equipment, thus leaving vital plant areas without ade-quate first aid fire protection.

Maintenance record tags on most extinguishers were not up to date.

4 8009090062