ML19329E330

From kanterella
Jump to navigation Jump to search
Responds to IE Bulletin 77-01 Re Pneumatic time-delay Relay Setpoint drift.Safety-related Circuits Reviewed.Type 1972 & 1973 Ite Imperial time-delay Relays Not Used at Facility. Pneumatic time-delay Relays Used for Alarm Purposes
ML19329E330
Person / Time
Site: Midland
Issue date: 06/28/1977
From: Howell S
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
IEB-77-01, IEB-77-1, NUDOCS 8006120639
Download: ML19329E330 (1)


Text

_

1

  1. M h

/

l 5

,s UUY Stephen H. Howell Vice President General of fices: 1945 West Parnall Road, Jackson, Michigan 49201

  • Area Code 517 7884453 June 28, 1977 Mr J G Keppler, Regional Director Iluelear Regulatory Cor=ission Region III 799 Roosevelt Road Glen Ellyn, IL 60137 IEDIAID PROJECT DOCKET HO3 50-329, 50-330 IE LULLETIN 10 77-01 FILE: 0505.2 SERIAL: 3900 Your letter of April 29, 1977 transmitted IE Bulletin Ho 77-01 which discussed pneumatic time-delay relay setpoint drift and requested that Consumers Power Company respond within 60 days of receipt of the Bulletin. We have reviewed our safety-related circuits and have concluded the following.

1.

Presently ve are not aware of any ITE Imperial time-delay relays of 1972 and 1973 vintage of the types listed as being used in the Midland plant.

We vill take precautions to ensure that no equipment purchased in the future contains these relays.

2.

The majority of the pneumatic time-delay relays used in safety-related cir-cuits are used for alarm purposes only, and serve no safety functions.

j l

1 3.

The vast majority of the pneumatic time delay relays used in safety-related functicas have repeat accuracies of + 10% or better.

i l

h.

The suppliers of pneumatic time-delay relays with repeat accuracies of +

15% vill be requested to supply alternate relays having better accuracies.

liovever, in cases where the exchange for alternate relays is not feasible a surveillance calibration program vill be implemented during scheduled plant outages to verify the specified time delay settings.

c Scii/JJZ/jg

~JUL 1 1977_

g, g, 80 0 612'O ( 3 p g

Gp

.