Notifies of Region 3 Determination That Const & Preoperational Testing Completed Per Commitments & Requirements,W/Exception of Encl List of Items.Operations QA Program Meets 10CFR50,App B Requirements
ML19329B719
Person / Time
Site: Davis Besse 
Issue date: 04/01/1977
From: Thompson D
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE)
To: Boyd R
Office of Nuclear Reactor Regulation
References
NUDOCS 8002060727
Download: ML19329B719 (11)


Text

.-

As S

.l

.~%

v:

n m

D D Ik Docket No. 50-346 liZ::0EDU:1 TOR: Roger S. :oyd, Director, Division of Project Management, Office of ~uclear Reactor Regulation FRCM:

Ludley Thonpson, Acting Director, Division of Field Operaticas, Office of Inspection and Enforce =ent SUUJECT:

TOLEDO EDISO:i CD:f?A:J, DAVIS-BESSU,I, LOC 5/I 50, 50-346

!RC Region III has determined, based on the results of their inspectica offorts that ccustructica and preoperational testing of Davis 2csse

'J.a. i t I have been completed in substantial agreenent with docketed cot:nitnents and regulatory recairenents with the exception of itens indicated in the enclosures. Renainint: constructio1, tes tin,t and insp2ction items identified in the enclosures have leen categori:cd by Ir reco onded completion ~ilastones.

As a part of the inapection effort, Region III inspectors have reviewed the licensee's preparations for i=plementation of the quality Assurance Pror;rati for Operations, and have fowd. that they generally :aet the raquiranants of 10 CFR 51, Appe ndix T,,

as specified in the licensee's luality Asaurance Progrart (Chapter 17 of the FJA2), which was reviewed by cae Office of Nuclear Reactor Regulation.

Meist t4 sed by

2. n m *+e Dudlay Theepson, Acting Director Division of Field Operations Office of Inspection and Enforce: mat See page 2 for enclosure

//

and distribution list

,3y

  • v CONTACT:

R. F. Warnick, IE 49-27261

(

ova-v FC&EB.fc,.:

. _FCGEB,.G '

.._IE:DE D.

. nc.

  • rr

.u....*

RFWARNICK:ckc Y-DTHOMPSON--

a 4/f_l77 4/Il77

..,, g 4/_1/ 77 L

p.,. Aac.sts <m,. om anew e:4e

  • u. a..v======v==== ornc e i u-==*i a 3,o080727 g 1

r~

m m' D

D Ls a Roger S. Boyd o' g~}

~

F t ('h

-]

i.v inclosures:

A.

Itons to be completed before fuel loading B.

Itecs to be coupleted before exceeding 200*F C.

Items to be completed before exceeding 239*F D.

Items te-be completed before hot standby E.

Itans to be ocupleted before criticality F.

Itama to be completed before power operation G.

Other items to be completed but not associated with an operational modo ec: u/ enclosures R. C. DeYoung, fG J. F. Stolz,?,TUL L. 3. Engle,2.1".

?,.

D..'Lirtin, IE:III

3. 3. Vass alo, ILE v/o enclosarca J. G. Ecppler, IC:III Ps. F. Varnick OPPtC S &

sunseaus W.

r== Aac.3:e (a. p ss: Amor esee

  • m =

v======r====..eeic= iere-one ies

DiCLOSURE A items to be completed before fuel loading:

1.

Preoperationsi Test Completion As of March 24, 1977, the status of 94 Preop tests identified as being required for fuel loading is as follows:

Thirty-seven tests have been completed and approved.

a.

Thirty-two tests have been completed and are in the review chain.

b.

to be started.

c.

Twenty-five tests are either in progress or yet A select number of these require review by the inspectors subsequent to the licensee's review.

2.

Diesel Generator Sequencer - SFAS Wiring Modifications to controls necessary to prevent interruption of sequencing when the SFAS is manually initiated have been installed but remain to be tested.

3.

Diesel Generator Fans 1 Temoeratures Modifications and testing have been completed to dirott the Diesel Cencrators units discharge temperature away from the panels. Licensee is awaiting cer-tification from vendor that high panel temperatures did not damage electrical relays.

4.

Diesel Generator Sequencer out-of-Phase This item is awaiting an engineering study to determine the potentini for the sequencers getting out-of-phase and the resulting consequences of the out-of-phase condition.

5.

Safety Related Listing of System and _ Components The licensee is to develop a list of safety related activities including cem-ponents, systems, and operations which fall under the cognizance of the Toledo Edison Quality Assurance Program. This information is to be included in con-trolled documents prior to fuel loading.

6. " Power Ascension Test Review Of the 5 test procedures required to be completed prior to fuel loading, two The have been completed, two are in progress, and one has been cancelled.

lattet concelled test ia the Loose Parts Monitor. The resolution of this cancelled test has beam. forwarded to IE:HQ for action on March 17, 1977.

D D O

[.

ooA

~. a m.

d

~

_. -)

O s

^

t Enclosure A March 29, 1977 7.

