LER 80-023/03L-0:on 800709,during Test of Steam Driven Emergency Feed Pump P-7A,main Steam Supply Valve CV-2667 to P-7A Did Not Fully Open on Demand.Caused by Valve Operator Torquing Out Early.Torque Switch Given Small Adjustment