Responds to NRC Re Noncompliance Noted in IE Insp Repts 50-329/76-09 & 50-330/76-09.Corrective Actions:Broken Rebar Inspected & Identified as Nonconforming.Instruction FIC-7 Will Be Revised.Inplace Maint Will Be Covered in F-10
ML19329F344
Person / Time
Site: Midland
Issue date: 01/27/1977
From: Howell S
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
Shared Package
ML19329F337 List:
References
HOWE-15-77, NUDOCS 8006250430
Download: ML19329F344 (5)


Text

%A 9 [%

Czeumers

' M : r.3 =

i n

.'u.. ul

\\

[]'

1 Stephen H. Howell Vice President

. General offices: 1945 West Pernell Road, Jackson, Michtgen 49201

  • Aree Code 517 788-0453 January 27, 1977 Hove-15-77 Mr J G Keppler, Regional Director

' Office of Inspection and Enforcement US Nuclear Regulatory Commission Region III 799 Rcosevelt Road Glen Ellyn, IL 60137 MIDLAND NUCLEAR PLANT - NRC ITEMS OF NONCOMPLIANCE -

INSPECTION REPORT NO 76 DOCKETS 50-329 AND 50-330 m

(

This letter is in response to your letter of December 17, 1976 which trans-mitted the results of your inspection of the Midland construction site on November 16-19, 1976 and which requested our written response on two items of noncompliance.

gmdb e

t

)

N.,_,/

8006250 kN

  • ~

/

CONSUMERS POVER COMDANY RESPONSE

\\s-TO ITEMS OF NONCCMPLIA:!CE DESCRIBED IN NRC INSPECTION PE? ORT #76-09 I.

Failure to Identifv Broken Rebar as Nonconforming A.

Descriptions of the Noncemuliance 1.

From Page 2 of Report #76-09:

" Contrary to Criterion XVI of Appendix B to 10 CFR, Part 50, and Con-

~~sumer's Poier" Company Quality Assuranc'e' Policy No. 15, a Nonconformance Report was not written to identify the reinforcing steels that were broken due to bending for equipment installation access.

This infrac-tion applies to Units 1 and 2."

~

2.

From Pages 7 and 8 (Item No.1) of the report:

"10 CFR, Part 50, Appendix B, Criterion XVI, states, in part, ' Measures shall be established to assure that conditions adverse to quality such as... nonconformances are pro =ptly identified...'

The CP Quality Assurance Policy, No. 15, Rev. 3, dated December 1, 1975, ' Nonconforming Items,' states, in part, that 'Ite=s, services, or activities which are deficient in characteristic, docu entation, or procedure which renders the quality unacceptable or indeterminate and which is considered significant to safety, are identified as noncon-formances. Ncnconforming items (structures, syste=s components, parts, I

materials) are identified by marking, tagging, segregating, or by documentation.

Nonconforming items are controlled to prevent their inadvertent installation or use.'

O(m/

In addition, Bechtel Power Corporation QC Notices Manual, SF/P,SP G-3.2, Rev. 1, dated June 28, 1976, titled ' Control of Nonconforming Items' Paragraph 3.2 Control of Nonconfor=ing Items, Paragraph 3.2.h (Partial)

I.

Failure to Identify Broken Rebar as Honconfor=ing

[h' A. ' Descriptions of the Nonec=cliance

%,J -

2.

(Contd)

'Nonconformances discovered after final verification inspection of completed work shall be reported, controlled and dispositioned by the use of a Nonconformance Report.... '

Paragraph 3.4 Installation and Further Work on Nonconforming Ite=s,

' Nonconforming items documented on a nonconformance report may be released for installation or further work subject to the following condition:

i (1)

(2) Traceability and identification as a nonconforming item are

()

maintained by tagging or other appropriate methods so that the item can be removed or corrected at a later dato prior to use. '

Contrary to the above requirements, the inspector observed that two No.11 rebars and one No. 8 rebar vere broken because of bending for equip =ent installation access at east and vest sides of the Engineer'ing Safeguards roons in the Auxiliary Building, Floor Elevation 586'-0".

The identification and docu=entation were not available for review at l

l the time of inspection.

This is considered a nonco=pliance ite that I

requires resolution by the licensee."

B.

Pertinent Background Infor=ation While the reinforcing steel had not been identified as nonconforming at

(}

the time of the NRC inspection, it would have been identified during the preplacement inspection made by Bechtel Quality Control prior to placing any concrete which would have embedded the bars in question.

l

3, I,.

Failure to Identify 3roken Rebar as Nonconforming (Contd)

C.

Corrective Action 1.

Bechtel Quality Control has performed an inspection and has identified all existing broken rebar (dovels) as nonconforming in accordance with SF/ PSP G-3.2, " Control of nonconforming Items".

2.

The Eechtel Project Field Engineer vill revise field instruction FIC-7 by January 31, 1977 to instruct all Civil Field Engineers to identify any broken rebar to Quality Control.

Qaulity Control vill then identify these broken rebar as nonconforming in accordance with SF/ PSP G-3.2.

II.

Reactor Vessel Skirt Hold Down Studs Not Protected After Insta11ation' A.

Description of the Nonces;11ance 1.

From Pa6e 2 of the report:

" Contrary to Criterion XIII of Appendix B to 10 CFR, Part 50,...

v hold down studs for the reactor vessel skirt were not protected, following installation of the embedments.

This infraction applies to Unit 1 only."

2.

From Page 13 of the report:

"Two concentric rings of studs which vill hold down the reactor pressure vessel skirt after setting of the vessel vere not uniformly protected from corrosion or damage from falling objects. These seismic Class 1 l

studs were installed in the embeds and surrounding concrete.

In two studs the threads were open to the environment with no protection.

Of the remaining 9h studs some were covered with tape and others with

~

~

l a netting material.

The contractor had instituted a storage ievel of'

'C' before installation for these studs which required either inside storage or outside covered storage and surveillance every 30 days.

~

After installation, a continuing progrs= for corrosion protection and other protection, as required, should have been instituted but was not."

-o le 9

Reactor Vessel Skim Hold Down Studs Not Protected After Installation (Contd)

GI.

i B.

Pertinent Backeround Information In the interest of accuracy, it should be noted that the studs in question are in Unit 2, not Unit 1.

The Unit 1 studs have not been installed at

...this. time.

s C.

Corrective Action Bechtel Field Engineering vill generate a F-10 form (Maintenance Require-ments) to cover inplace =aintenance requirements.

This F-10 vill include requirements for protection of the bolts and periodic inspection. This F-10 vill be irsued and protection completed by January 31, 1977

[(

s 0