Responds to IE Bulletin 79-13,Revision 2, Cracking in Feedwater Sys Piping. Main & Auxiliary Feedwater Line Snubber Operability Verified 800701.Support Design Conformance Will Be Verified Through Required Insps
ML19331D009
Person / Time
Site: Davis Besse 
Issue date: 08/06/1980
From: Crouse R
TOLEDO EDISON CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
1-155, IEB-79-13, IEB-79-13-R2, NUDOCS 8008270080
Download: ML19331D009 (1)


Text

s-J p Gp TOLEDO

%mm EDISON Fheni.nop caoest Docket No. 50-346 License No. NPF-3 U.7 Serial No. 1-155 me m221 August 6, 1980 Mr. James G. Keppler Regional Director, Region III Office of Inspection and Enforcement U. S. Nuclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, Illinois 60137 Subj ect: Davis-Besse Nuclear Power Station Unit No. 1 Cracking in Feedwater System Piping

Dear Mr. Keppler:

This letter is in response to IE Bulletin 79-13, Revision 2, dated October 19, 1980 (Log No. 1-257), as applicable to Davis-Besse Nuclear Power Station Unit No. 1 (DB-1) relating to cracking in feedwater system piping.

Toledo Edison was required to perform a visual inspection of all feedwater system piping supports and snubbers in containment to verify operability and conformance to design.

The operability of the snubbers installed in the main and auxiliary feedwater lines was veritied on July 1, 1980 by performing Surveillance Test Procedure 5044.01. This surveillance test aeets the requirements of DB-1 Technical Specification 4.7.7.1.2.

Conformance to design of the main and auxiliary feedwater supports will be verified through the inspections required by IE Bulletin No. 79-14.

Any deficiencies found will be reported under IE Bulletin No. 79-14.

As a result of the above actions, this completes Toledo Edison's response to this bulletin.

Yours very truly, ff

==