ML19331C820

From kanterella
Jump to navigation Jump to search
Forwards Response to Seismic Qualification Review Team 800710 Request for Addl Info Re Selected Equipment Items Including Power Supply,Battery Charger & Battery Rack. Oversize Drawings Available in PDR Only
ML19331C820
Person / Time
Site: Farley 
Issue date: 08/15/1980
From: Clayton F
ALABAMA POWER CO.
To: Schwencer A
Office of Nuclear Reactor Regulation
References
NUDOCS 8008190596
Download: ML19331C820 (33)


Text

{{#Wiki_filter:7 J Alabama Power Company gggg j INlb 00COMEHT C0 s00 n:nn istn stree' Post Office Box 2641 To:epnone 205 250-1000 POOR quAUTY pgg{$ Birmingham. Alabama 35291 J b F. L. CLAYToN, JR. se,ior Vice President Alabama Power me sout.wn e ec:rc s, rem August 15, 1980 Docket No. 50-364 Director of Nuclear Reactor Regulation U. S. Nuclear Regulatory Commission Washington, D. C. 20555 Attention: Mr. A. Schwencer JOSEPH M. FARLEY NUCLEAR PLANT-UNIT 2 SEISMIC QUALIFICATION REVIEW Gentlemen: Enclosed is the additional information requested by the Seismic Qualification Review Team (SQRT) for the selected equipment items identi-fied at the site visit exit meeting on July 10, 1980. Information to resolve your concerns regarding the containment purge valve, emergency air compressor, and motor-operated butterfly valve was provided in a telephone conversation between our staff and the SQRT team on July 23, 1980. Should you have any questions, please advise. Yours very truly, ,k - ), !b +~b. r' F. 'L. Clayton; Jr. CLB/sc Enclosure cc: Mr. R. A. Thomas Mr. G. F. Trowbridge Mr. L. Kintner Mr. W. Bradford Licensing File No. 243 'g O / S // e00819 09% 4

Enclosure Seismic Qualification Review ITEM 1 - POWER SUPPLY 1 Concern was raised that the power supply might not have been monitored l continuously during the test. The manufacturer of this ecuf pment has con-firmed that it is composed of solid state components and a transformer. There are no moving parts involved, such as relay contacts. Therefore, it is improbable that a malfunction could have occurred during the testing that would not have been permanent. We maintain that the methe f of monitoring was adequate. The mar.ufacturer confirmed that the words " rigidly mounted" in their test report mean-the specimen was mounted to the test fixture using the standard bolt holes provided in the power supply body, i.e., the test specimen was nunted like the field installed power supply. v-e 6 i l

I ITEM 2 - BATTERY CHARGER (a) The battery charger is mounted differently in the Service Water Building than it was for the seismic qualification test. No natural frequencies were found in the range from 1 to 33 Hz for the test mounted battery charger. Therefore, the test mounted battery charger behaved essentially as a rigid system during the seismic test. Frequency calculations have been made of the battery charger as mounted in the Service Water Building, and these calculations show the lowest natural frequency of the charger as mounted is also above 33 Hz. Therefore the battery charger behaves as a rigid system just as the test mounted battery charger behaved. The battery charger was qualified as a rigid system (dwell test 0 33 Hz). The Service Water Building mounted battery charger is shown to respond as a rigid system, there-fore it is also qualified. Additional conservatism can be found in the frequency search. The search was done in " discrete steps of 1 Hz and vibration was maintained at each step for a period of not less than thirty (30) seconds." This in itself is ~a continuous sine test. Due to the fact that the charger was a rigid system, the input and output G's were essentially the same. Plotting the output G's on the Required Response Spectrum (RRS), one finds.that even if the Service Water Building mounted battery charger has natural frequencies as low as five (5) Hz horizontal and nine (9) Hz vertical, the test input was large enough to qualify the function of the charger at these natural fre-quencies. The above discussion clearly shows that the function of the charger as mounted in the Service Water Building is seismically qualified by the test report. The only other concern is the structural adequacy of the mounting system. Calculations were made to conservatively show that the stresses are well within allowable limits. Even though the system was shown

Item 2 - Battery Charger (Continued) to act as a rigid system, thus allowing the use of the ZPA (0.llg OBE, 0.15g SSE), the maximum response accelerations were used for 3% damping OBE and 2% damping SSE. The stresses were shown to be well within the allowable l imi ts. See the attached calculations. Based on the above, the mounting method used to install the battery charger in the Service Water Building has been shown not to negate the seismic qualification test. i (b) The box attached to the charger contains a timing relay (Agastat Model No. 7032). This relay was added to modify the equalizing circuit such that automatic equalize operation would be obtained. This relay does not perform a safety-related function and its failure will not prevent the charger from performing its function. This equipment does not require seismic qualification and since its attachment to the charger could affect i the seismic qualifications of the charger, the box and timer will be removed 1 and mounted remotely to the charger.

.. Edien calculations SouthemCompanyServices A Project (Prepared By Date 5t/res IAssa'b # E. D. f // oo v e. TfE6"lBu f ( Subject / Title Reviewed By Date ^ Ek t'lftf b/ser - $ets ori kY Calculation Numt;er Siteet I of fLL PrN~ - Qecose.1e L el; tte < ~.a.e be w, 4,, Mery e t..<, e w,, s,.y,,ea,.I j,,;$ L seosm,*s Lerk & law 1 4 1 ssor porta,I in H.e tietJ. 1 D& res+ m. ~ ka,~ : e The Charger uas counted with eight (8).1/4-inch bolts to tuo (2) secticns of 2" x 3".x 1/4" engles which were welded to a one-inch steel ecuntin;; olate. The Batteries were counted in a special test fixture, sucol. icd by C 5 D Batterias, which in turn was bolted to the'.b.cunting olate with four (4 ) 1/2-inch bol:c. The clate was secured'ro the table of the vibration machine kith sixteen (15) 1/2-inch bolts. field Ne u n t.+) ' U

  • r;er h s u pre e G.l Ste w, %a Gro II lse U!, aollr'hr>'al npper/*al,.trevioled luy a 2 " cf.w.. e ler cc> ><f.a i4 he>., 41 e Sloct h h.e a fs.'e re (.rppies.,vsJc !aeipt-
  1. 2. '). TAe c,e '4 o t:. e. :. " rger d col'e) s. M 4 - % '/cn.,,IJ. 'Ars e f

s bolh hoII h druk ( Co le I'/s s l 9tb. T~e t 5 fr.n h it ers bel!<*l$ 'tes//.

