Text
ma APPENDIX A NOTICE OF VIOLATION Tennessee Valley Authority License No. CPPR-150 Hartsville Nuclear Plant Based on the hRC inspection May 20-23, 1980, certain of your activities were apparently not conducted in full compliance with NRC requirements as indicated below. These items have been categorized as described in correspondence to you dated December 31, 1974.
As required by Criterion XIII of Appendix B to 10 CFR 50 and as implemented by the PSAR Section 17.1A.13, measures shall be established to control the storage and preservation of material and equipment in accordance with work and inspection instructions to prevent damage or deterioration. The TVA valve list requires Level B storage for valve No. E12F105.
Site Procedure M401, Rev. 5, and M402, Rev. 4, specifies Level D storage of stainless steel pipe and carbon steel pipe respectively. Procedure CEP 13.02 specifies that Level B storage include protection from the elements and uniform heating and temperature.
It specifies that Level E storage include cribbing and storage in a well drained area.
Contrary to the above, May 23, 1980 site procedures for storage of piping were inadequate in that they did not address in-plant storage and were not being applied by site personnel to in plant storage.
In addition, there was no procedure requiring inspections of in plant storage of piping or equipment. This resulted in numerous safety-related piping subassemblies being stored in the auxiliary building in direct contact with wet floors or standing water. Examples are subassembly Numbers 17AB-ESW-145-1,17AB-ESW-74-1, 17AB-ESW-353-14, 17AB-ESW-68-1, 17AB-ESW-143-2, 17AB-RHR-6-5, 17AB-RHR-7-1, 17AB-RHR-15-4, 17AB-RRR-21-7, 17AB-RHR-34-2, 17AB-RHR-72-1 and 17AB-SPCU-7-4.
This also resulted in 24-inch motor operated gate valve No. E12F105 being stored in the auxiliary building unprotected and without uniform heating.
This is an infraction.
8008280 /Q