ML19330A581

From kanterella
Jump to navigation Jump to search
Forwards Revised LER 79-084/01T-1
Date released: 12/10/2019 Download: ML19330A581


Revised LER 79-084/01T-1:on 790806,containment Air Coolers Svc Water Outlet Valves Failed to Meet Response Time.Caused by Undersized Air Opening on Pneumatic Actuators.Valves Forced Full Open.Actuating Mechanisms Redesigned
ML19330A589
Person / Time
Site: Davis Besse Cleveland Electric icon.png
Issue date: 08/17/1979
From: Rudolph J
TOLEDO EDISON CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
Download: ML19330A589 (2)
Forwards Revised LER 79-084/01T-1
ML19330A580
Person / Time
Site: Davis Besse Cleveland Electric icon.png
Issue date: 07/23/1980
From: Murray T
TOLEDO EDISON CO.
To: KEPPLER J G
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
Download: ML19330A580 (1)