  1. re S c lu.Gav o) S% O cs Ue<y cl.a.ye bs. s enyu.s... c / y 's ih ereess e C l22S.

b) Sitew. %+ Z; e iJ La IL 'g h < C-wr-i &. f u < c /Ms. :!w i<) d.~lJ pic r e Is r *, e,,

u. af ;le. U.,) peus.. sMLr<( in I*ye;G, o)

Ce eI( L--? u.-eic

, Jc. ss l lle.<-s o

7 8 -a. Vrrf 334a i c p.t-1.13 /,4 ( t. G e, pera eu L + l.' c, 2,.. h >> C. I s, (g 40 p s$ - vert : 33:Ig r.43 -.i /. fp .o ., m ,, 9.. c i.,, Mar.; U-.s << *,, e< e ulJ % tr p J d a r W;- a ,-, e <.j2v7 6 e,ue.4,. : 4 3.,13 ug. .t i#4/3o3,c g, /.,.t.,y 5 c;oe /44Jt a-o '. c kerve.f Ev c cse n+ e.r,.J.;,k h.,' :4 ret p 4ca.sL l C ow. ,yrm cJp.r* e, e..ts r.gJ U. !:e ?<<3 5 % ] 4. % 3% lttDX C6G 3 , -. ~.,.,,. ~..... ~. . -), a..., -h!!.d* UI" !IT s fd%I s.$ e. eee'< !ct,'l p 4i fres 9 hL 'ter + cu y r- -n

' D'esign dalculations SouthernCompanyServices A Project Prepared By Date Fn/es fl.s.d '&

b. /. nt a c te.

7(2ilpa i Subject / Title / Reviewed By Date EsYerg $ $a r< r e $ rri os.'e S ua.t:Da)w Calculaticr1 Number Sneetk Of hY

4) C,,,4 Sa,.e.sY e,uan'. eF kuuy cLne k wm pnc,J ns,, /.s oc Da nwQ C e ha G. <

,e of 5 es y,r:s nJ;<ase

a. f m ve< w m

t Jyeder. [L M <rA<.1 fiq s: % Wre7 c4 er a, m-Call m:u.,JJ n k 9 f w $ be r3 ~ l b et greal*< t w V 4 Heist e-J cf h areL +~ l fa bw&rd ?$ %t beYery CA'-e r$ e,' ok sser/,* sic.?,y h4 //r.f.)c:$frpeei. f / e CC c:a rse fa Grae W eJeyeay o4 %e nr,m 4.,} n p,eas,o ci.-cy r cc/e. dea M. FCf m No. 9 324 A ~

hesign calculations Southem CompanyServices ah Project Prepared By Date Fsr/r L i

  • z.

D 12 niccm. 7 h.c/s.3 Subject / Title Reviewed By Date ) L Pns, C(,aive - (4..i n,,J.C.rl. Calculatiori Number Sheet '- of J CL f) Cen 'L ?u qes c,' Alc nahraf $<epecies tve/r SJ he/cu- $3 //s t/arrir) Ae $ s e-ry 9 t -h. e La t e< 3 cl,<y s. 7Xe pu,pe se o f ze -o //o w,4 co /c Is.% w eep a 'i k~ cesser /s %e t c'.%cJ e 1At /cu e:/ m/a/a/ Eep+ey of k lafe/y' Jeaf iri he Sit /s. As chiled 'reviesistf ;S 1'l e na/wral f c&seger os mo t Cre a,,e can, be sI. u o k he &a./ fo ce grenIce,% 5/r Arn$*cri'</k d 9H ver e a./ h<, r % ?c< *ch e>\\ s ' 4 I*irrf e(** #rs't f**.c/lArl N ?!e i ie(cis: eI +:s+ rrpeeh llssswrphcnS (

1) Be cappee! n.,$ dde) SIiJ.C,,m :I h e 2 " dier... < L er en -/.< ; & 4 < +

cenrech +e fu b %ry cGeyr Ac...+u [!ose it r: r + inch,s e.,l..'Ir.s d l Censee n h.e sin ce. n s '- t n eiJn$ h ls 14 Uness u-ilI c. *se. % C-cat wid e,) e.<haal ?ree a, esj % 'ac <n ut.Iw-te f: a.. - k p-M r d ve n' y n*ff & z)0+ 5"je.m s 0: fa e n ie @ m ie is emicienJ e fsee..e. n e a~,le r see % Ilg runs the Ell hei%F o ' he cl<ar9 er. O'is agaisisc:rser"h0c Sinc e u,s i n q.w nec' ilta r ily s korb Im s, w;IIpiccluce. mo<< lloilsil:l y n) cuts e .s fewee cate.JsJd t h.eI O 9.s e.a i 3)Ihr.G e < ; 4; l; L I M EUrry LG.$ ge L & $h u-<.5 l L eer'vs<ra).';s i t \\ ; s' rie ? t 3: eo as w sJ G < <y..e...e,h : : m k. u, :..:.a,y e n) a < L. A. > ~~ h e. i G reer : s ,;'e we v e,1 3 f. er-e W. % e n -,

3.,;f a. r,.s.

7 !-} The e r o $d Cles. h;\\;ly cl. % n<e .).e'ag %:l*e,

  • c %'e) is 1 J

G) C,oee b,e n e.t.or kIls see > a', v*ey etos e jtc :. o m; /y o +:.' at:v m', A, heH$ here t&) 6c I; H!c -l#s i ;'3.; :~~ f.' e *Sr.d, o n#I-* <, 4.:s 4 ;b;/;2 ^ 1 7 w;rs no / in elaol.:). /.Y ' 0 C I:s..-f5 6 *n.5ssf.b f.q se

  • v e n;p)$ h ~,.c.),;&cz]

( pgly ',,*, L ,..( ke b rete,J,d c y,3 p,,l.- t y 6,,,. u). R.s si h,ec.u w A b p :<..e.,'.$ k / 9 P,3,". F,f h., yef.,),,,, f Afyge, n to e 5 : < c ' in P.i f.ac.%;,,. e,. I.j Y1. e nic u~J ej kcIt cpa r ;e 3 ,5 13 'y, e,. /,3,e o,,,,,,,..: .,, j g,,,_,,.,;./,,, Fcrm No. 9 324 A

uesign calculations SouthernCompanySenices A Proj:ct Prepared By ' I'" NY' Date ( ~ Subject / Titre ?). l /}/ cord. j/7h?o a,vi ma gy h /I" - CA*r w - 6ers%.. du /;4aso g,,, Calculation Number Sheet Y of ) o.cs s= Y.h'/s' / 14 h, j ropet Eo Ac'1 t ~ ,.s-i. c"<se 3 y 4,, g ,. /. r . c., O b.:e l e p.3: e m- -~~- ew %h. ~. _. f i.' llY f1b, l b i >:L r ( v;;f'G 4 F '\\5 ~j].. fi t _ g 9,3 r-k E s a v.,c it 9 cL. <, c,- y

  1. , g i

i 4 .8 I...f. e .. g L-i~ W sc 4 t.$1 e p -- t I f t.fi',d

2...

