Requests Review of Util Proposal Re long-term Solution to Minimize Exceeding App G Limits.Input to SER Should Be Submitted by 770611 to Allow Implementation of long-term Fix Before Power Escalation Tests Scheduled for Late June 1977
ML19329C107
Person / Time
Site: Davis Besse 
Issue date: 05/26/1977
From: Engle L
Office of Nuclear Reactor Regulation
To: Mosetis G
Office of Nuclear Reactor Regulation
References
NUDOCS 8002120840
Download: ML19329C107 (1)


Text

- _.

a

/

4

,,a y

Distribution D cket File MAY 2 6 1977 LNR 1 File J. Stolz L. Engle E. Hylton Docket No. 50-346 MEttRANDUti FOR:

G. Mazetis, Section Leader, Reactor Systens Branch, cpcj DSS THRU:

John F. Stolz, Chief, Light Water Reactors Branch 04 1

DPf8 b

FR0!i:

L. Engle Project Manager, Light Water Reactors Eranch No. 1, DP't

SUBJECT:

REQUEST FOR SER INPUT REGARDING THE TOLEDO EDISON C0'iPYiY'S PROPOSED LONG-TE"J4 SOLUTION TO MINI!!IZE EXCEEDItG APPENDIX G LI'1ITS FOR DAVIS BESSE, UNIT 1 The applicant has submittad a proposal (by letters dated Acril 7,1977 and May 2,1977) for the long-term solution to further minimize exceeding Appendix G liuits.

The proposal for the long-tern fix incorporates an interlock being crovid=4 which trips off the pressure heater in the pressurizer if the primary systea pressure reaches 230 psig and either one or both decay heat raroval isolation valves DHil and DH12 are not fully closed.

The Toledo Edison Company has already discussed these :atters with you, and at your request, the EIiCS branch has reviewed the electrical portions of tne submittal and has found the applicant's proposed fix to be acceptable.

The applicant has indicated they wish to implement their croposed design fix as soon as staff approval is obtained. Although we have allowed (condition to the operating license)-the applicant to implement the long-ter a fix up to the start of the 2nd fuel cycle, approval and implementation of the long-term solution to minimize exceeding Appendix G limits at this time is in the best interest of plant safety.

[hg

/

ovesca r summaus >

oava >

, _ Qs. aovammuswe emeunwo orese_m. sm -eswas NRC Poax 31s (9 76) NRCM 0240 8002noJyo 6

a

~

2-MAY 2 3 1977 We request that you review the aoplicant's submittal and nrovide the SER input by June 11, 1977 in order that the applicant may innlment the long-term fix prior to power escalation tests cresently scheduled for late June 1977.

Or ginal Signed,by W&

U Leon Engle, Project : tanager Light Water Peactors Branch No.1 Division of Project "anagement ec: