-State of Illinois
-Department of Public Health ATTN:
Mr. Gary N. Wright, Chief Division of Nuclear Safety 535 West Jefferson Street Springfield, IL 62761 Gentlemen:
The enclosed IE Information Notice No. 80-29 titled " Broken Studs on Terry Turbine Steam Inlet Flange" was sent to the licensees listed below on August 7, 1980:
American Electric Power Service Corporation Indiana and Michigan Power Company D. C. Cook 1, 2 (50-315, 50-316)
Cincinnati Gas & Electric Company Zimmer (50-358)
Cleveland Electric Illuminating Company Perry 1, 2 (50-440, 50-441)
Commonwealth Edison Company Braidwood 1, 2 (50-456, 50-457)
Byron 1, 2 (50-454, 50-455)
Dresden 1, 2, 3 (50-10, 50-237, 50-249)
LaSalle 1, 2 (50-373, 50-374)
Quad-Cities 1, 2 (50-254, 50-265)
Zion 1, 2 (50-295, 50-304)
Consumers Power Company Big Rock Point (50-155)
Midland 1, 2 (50-329, 50-330)
Palisades (50-255)
Dairyland Power Cooperative LACBWR (50-409)
Detroit Edison Company Fermi 2 (50-341)
Illinois Power Company Clinton 1, 2 (50-461, 50-462) 80081808N
4 State of Illinois Iowa' Electric Light & Power Company Duane Arnold (50-331) 5
[.
Northern Indiana Public Service Company Bailly (50-367)
Northern States Power Company Monticello (50-263)
Prairie Island 1, 2 (50-282, 50-306)
Public Service of Indiana Marble Hill 1, 2 (50-546, 50-547)
Toledo Edison Company Davis-Besse 1 (50-346)
Union Electric Company Callaway 1, 2 (50-483, 50-486)
Wisconsin Electric Power Company Point Beach 1, 2 (50-2e6, 50-301)
Wisconsin Public Service Corporation Kewaunee (50-305)
Sincerely, H len Pap as, Chie Administrative Branch
Enclosure:
IE Information Notice No. 80-29 cc w/ enc 1:
Mr. D. W. Kane, Sargent & Lundy Resident Inspectors, RIII Central Files Reproduction Unit NRC 20b AEOD Local PDR NSIC TIC
a' SSINS No.: 6835 I
Accession No.:
UNITED STATES 8006190028 NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.
20555 Si August 7, 1980 IE Information Notice No. 80-29 BROKEN STUDS ON TiRRY TURBINE STEAM INLET FLANGE When removing the governor and stop valve on the Unit 1 steam driven emergency feedwater pump at Arkansas Nuclear One for repair of a steam leak at the steam inlet flange Arkansas Power and Light discovered that five of the eight studs securing the flange were broken.
The cause of the stud failure is unknown at this time.
Metallurgical evalua-tion of the failed bolting will be performed to identify the mode of failure.
The failed studs are 3/4 in. diameter by 3-1/2 in.
long and are thought to be of ASTA-193 grade B7 steel. The turbine flange bolting is generally covered with insulation and not visible for inspection.
From the information available, the bolting has not been removed or inspected since installation seven to eight years ago.
The steam driven emergency feedwater pump turbine at ANO-1 is a type G turbine manufactured by the Terry Steam Turbine Company of Hartford, Connecticut. The turbine is rated at 680 BHP and 3560 RPM.
The turbine operates at a reduced steam pressure of 270 psig and temperature of 400 F and has'previously experienced overspeed trips and vibrations which may have been caused by slugs of water from the piping.
Licensees are encouraged to carefully examine insulation in the flange to turbine casing region for evidence of leakage and consider inspection of the l
turbine steam inlet flange bolting.
Further, during surveillance testing, care should be taken to observe if abnormal vibration or other transients I
occur which could promote loss of bolting integrity.
This Information Notice is provided as an early notification of a possibly significant matter.that is still under review by the NRC staff.
It is expected that recipients will review the information for possible applicability to l
their facility.
No specific action or response is requested at this time.
If l
you have any questions regarding this matter, please contact the Director of the appropriate NRC Regional Office.
l l
l l
l t
en e -
e, w ew. --..
=
I IE Information Notice No. 80-29 Enclosure August 7, 1980 RECENTLY ISSUED IE INFORMATIOR NOTICES G
.Information Subject Date Issued To Notice No.
Issued Supplement to Notification of 7/29/80 All holder of Reactor 80-06 Significant Events at OLs and to near Operating Power Reactor operating license Facilities applicants 80-28 Prompt Reporting Of 6/13/80 All applicants for and Required Information holders of nuclear power To NRC reactor construction 80-27 Degradation of Reactor 6/11/80 All Pressurized Water Coolant Pump Studs Reactor Facilities holding power reactor OLs or cps I
80-26 Evaluation of Contractor 6/10/80 All Part 50 Licensees QA Programs 80-25 Transportation of 5/30/80 Material Licensee in Pyrophoric Uranium Priority / Categories II-A, II-D, III-I and IV-DI; Agreement State Licensees in equivalent categories 80-24 Low Level Radioactive 5/30/80 All NRC and Agreement Waste Burial Criteria State Licensees 80-23 Loss of Suction to 5/29/80 All power reactor to Emergency Feedwater facilities with an Pumps OL or CP 80-22 Breakdown In Contamina-5/28/80 All power reactor tion Control Programs OLs and near term cps 80-21 Anchorage and Support of 5/16/80 All power reactor Safety-Related Electrical facilities with an Equipment OL or CP 80-20 Loss of Decay Heat 5/8/80 All light water reactor Removal Capability at facilities holding Davis-Besse Unit 1 While power reactor OLs or cps in a Refueling Mode
.... -.. ~..