-j + P 2-( k9 c a i. @n .n $ -- .-}.i. ~ i de7 4-- .a. g I

1. % ac3 y;. 9,.@n]

i.s -zu,tr ks: 3 yIe.+ fn=.1.*.6 p:o,au. 5:f s ')gp L,, g, p. f . ex. w Jr: ) us za : h.2 - 3 " (49 - 0.000o su mr s 1. , f o.n g' Ls c.outnc.c sc + b :. c.g,,.g

  • 4: 0. o 3 2.,D I O n)'
. s. 1.( L.h L N rg

.c. p.m {/ -. o s.,.s

  1. 031 O*=d,

= 2 ('9.75j,.. e. s,o

2. %.,)

a 3(;%,5)$o,sesi) g A -& ( + cs t s vo*) =

2. s t 45su ci' <,,

.,<< % 6 ,,,, 4., z.y a y,,q-6 7,,,,,,gs y, y,,,,,.,,a 4.4. rf e 4 n,-- ' L,,,,., - i. n 9 >, o *%t-- u S r,, e- [#ia m e'; M~ ,'L,,,, = 0.. r n U say,,, e -,. s , ; , :pq-4 I, w', {,2'.,a9,,,,g 2 3g7 3p, 3,3 ,,, ;, q,,,,,, g,,,, y c .L rf. 2_ < sm,o" s 9. /, 4 2 7 y -.'~ z \\,3,33 - T. .. _r._ P ffri No. 9 324 A C .y O.

SouthemCompanyServices A Prject. f.e el<n O# E. Prepared By Subjec!/ Title (). A /N ecte. 'Oate

2. h<y Clame - Gl.a.:e O u d ;[.'e J ?

Reviewed By 2/7 r/f a Date Calculation Nurnber Sheet b Puense. 6 of i'E \\ CC<<L dej~ej & n' ~ h h helh s'. I k'*//P' w'$ 4y/c. AsN,ws. y //eatec+ e nyyc.= pad / ib z.ra it man,J.,4 sys+em.. censewa hJe)y 2

  • h cc 4.e y

- Ev n hough he ha //uy c4e<per A<s bee.. riah<r J fr#pe.j peaJee % 53 4 st.en 'c ke ik A <4.J.J O e % he..v e. %' %.,s y, dw c v*<u d llee.- tespmse accek <sso.'. e fr p~. *

  • c $fecke<r w ni be us<.f CV.< j cm raek-).

/)de ' 7[e cenere tt. A efer helb 'hd / dack h c C& <. >* e.( b b Ce lh 'Jeff C l:% L frosim;Q h N mewke$ r Icah seen by ho hs (:"e ers On Q $ ret! 0tC, w N n.e ~,. ti->; bo ts sie ( & ceuJe ndws. Ilha ho+L e' * \\ h es:~uay ksa,<./ d<een 4 y are M s ~ < ehr.~~~e4r'. por ;,-, me<< B syeme S u le Jeele/< Ae, Atues (Gned'h % 21. Ins 1 i c cz 3% _eas 53 lhnv !. cy e ).ye (if/ :c.vg) Herd C. nyG t5ra(wnq) vitt o.a y G c.s % r:m : c. 4) Veit

c. 9 59 2 c.z n ( w a. Q 0g g,%,;r eA t.

(em s. A A luS <<%i th e +u6 >rn s. t. ).t)so 4-e cz e vn'- 9, 4r,1 5,oreausc

.e
  1. 17 'i t?!6N o f' -M 6<en ^< ce e A u u.A ten 4.. r 4 3 87 a tr t u d '<.
4. / c<e 6: G M, <><c.; ( r
s. s,,.,

f 7 :< ',I ' i. m: 'orm n.,.nu o 4 h 9

Deign' calculations SouthernCompanyServices A Project Prepared By Date Ko < t< /L.*t

  • z D. Antact:

7/trbo C subjecerntie i seviewee ey oate 2.. its,,, t*6 ve $~-. ;,s. a O a:Cea s? / Calculation Number Sheet 7 $ of i G lbcw lap o *

  • Sn $wo luols'y s

n _M" 75* I I g i

i f.G
I t

6.o M a t ll 37 $ w l 3

, e v, h

i, -_o 1 I (/r t.S)t.c'b:ic3 !)- u L. s a y ?e,L care.:. -:. IM 'o : 4.c:5C Ad

  • 7 5 (toc-9.25?

o l19. 7 P:

9. z s
  1. l9*7 -

" 9.2 M' ft. Q= 5'* 3 = /370 p, ?

0. c A Z ed,

~ nw., b re sd A.*w of h*p l M *v Cl.rar f er urs k-fa+ kes**'7 Ccn fes* n*** l's !b f spo t". 3I.k Lb. 1/~ l ga : r. s-e

  • i~4 7:

~ 952, as e-

f. e 5,-

l 5.:s i f a,4 $4 rest s' n l I n 'k 7 I/n." h.1% w e eE[ecL;ye l 5, p.,3,, \\ 3 ',.,. g Q,* (. 1 i l % m 'c rus % (w>I ke,}u.:e.l..r:n) f. M t. [3.e:5-3.ss EC( a.2 ) (Mz)

I,o g s. ou O. c o c o ca l

( %hf O g ff**Y$ $ Of * ..?# e c : 4. G W ( 'e **.1) + 9. l ? /10.:', - ?. " E 1Z89 fT

  • /39.480, f, ',, i.- r /27)' : G 1. 7 tb g,,. 3-2 / 7 a. p *.

l/ r"e 2 r 3.o s :. Form No. 9 324 A L

lGVIf M -en e -c .~ - < o, -tn d k -r . W ;it e. in t *, = m A

  • g t) m.