System Modification Review The licensee has committed to review all proposed and completed systems re-visions to assess whether or not system retcsting is required.

Approximately 220 of the 370 field changes and startup revision notices have been completed.

The review indicated to date that 15 of the revisions would require system retest, six of which will require retest prior to fuel loading.

8.

Penetration 29 Resolution Manual normally opened bypass valves have been installed around the contain-ment isolation valves for the Decay Heat suction line thus requiring a dif-forent containment boundary for penetration #29. This item will require NRR review.

9.

Infrared Detectors The FSAR states that infrared detectors will be installed in areas such as the emergency diesel generator rooms.

The licensee has installed scoke detectors instead. This discrepancy nust be resolved by the licensee.

10. Instrument Cround Grid System During preop testing it was determined that the acceptance criteria could not be attained due to ground currents between the instruttent and station ground systems. The licensee's testing technique was not sufficiently pre-cise enough to define the problem.

The licensec has obtained more precise testing equipment and is currently rerunning the test.

11. Preoperational Test Deferral The licensee has submitted a request for partial relief on twenty-five preoperational tests required to be completed prior to fuel loading in accordance with Chapter 14 of the FSAR. NRR is currently reviewing the request. The licensee is still ecmmitted to review and approve the sections of these tests not contained in the relief request.
12. Flow Splitter Resolution of representative particulate sampling characteristics of vent stack sampler (i.e., isokinetic flow at splitter) and orientation of charcoal filter assembly.

This work is in progress (March 17) and is scheduled for completion by fuel loading.

13. Completion of Other Preoperational Tests Completion of preoperational test procedures - radiation protection, radwaste, radiation monitors, ventilation (see FSAR Table 14-1) - except as specified in the licensee's relief requests dated February 22, 1977 and March 2, 1977.

Moos of these procedures had been completed as of March 4, 1977.

D D

g ooA 0

i

_[f, r :

5

~~

  • 1
  • Match 29, 1977 Enclosute A i

14.

Control Rod Drive Systemt The licensee's rod drop test does not conform to Regulatory Cuide 1.68 with respect to rod trip time testing. The licensee has bcon informed of NRR's position and is evaluating further action.

15. NSS Heat Balance The licensee's test procedure calls for adjusting flow instrumentation read-ings if the mismatch between reactor and turbine power exceeds one percent.

The licensee is reviewing this meched to determine if there is a conflict with Technical Specifications calibration requirements.

16. Records and Document Control The licensee's corrective actions relative to records and document control 50-346/76-06 remain to be inadequacies identified in Inspection Report reviewed. This item is scheduled for review during the week of April 4, 1977.

17.. Physical Protection Reinspection of physical protection items noted during the inspection on 4-6, 1976, were conducted during Mbrch 15-18. 1977. The following August outstanding items must be resolved or co=pleted before the licensee's phy-sical protection plan can be considered operational:

All security type alarms identified in the security plan must be a.

installed, functional and tested,

b.. All openings to vital areas must be secured with formidable barriers and where applicable, with adequate locking devices.

The security plan must be revised to specifically identify all Vital c.

Area doors.

d.

All security training required by the security plan must be completed and adequately documented.

e.

A Clear area must be maintained on each side of the protected area perimeter fence.

f.

The locking devices for vital area portals must be changed upon turn-over of vital areas from Construction to Operaticus, All Physical Protection related communications equipment must be s.

installed, functional and tested.

D T

/P OWE

?:

m

'9 ~q-b S.l 3

o

~

Enclosure A March 29, 1977

18. Emergency Planning The inspection requirements in this subject area partaining to offsite Agencies Facilities, Equipment, Procedures. Tests, and Drills have been completed.

following outstanding items are being resolved with the licensec, The activity is not expected to impact adversely on the IE recommendation for and this issuance of the 0.L.

Items to be completed prior to fuel loading.

a.

(1)

A recently received letter of agreement shall be entered into Appendix C of the Emergency Plan and a list detailing the letters of agreement updated.

(2)

Periodic testing procedures for supplied breathing air and those communications not related to security shall be developed and imple-mented.

(3)

The station public address testing shall be completed in order to determine the adequacy of the quantity and quality of the system coverage in order to assure that personnel are made aware of emer-gency conditions.

(This item may be modified dependent upon NRR action on the licensee's relief request of February 22, 1977.)

(4)

Documentation of the completion of general orientation training for all station personnel, contractor personnel, and consultant suppo rt groups stationed on the site shall be available for review.

(5)

Changes in Administrative Procedures, E=crgency Procedures, and Health Physics Procedures discussed with a licensee representative during a previous inspection, shall be made.

(6)

Clarification of the response to a fire alarm and/or the use of an additional emergency classification for local emergencies, uhere limited response is required, shall be made in the emergency plan and the FSAR.

Ratraining of personnel for the required response shall be performed.

19. Valve Yoke Failure This item was reviewed with B&W during the past week.

Based on this inspec-tiod it was determined that supplemental information would have en be provided to substantiate the seismic qualifications of the valve assemblies.

