ML19330C378

From kanterella
Jump to navigation Jump to search
Forwards LER 80-023/03L-0
Date released: 12/10/2019 Download: ML19330C378


LER 80-023/03L-0:on 800709,during Test of Steam Driven Emergency Feed Pump P-7A,main Steam Supply Valve CV-2667 to P-7A Did Not Fully Open on Demand.Caused by Valve Operator Torquing Out Early.Torque Switch Given Small Adjustment
ML19330C384
Person / Time
Site: Arkansas Nuclear Entergy icon.png
Issue date: 08/04/1980
From: Bramlett L
ARKANSAS POWER & LIGHT CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
Download: ML19330C384 (1)
Forwards LER 80-023/03L-0
ML19330C377
Person / Time
Site: Arkansas Nuclear Entergy icon.png
Issue date: 08/04/1980
From: Trimble D
ARKANSAS POWER & LIGHT CO.
To: SEYFRIT K V
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
Download: ML19330C377 (1)