A. 4 a 2 v +-L- ...gy t ( b e,% u L' v s si e

L D

e %s -o .T-N = W g 7 ~ u 2 w \\0 c.d 4 % A 5,. _3 -w r.n I n ' U') L' w ~- .L..)- .cn <. La 3o tu -cv cc L:_ OO e -m .e -n - t.D -1.0 .~T _n -cv l t .o GD*E Oh*2' 00'2 09't og l 09'O Di '0 00'0 ~ '~ 0 8 ' : 'o' r ' A v"o' c. ;>.1. .. O-i ...-, 3..

i. o :

., o t, 3

i befIf .e l r. - -e' f -m i i. .u e v k 0 ft -m .s E m 4 Nta ^@ t -m q . q 2 s y s s{ e s m s N

r. <a 4

x A g i -w u m u " %g.4 t C ,h y N -1' g s,' s -c3 5 -4 ^ c I'r. e (f) 6 .y G 9 ^ __ p >- c.J ..n Z Lu 3 O La -N g Lt oo j -en -e -t-I -e -m I l -w -m -ev i I O G r r :-' 03'c '0! 'c. 00*2 09't OF'l 00'0 0 11 ' 0 00'0 Je ..e .r. u u.. ii.- - i -... o d ;; u, i.. o i e.. : l

s \\ ~. E M R U i O H 6 tT = f 0R 2FR 7 E a Rs 2 6 9E i 1 1 i Ri 1 H s

  • Cta E i

RWO I I nO H Hc i Sr I ST ER l Uf LE Ar Vc '0 5 1 O 2 3 1 O. O. 0. 0 [. g 7 g. = i ) 4, $ S \\ d 1,i ? r ~ $ C ( ( I ~ Y C + N E U Q E I 5 R F O N T 0 1 I 3 ~ N 0 U E C R N TU 2 i T 0 NC I AU R .S L T 1 E PS 0 M C .t H t ~ E al l I'R i M.. lG V ADTT5T0 TR F0f f l l R EJ E i 0lE V t .E Ll 5 .E L LE S C R4 0O EC U E 8ICC N NT 1TCR AT DR R H1 1:H C t E Y I0 EI H E E O!G S T i CPT' ;C t T'LI 9I; ;t U H*.SVI T E n Ri:~.'.: i t '.,L i E T E S ' F S'y,E D i S 0 l 1 3O." O N, oO ~ Ow - go $s oo. cL ' C n .~o m,__ C c 'j w U u C unzoo_Otdn o "^~ C( ^ C t < i

I. l0.eFI .C3 ,. p. e f?u .M ,,og g CD -O i OO e N AC (.9 i e H m wC .a Q4 10 w CC r "W '4 ,. g O Z M to C." 3 M u x C.y C OM (A CJ t e ,. m 'M *2: W L.3 DM .l D e CUS >O + O 4 ~ s O. O. O. -c3 ) e -C3 .p .r my = .g N N-. C,L, si e i , g -s

  • M f

N w ~* u W b,. i -O t M Q. C \\ 'g,' e -N c-O Z L: i i .h g. ~ 2 h a tj a - C? l-- M Zw \\ -:J e U' C C g -N .z ) D n W LU j -fl3 I( ' (n 0~ 5 0 -m W CM ZC U.W 6 -n w' nC tri - J ::: M e -O > U C&& &C d W e4 W e* C C D Z td OCW . cr1 W ZM>M eWJ e JW t p CqOOWU bW C) - U U Z WH ~>UC s a .. N CH C C: C 3 ;" ' C U N l S, W (C -O W~ I Cwo-co-I uun=u e, e t.t. -> n 3. :.,n C-O ie = * (;etet.t,*:.1 *.3 r 'a O i:r...- .. s : m v n a u z.:re, ts i i r i _i 00*8 Oli 2 00*2 00*I 02't 00'0 O tt ' 0 00'0 . n. 1.i.t:.: 2 7..:. m q u. lc.. lJ. r.'.t e : r ' ,i trc ,0 d a s.

I/ oF l.f s / .m a e

  • C 10 M

-l'. c, D i O -LD Z (C H "O Q O CC e N LA. C; N LU -;T e-= (n td .

  • c (A e cw I

to. UZC to -CO CC 3 CO,"** %O E % (3 OO -N m OH 10 C D C*. .Jtu C C',. >Q s I o ,e j J!

-4

-m i _e .h .tg (/) .A. -tr) U w .~ Y _O 1 -M l

  • Ls

, *(, Da c N TO W 0 -N O. O. O. O. c- -4 ,c n O p a p ,~ 2.'-f. .-.Y Y - -- - --36_ _ _ _ 1 O N -..p._ j l== g l N .m -co a ga U c .n o . :.. p= g a -LO &-4 2y co -13 C (/1 J W (L. rn = t in = c y. 1 tU OCC H4 CM e === C H ob O .C C u. e cC -O C Lt.) g 3 c tu. . w s a.. tn to 3 . au g o c cs a tu u O ta eco.- v u - >- u c .g z 2 >c b= C CC C u W >- s.: z c -O tua-. '" g ta a - e tn r t y c t -

  • ! t' '

l -s W c >,CCs-O 'C .. r., i : 2 o o. t. e v,3, e= tu r <o v. .wc_ 1 tn u mr.taaetn ,~ 9t q ?. ' t 00 0 Oh*O 00*0 0 3.rC un c ~ #' , 0, q I A v a., i., s s 0,0,c' ..i n. m -' u , u. i, , m.- p! 3 b,,o.. , t. 6

m. -

i 1 . a,

  1. S'OUTHERN SERVICES INC MRRCH 1972

~~", ) VALUES SHOWN ARE F0ft" FRELET NUCLERR PLANT UNIT NO. 1 GPERRTING anSIS EnflTHOUAKE. SE3VICE WATER IttT3KE SinUCTURE Fig. 17 0 t'0 S T-C 1 f4 T 4 tt-s 5 ELEVATIGN 103.5 FT. N Cfth! Ir:G finI10 .00S .0t .02 .03 hE':i'Cr:5E RCCELErlGT 10tt STilitiEi1C ACCELEft0GBRt1 a o .005' ze -a. I c- .0I 4 m =. / a => ,s 4 t a 4 s-l .O2 C.~ l 1: '/ l .\\ y. .o5 e :. p 4; ,l4) '^ 1 w 5 f U.' ) t 29: .a h<- 4 t b r c_. a y f. l. t w u f to cc i m 1 = c m =- 8 \\ r .I I G ,Y e _.;.crM E'}~0-S 5 0 S S i A 0 '10 5 .5 'I $ U i A 0 '10' 5 5 0 $ 5 i S S 'lli FREQUEl'lCY tCP il

