Submits Revisions to Re Control Points for Initiating Condenser Leakage Location & Mitigation Procedures.Control Points Proposed for Condensate Pump Discharge & Hotwell & Steam Generator Sampling Points
ML19330C688
Person / Time
Site: Farley 
Issue date: 08/05/1980
From: Clayton F
ALABAMA POWER CO.
To: Schwencer A
Office of Nuclear Reactor Regulation
References
NUDOCS 8008110339
Download: ML19330C688 (2)


Text

1 bi*?, *?.M?h?.,*

D sh$: NceSc[dNi 3 rm ; nam. Alecama 35291 Te.eanone 205 323-5341 h

hbS^;T;L Alabama Power me scawn e:ec:::c sys:er, August 5, 1980 Docket No. 50-364 Directer Nuclear Reactor Regulation U. S. Nuclear Regulatory Commission Washington, D. C.

20555 Attention:

Mr. A. Schwencer RS: Alabama Power Company's letter from F. L. Clayton, Jr.

to A. Schwencer on July 28, 1980, concerning Unit 2 Steam Generator Tube Inteerity Gentlemen:

As a result of discussions with the h"dC Staff, Alabama Power Company revises its submittal, dated July 28, 1980, concerning the control points for initiating condenser leakage location and mitigation procedures (Abnormal Operating Procedure -25).

The control points, using cation conductivity as an action parameter, are now proposed to be the following:

1.

Condensate pump discharge sampling point 2.

Condenser 1otwell and steam generator blowdown sampling j

points.

The condensate pump discharge sampling point will require the addition of continuous cation conductivity measuring capability with i

appropriate alarm. This is scheduled for completion prior to full power operation.

In addition, feedwater impurity-time operating limits, utilizing the parameters of pH and cation conductivity, have been incorporated into condenser leakage abnormal operating procedures as specified in our submittal of July 28, 1980.

$ bel

\\

S

/0 8008110 3 8 9

.. ~

~..-

. ~. -

e j

.' d h-

' Director I

4?:

Nuclear-Reactor Reg'Alatica.

2 --

August 5, 1980 e

s-1:

=

T:

4 t

f l

If there are any questions concerning this item,-please contact.

i us.

f.

j '-

.Very truly yours,.

k fl

~ -...

~

f F.L.Clapi:en,~ir.

t-I-

-RLG:de

+

'cc:

Mr. R. A. Thomas Mr. G. F. Trowbridge Mr. W. H. Bradford -

U Mr. L. L. Kintner 4

i 1

s.

f e

i-

{:

i

+

i i

l.

l I,

il k

4 y

f

-.t--

e r

l20

.1 -,,; _ _.;..

__;--....., _, - -...... :.__.....