m

  1. SOUTHERN SERVICES INC MSRCH 1972 VALUES SitGHtt ARE FOR FARLEY NUCLERR PLANT UNIT N0'.1 OEsics ensis EnnTt:00AKE.

t SERVICE HRTEft INTRKE STfluCTURE Fig. 11 3 1 DSS POINT 4 E-W ~- ~._ ELEv0T10N 180.5 FT. N 00:#liiG RHT10.01 02 .05 ilES:'CNSE RCCELEBRTION S11!t'.EI1C DCCELEROG80H .01 I ,3 O zo m g..___ <n ["O2 58 d 'c'~ ~ r-tu uo [ ( ~ o.. c l .of o-as m XS C. f> E2... O-. O m J bJ l C T O 7 .16 G .c d-3= f ..l A I g 10-5 2 3 ti s a 7 a s 50. 2 3 it s a i 1910' 2 3 ti s s 7 esh e 1 FREQUENCY (CPS)

d 'x O a 5' SOUTHERN SERVICES INC HaaCH 1972 FARLEY NUCLERR PLANT UN.IT NO. I g$sS!fibNS$s !nnTIt00RKE. SERVICE tt0TER It1 TOKE S ffluCTyBE Fig. 14 O 'r S$ P0ltiT 4 t:-s 'ELEJGTICtd 188.5 FT. N OPT'!!iG RATIO.01 .02 .05 1 fiESPet!$E ACCELEfl0T 10t1 STitittE TIC 11CCELEll0Ga0M ,o j o zo cc en 4 m-s~ c;~ u_1 1 0 ua 3 m u.. j' ~ 05 ^ L* 2 C.95 O -"*3.. u.o

n

~- 1: s l c: y b o M .I S G o ~ . -y. x S 2W ~~ i 1 i i r-i i i i 2 3 ti S ' G 7 3 9 '10 2 3 is s 670910' 2 3 't S 67094 i i g gi [f' F!!Ef]IlENCY (C"S1

ITEM 3 - BATTERY RACK (a) The seismic mt '. iematical analysis performed by Alabama Power Company on the Service :lat;r Structure battery racks was' dependent on the racks being both wall and floor mounted. In the analysis, the rack was anchored to the floor using four (4) 3/8" diameter bolts and also anchored to the wall using two (2) 3/8" diameter bolts. The actual equipment is only anchored to the floor using four (4) 3/8" diameter bolts. Therefore, in order to maintain validity of the analysis, a design change will be issued for field personnel to anchor the rack to the wall as specified in the analysis. (b) The battery racks in the auxiliary building are located away from the wall and are mounted by bolting to the floor. The battery rack and battery assembly were seismically tested for this floor-mounted configuration. l %6 e- -y iy--- -wa

} ITEM 4 - DC DISTRIBUTION CABINET Although the test specimen was mounted with six bolts, an inspection of this cabinet revealed that it is mounted with four bolts. There are no provisions in the box for two additional bolts. We have contacted the 4 vendor concerning this. Based on his reply (attached) it is concluded that the four-bolt field mounting is adequate. I i i 5 4 n n - - - -, -- ,-,c- .-_--,---,-,------w 7 c.7,y ..-- me,- w -,.,,, -,- -.,-,-,,.,---,.--.,,,+.a 4

r, D M i!."J T E s. min.~,m.c m :, + GOULD-BROWN EOVERl Tek:.sce.c t404) 4514575 [' August 4, 1980 Southern Company Services, Inc. Post Office Box 2625 Birmingham, Alabama 35202 ATTENTION: Mr. J. R. Crane Nuclear Plant Support - Farley

SUBJECT:

D.C. Panelboards Mounting Requirements P.O.

  1. FNP-249 I-T-E S.O.
  2. 18-93210 Gentlemen:

In response to a question by Mr. Cary Martin in your Electrical Design Department, we have the following information. Cur factory QA Department has investigated the conflict between four mounting bolts and six as reported in our seismic certifi-cation and test report. We state that a minimum of four (4) 3/8 inch bolts are required. After investigation, four bolts are suf-ficient, even though the test states that six bolts were. sed. The two additional bolts'were not load carrying ones. These were used due to the particular fixturing in the tests. Therefore, with respect to the seismic stresses, mass of the specimens, and the number of bolts required, our certification and requirements are

covered, i.e.,

minimum of four bolts required. Yours very truly, GOULD-BROWN BOVERI ~ s/ (n/, h,3 S-N- .6 l^ ~/ / '/ John T. Hutto, Sr. / Senior Electrical Sales Engineer JTH/sc R~.C.C$1'!ED cc: SCSI - Cary Martin q t l x.ao s unc tMT.i T/u ....r SUJ307U . _;.gp A. n f. 'l'd

  • IANW i

,f e T o-h h h' I-to p e d = e-* 5 b I** e + e e - -~ -,

-ITEt4 5 - SOLEf1010 VALVE The manufacturer of the solenoid valve has provided additional informa-tion about their seismic test report. The test motion was described as basically sinusoidal. The duration of the test motion depended on the maximum G level that was obtained since the test was continued at increasing G 1evels until failure of the valve occurred. The valves were operated at the varicus G levels. The exact duration of the input motion was not recorded - but from the description of the fragility test, it can be concluded that the test duration is more than adequate. The solenoid valve was not tested below 20 Hz since the manufacturer has previously determined that no natural frequencies exist below that value. To assure that the method used to support the solenoid valves does not negate the fact that no natural frequencies exist below 20 Hz, the valves will be modified by niounting them directly to the seismic supports with suitable brackets, a

ITEM 6 - SERVICE WATER PUMPS, (a) Seismic restraints have been provided for the Service Water Pumps manufactured by Johnston Pump Company as required by the Seismic Analysis Report. The following documentation is prcvided as information on the installed seismic restraints. eDrawing #U-209741D " Sectional Illustration Service Water Pump." This drawing shows the seismic restraint and how it ties to the pump and concrete wall. eChange Notice SC-257. This is a field change to install new anchor bolts for the Unit #2

pumps, eDrawi ng 0-171336, Rev. 3 " Outdoor Concrete -

Service Water Intake Structure Wall Sections Pours 2 (A thru F & K). Revision 3 shows relocation of the Unit #2 Service Water Pump seismic restraint anchor bolts per Change Notice SC-257. (b) Hydraulic reaction forces at the output flange of the Unit #2 Service Water Pumps were not considered in the seismic analysis of the pumps because the bellows connection on the output flange is secured with tie rods in such a way that the bellows act as a solid connection, thereby allowing the hydraulic reaction loads to be in balance. The result is that the pump will not experience any forces from hydraulic reactions at the discharge nozzles.

m._ " 7j .2 2 e ..O I kt jp.,/1 ~ ,.4 4. y y -(.%, 9 - p ' 14 - 4,..; -;;, q p b 'D - = i.'. ; 7 g, f i .T'.t". - t. .. 1


4....

r-T & [.#"* e.,* e. ./, ,A ',. l g.g g 1 . ") e 5-5,, n. r , o r. .s 7 ef. a i W,8 f f, W. f 60s I a.0 .r n i.. I,[E t .3 .k~ t

  • 1.

[

t.
  • f.. uw 8

,,.t < :.., 3 m,. :rcr.k t... I. 4.4 t. M z. 'Q . / \\ 3 p m r \\ \\ etr m b -- b, s.e - - s s..

y..

\\ l. g f: ! w.a..c?. : *"-~ h. ..---.n

  • s -
h-

- 3:. 1 s. x 1 .4 j e.e. j.

p..

~ .s .g. (6i 7e.* - E., s: . st:,oJ.I '-% t t. v. Lt. 1 - 'k i .W:1, s s .e g. r 4 s s .1 n .iJ7* ,t 1 . lh.'. s I, s ,p

s.... -

, Q, q .i. '.y s,j' ' * .,. j.. 3, '., p;f )- i ,k '? g, ? ;,, w 3 ..c.. -., f,. .. y. kr. /. / 7]1 8 c U., / :.-- %+i. f., \\. a I* , s. ,i t .r. [e.

s. j -

U S

rf,n. V ; 's r1

) r. ..e u v .L-) I , ~. ~ "~ ~ \\'- ] [ D. /,

  • .j p, -

,k//e,. '."r,.. . ?, . I y

s.. '

.] r.s:

  • )~

t....

e..a -

w-.. ~ -,/ ' I d,. i-i? .a a.. ~4 f.. sec.ncs s.e r.., .'j;~1.. '. -

/

~ r 6 s. I4 . g )g: i.. ..( 3.. .m v, .,.L. :,x Ti. r-i s - o C4 ]j/ ,Q..;;','s. g y A -* ..; s y ..4.. ,;.u;",/ n ~ W

T s... < ' S.. C '. '

d1 i z. n-3 ~ 1 I , [.f J., x i . -.... ~,. o f. j'~; s V ""' _Q'... ' >, ~ ; g .,r-O

a..

o ,:.t.A 7 ~ a.,. Q.>. Qo'.. ~ n .s. g su. t* .< 3. a _ ;.. g Bg. :j !r o,...,,.. ,...,,.,, q,5 - g ~. - . n. f .,,, e. .,.s ~. s. u '.8 _,,%.-f *f !,,G.j-h i ,'} g_. c_. . ~; ., s f.....{ f. f M. Y S**I"'-7-Q-] ' ~ 7 1,'. -}. ((.., - M .:5 p i 4 sv. - .. ~..,.. r. = g .m Bi: h. l...-:*.. :..a w 1 c =.k i 2 L i -= - i l.h i h E..v 1c i 4 3 p-

=

1 1 O O O r.;. T ::o B f .e., y z e p.. .o o 6 4.I f I I c- >= :: i .e i. z c [ t[ [ [ 8 .a , -. 7:. m g i s ~. s. A a i .~ j g .I -. 8s c, rc g :. { at [ .x 2 J. > r; 1 c=.: o c. P } [t i., g ( t i 1 I c.3,.- g< = s [ 3 3 2 s i 2 11g y [ 4,: -c

i. t I,

E;s me,. n m,, = c [.s z i i i n-2 .e c> v J In l = --q.'. $ :3 $=2 I C O ,t l 2 f"" l [ l3 1-< p. ! ! T a ,,. gg 3 1 i: c 1 1 E n e a. z r $~ E W N b

t

  • y g, -..

, / '.s,r**e y

  • .g.

,s,e.. .c .e J

  • o

,t. toy.s. n. t.t ;9 .i.- 's r i r 8 ' * ~~ e-g 4 (I \\, \\

  • f e.

I f e... s..,-.a v.. v, e,v. s. ary a.. ), l .a f f .n t f c: .,I N.

  • ,,- ja

\\ t ss s s b,

  • s f.
, g th.

.l sY,& N. I *

  • r/
  • 4 P:

9 f. 4 O O . :. al..h.. ,. L..,.j .e .,A, - g, p " 1

  • = -

s - - - = N. y ' f- '""W gf,e.s* 9.t s.s w - 9

  • * %. Q..u ),1 r

~ k 2 %.. g f. 7 "., '4.. p v. ---'l N., Pa - a n - I ss ....d -..........l .....%,.%.,4,.L.1,.& %,3., D.e l ........r_ _v .e . 4 s.r n., f.......,. egg W.,. 4. ..n s, ..s. o 1 e. ..,,' g .sl.- n ~ = .d . w.;. - .u .s

e..

g p s 8"'. g *,, \\ , I '< ' \\,* {- s 't u. .... m.'s - ( t s .,/ - s t g. / .g ,o. sq sm.e so. o... g e t.s .e. 1 r i s-j..v ts Ar.s er. a + t- -.4. r a. ._*4w.w; *" a.:,i ne.< p j.'. [ './ l e 'N l J M, 2

  • G b i'F.N

,1 ? -l Is 1 . ~. d .E J.,' r \\., e., s . s,.. 1 .e,. c. n 4g q, r1 l E Q u p*' ~ * '*( .x e .f,.... .p '/ {T*T' s-r l. CrW7*

  • .* L

.s. ;T. - ,?,.,., i ;e i I. .s... . 4 .,,v;..,. ..o g

3...
'. *. l rpJ..,

g* .s y, e.f ~

b. ;

g. ' '. ' {

y..~,}.

l . '.,. y p. ",j,. l, . F ~ - \\,, .., -. ~.. ; .m. c.. 4. r,. s ..,..i.,

g. :..

... I,, f,., p* v .=

9.. z g.

....s-L , L..-.. s. ,. ~,.,.,.

o. TS.

. s... 3 .. r f. t >: g .. -.s 3 c .a-q. 3 .>. Ja. <..../ .. 4. g,.

  • f

.q:. .s..~~. 1, ....,. s -...- *3 1. g... c. .,e . T,*....... .3

  • s.

F.

  • ,.5

..s 3:. %...,....,..._f_..u i ,s. .1 .(.-..;,.' *.. a,, *;, ..g, ;.,

.?...

.F.w.m..,; < i.

a...

r* e

.. /.

.,r .o s. s w. .f,, -. t. ....c- . s

s. t..,..

.. c... .,.. ~ 3e....-, .f g . s.. n,. * . ~- n.,.-. y ,. ~.. ...s -.. ". ~..... . e..,- r,, y, n

  • p.,

.r. e

w.. '...f. f

[.W '_ * '. Q &.',' '$... {. ~. - *. k jll.,:.'.,)s. .'l, - I.* *. 3 ',L g.I,. ]. ;.. - - A ....,;...g., .s' - 4.. e w: -.,... ; r r;-....-....:. -..... e.... .. ~- '.'.e% .s *. - l &; 4..- - ~, ~ ' ':.-l~.-

,,. *,,.. Y *y*a -%-*,'.,.

li K.. i-Q. * ' %. e - s,.. s. 5t f* i p ,c. ,ae, ^= ,',,,.Y,d.,

r
  • y v

..; " '~, J. -f.. .g*.,.. e y. ...?,. ,, m '/

s..,e, g g - tt. y e

.,..g.....-.;..,.s4.* ,.p,.,- .,,,...,., ) t. t- ....,. t..-

l...

e i. .,, _, --.. g .. e... ym......~.g, ..r.

g...

= +- -

,.n..

. r ".. -}... s. .t s.... p... .. k., '.., .=. .y {'m... .s.** ,e, ..,. ~ ~,.. ,.,. ~..... *. .,*; 6 .*r.,.,... .e .a 4 .,.., ;,. n . t ~ ,L. .a,. ..i... .5.< -.s .'. s. 's .,.:.. s. %, '-N3M. pp. - ).* s, 6. ,.e.- . e '..., e .-,.,...3.. p p.. .c * -, . ',o.,- c s .e a ..s. ,u .e ,s..... .t-1 '.ra-- .r. ..,f,"'., r-s t, g.. s n .,,.. I r. r * - - - : - -. ' ...... / *.>. 3

1..

trin vs. 1 ,:.~ .f,y,!,. : ------ s - - - -. ' i. ', 7 ~ T. n... y. .h...,,. C...,..

a..;. v.,c q.. L.L..

-~7 4,,. c. c. e .-,.'.N,'.* -Q... Dq5.' 2.'. - * )

  • e.,... 'f".g *. r%...

l- . ~ - ,.[r

  • 8; 4

.>.i* * .4, .. (. -

s..

,a.. ..., s pr....... ., f,..$,,;,l. b. .1 - e.,....,...(, .N .g p g. . s. -r-l

  • . s s
  • t'.,

. t.. p ,.\\ . 1 *; "~.n %.ll d... h.,, '.- 1 ..... -.t t,.

  • ~

- -e..a' 3,. N. _ s. '...,.t..',,..,.

h. m.s a

.t-.- [ ...s., 1.:, .,.~ ,s..,.- .p.... ..j. e,. ...v..... m f.% l .s q .. s}...e. . s.f,. p,..

1. 3 *

.{. r. a ,,4.. .s n. a.

  • g.

,s.., s. t . r .,z...... ."..).,......~.a '4j. g*. ,t F .W. -... .g-oi.w n. 9,.. - s .....s .,r. . w ,w 4 . v.... ..s.. r.. -.. e. m. . e u y - :. ;... _f.< . b,,,. :.,,,.. 4 t..._........s t. u . 9.... ....w. s.. n -. 6 3 .e -.- - F-,a %s ' Y.v.r.m:.a s u.- vq-i,stm

  • H,O-h,.I.

{s. 9 I' ,' '. I,- I l ; s. *,-, ~~ es m.,,,,,

Jne. 1 FIELD Ci'At GE REOL'iST FCR NO. C-1092 Joseph M. Farley fluclear Plant - Unit

  1. 1 Date :

8/s/7s Field QC f rocedure.No. 5. 3. E. l A TPflS tio. A17.07 j ~ 0-17133e Revision 9 Drawing I!c.: ~ Orawing ii 1e: ouTDOCl< cor<'. SWIs System, Addressed To: APC0 Constructic,n - Attention Southern Services, Inc., - Attention R. rcwELL BSc tel Corp a tion " ttention 4 m Origina tor : .h PCE: ba ',QCl4.I f/ /p ( s-u i E'istina Condition: x e a ', ".. ANCHOR BOLTS MARK A3-3's FOR THE SEISMIC PISTRAINTS ON THE UNIT #2 SERVICE e. r WATER PUMPS WEPI INSTALLED ACCORDING TO DESIGN DRAWING D-171335. VENDOR DP;. WING U-2009714D INDICATES A DIFFE?INCE OF APPROXIMATELY 2 FEET IN ELEVATION AS WELL AS a DIFfERENTBOLTFATTERN. 9 ,{ [}T6 N 3fT % ' }3 AUG 8 1975 i, Recor" ended Action and Resconsible carty: ~ SOUTHERil SE.^3!CIS, !!;0. l STR. & !.R0H. DE?T. ...RECCMME';D CUTTING EXISTING ANCHOR BOLTS OFF FLUSH WITH FACE OF WALL AND ~ GROUTING FCUR ('4) 3/4" DIA. INCRGANIC' ZINC CCATED THPIADED KCDS PER ATTACHED SKETCH. C g RUCy, R.F.('.F.lVED o v3 r URGENCY: 8 AUG 6 1975 7 h (1 ) tiEEDED BY 8:00 AM Oil 9/7/75 (Time) (Da te) A-IENT COW (2) JUSiIFICATICN PUMPS AFI !!CW 3EING ASSEMBLED FCR !!!STALLATICN. APC0 ti?D Reply: Dispositi:n Reference Ct! f:o: QC Hold Tag Nc: (If AppTica::le) Distribution: CC FCR Suspense File, ATC0 QA Fleid P.epresentative, APC0 fG), Construction Superintenden:s.

s.o na em

i..

,u y y u tass-y Ewms Asw) = =- i M M M 'a' s,-v c -a;w a.a T-Et.a55. Oh I _I N I I l 'i T T T ( Et.. t55' l'/z. bas ~ToStAoOcb f Tw. 5 htsd. Devat coma.wT or WAu_. Pou2. 2.0 zu onrsw \\ Wt. To E t R epe.atto A vvez Lc. won. Bees ku.Cwr ]s

  • P' a nun J

r g l o' b EusTmq l'? AS.3 i .b i u a D* b. 6 3/(Q Tatst.ceo ?s,~hteue be P2.oa2c_T C-E p 2 @ u e u., At_t. % Tu b. 3 /m 52mt Geoc Ar c:. M lo \\6 -} E c e s B u. L s u t.t.c.c A ) m h, p NoTt.Tutst Socs To S: Cor tco h Leuwt h:_ W L1tu Or Cwt.vmu.ma. .s

  1. m m.s.t so w n so.x L.twc. r w.

A s emeur % FC_2_ Ce \\Oc32 ATTw. R. Pwa.t_- SSI - -. =. = = = =.... - -. - - =. =....... -.. =..... -.. e.s.ns

/*<...o g> .CMA GN E NO7 ACE NO e,c-M 1 DATE b = % t W JOSEPH M. FARLEY ilVCLEAR PLA!iT-U:1IT t!O. ( SHEET CF SHEETS ORIGINATED BYD.WE\\ (.cOc,k _b - DIRECTED TO_kt,!\\QM4.%._7cwED. (_c. COF1ES TO d2.DjhqE,O - Q133.19_JMCo.-.b.'.RNti\\_ } \\'lslbl.inD ST.G.Cl J.: REV. NO 3 APPLIES TO DWG. NO-TITLE CF DWG O_o t R C.D.n_ f.o M r._~

  1. N ll.h (OR OTHER DOCUMENTI APPROVED
    BECHTEl NOT b 41D SOU. SER\\'dske_(CE4.M~c.//ECR t'O. _C._1CeyL DATED %CS't_.S@*2'I _DATh_%CW k N"7$

DATE PROCEED WITH CCNSTRUCT!CN CHANGE AND PROMPT REVISICN OF DRAWING CR DOCUMENT. ~ ~ ~ ~ i ~ lI: I l l l l !iii ! Iii i i l i [ T-[ I l l l 9! j II I i iI i .I i i ,it l l r 1 -{ I l t i l l l i i t) 2---- Nk I ! - G C,O MMC-MD G.D._3f Ti o ti._. AS PEG,..'.?CS.- C. _.10%/ t-l s l f f k I l i l I l l l l l l I l l I I I I i l i !'i id _ b phe. h,_! M i l j l g l e + i i l l i i i i I i g e i i l l l i i I l r i i I i i l i i i l e f e i g 1 y '.// N.b. ' D.. NU b30 b. -. SD .E. i l e ) e.__! L l l l l i i I l l i i i i t l i i i m = S 6 \\ N. bg _ h _h 6 ___k.. f D )D /.,g. N)(~\\ . k "_br_ _._... y., m f E i l l I i a i i i ' __.6 W D G D U @ d T. I 9 10 (:n T N.,e 3 I I l i i i i i l I i i i i i - r. ~t .--)-- l l l l l I l i 1 I l l __,. y ._._5_- -.L_..._'_.._..

._.2__:.._.,.....

i l._ ("E6b6NC6D ) be. II,,h h E.. k l l _.. ' _. - l i i I i {'__l j I i - e_ __1_... h l A-l f f l l i i --- - -- t l f I i ff i l i l l l 4 s_ L L .L l l.. __. y-1 _7... l l l .I I I I i i F' t l I l I l I I i ,..,..__..._._.7., k l f I I i r-- !. 3... f' k fl l I ._......[. -.... ' -.., - -. -. -.. _.. ' * ~ ~ .__..T~~ !.' ? '.* ;' *-. 3 a m... m i p._ b ',*.., l I ") . _.f. ! j l l I i ..y 7( I l I i I i l i l i j h . j

4. _..

t I ...i l a o s i L_......._;. L .. _i..

ITEM 7 - 4160V SWITCHGEAR The contact chatter described in Allis-Chalmers Test Reports 40012-PR-3004 and 8971-ST-937 dated January 16, 1973 has been analyzed and found acceptable. The rationale for acceptance is based on the fact that none of the chatter spikes were greater than 10 milli-seconds in duration. Both relays producing chatter are connected to shunt trip coils in circuit breakers. These shunt trip coils are highly inductive, and together with circuit resistance, pro-duce an R-L time constant of 50 milli-seconds. As a result, the short duration contact chatter spikes are effectively filtered out, and the shunt trip coils do not respond.

ITEM 8 - DIESEL GENERATOR The CFVB Voltage Balance relays in the Diesel Generator Relay Panels experienced contact chatter during the resonant frequency search of the seismic simulation test report performed by Wyle Labs. This chatter does not constitute a problem with regard to the safety-related functions per-formed by equipment within the generator panels because revision 1 of specification SS-1123-13 dated February 20, 1974 in section 10-1 exempts CFVB relays from seismic requirements. This exenption is acceptable because the CFVB relays are isolated and not used in the emergency start mode, and cannot affect the operation of the deisel generators while in this mode. They are used only in the test mode of operation. 7, n w c-v r

ITEM 9 - RELAYS FOR DIESEL GENERATOR PANEL The normally closed contacts of the microswitch attached to the Agastat relay exhibited contact chatter during the seismic simulation test performed by Wyle Labs. The microswitch attachment was included in this test to establish its fragility level for use in other applications by the manufacturer. The Agastat relays used at Farley do not have these switches attached. 9 i .s J -, ~_. .._-..-__.._.._,-.-.o_.....,,__

4 ITEM 10 - FLOODING LEVEL SWITCHES Based on the test results performed by Ogden Technology Labs, it is concluded that the subject level switches will withstand and function as designed during and following a seismic event. The level switches are used for alarm purposes only and at worse would initiate a false alarm if there was contact chatter. However, the annunciator system has the capability to indicate to the operator if and when the trouble clears. Therefore, the question concerning the contact chatter of these switches presents no problem with regard to any safety-related function. . _.}}