Inspection of the stem replacement and seismic support installation remains to be com-plated.

10. Large and Small Pipe Hanger $ and Ancho As of March 25, 1977, approximately 200 hangers and anchors remain to be inspected and accepted prior to fuel load for safety related systems.

The acceptability of the exceptions, if any, must be reviewc rp rp g

OO e

g-L w 1_ l. _1 n_ _,

1

Enc 1'oeure A March 29, 1977

21. Electrical - Firebarriers and Separation Between Redundant Class IE and Non Class 1E Circuits.

Criteria for fire barriers and separation between redundant Class lE and non class 1E circuits within enclosures and between cable trays, wireways has been accepted by NRR and this matter is currently being examined.

Final inspection by IE staff is awaiting the completion of the work.

Criteria for separation of metal conduits containing class 1E cables is still being reviewed by NRR.

This item is to be accepted by NRR and the work completed by the licensee bef ore final review can be completed by regional staff.

During an inspection on March 23-25, 1977, it was determined that the licensee did not test fire barriers in accordance with ASTM E-119, which are representative of the installation at the Davis-Besse site. This item is being transmitted to IE:HQ for resolution.

22. Mixing of Protective and Control Circuits within RFS & SFAS Cabinets (Internal Cabinec Wiring in Conflict with IEEE 279)

Test results must be reviewed and accepted by NRR prior to fuc1 load relative to mixing of protective and control circuits within RPS and enginected safe-guard cabinets. NRR is concerned that grounding, shorting, application of

,high voltage and/or electromagnetic and radio frequency noise may degrade the class IE system. We understand that NRR will impose the appropriate MODE restrictions regarding the resolution of this item.

23. Reactor Vessel Internals The licensee is currently making repairs in accordance with the March 10, 1977 NRR meeting. The licensee's current completion date for the repairs is April 1, 1977.
24. Diesel Generator Sequencer - Anti Pump

" Modifications to insure that the sequencer is available whenever a loss of offsite power occurs..."

Final report pursuant to 50.55(e) has been received.

Item remains to be reviewed by regional staff.

25. CCW Surge Tank Instrument Interchanges i

This change is stated to be complete by the licensee. The item must be i

reviewed by IE:III.

P C'

D 0

su cv D ~9~

aL X L}L i

l

v-t 6-March 29, 1977 Enclosure A

26. _ Removed Valves Thirteen small valves were removed from safety related systems because of internal leakage.

Applicable code which governs the hydrostatic pressure for ratesting the systems is in question pending responso from the auth-orized inspector.

27. Motor Centrol Center Electrical Stabs The licensee has identified a problem with alignment of the MCC electrical stabs. This item will be reviewed during the next inspection.

e e

G 6

o D tao 66 D ~@~

w 1 J] _ J}L

.1 2

~

Enclosure g Items to be completed prior to Mode 5 (Exceeding 200'r) 1.

Surveillance Tests The licensee has 38 surveillance procedures out of a total of 141 remaining to be completed and approved.

Surveillance procedures with an interval greater than quarterly must be developed in a timely fashion to permit their adequate review prior to implementation.

2.

Electrical Reinspection - System Intera_ction The Engineering Inspection Reports document a number of conditions adverse to

" system interaction considerations".

This relates to a failure of a non safety related system which could adversely interact with and lead to the failure of a safety related system.

The licensee has determined that none of these EIRs impact on fuel loading.

Further review is required to determine by what mode the remainder of the approximately 274 items must be completed.

Enclosure C Items to be completed prior to Mode 4 (Prior to exceeding 2800P) 1.

High Pressure Injection Pump Modification The licensee must provide documentation to establish that the modification work for the pumps is in accordance with the SAR and the specification require-In addition, the licensee must demonstrate by testing that the modifi-ments.

cation solves the pump bearing temperature problem.

2.

HVAC System Adequate corrective action relative to deficiencies in HVAC welding was not provided.

Reinspection and rework is in progress.

In addition, the li.::enses has yet to provide documentation that the damper motor operators are seismic qualified.

e e

.w O

D D) ooy

  • 'O

~ 9

~ I O

Jb 2

_ A_

3 a

?

- - ~ - -,,

4

/

Enclosure D Items required to be complaced to Mode 3 (Hot Standby)

~ Mone identified.

l Enclosure E j

Items required to be completed prior to Mode 2 (Criticality) 1.

Communications Six additional speakers shall be installed in containment pursuset to an issued Startup Field Report.

2.

Core Flood Tank The licensee's evaluation of the pressurization of the core flood tank using nitrogen for the condition where there is a large vapor space needs to be reviewed to determine if the subsequent temperature reduction could cause the j

temperature-pressure limitation for the tank to be exceeded.

3.

Waterproof Trench _ Cover The licensee has committed to provide a periodic test procedure to assure periodic retesting of the leak tightness of the water proof trench cover installed over DH 11 and DH 12 in the containment.

' Enclosure F Items to be compl, ed prior to Mode 1 (Power Operation) 1.

Emergency Planning A permanent supplied air cascade charging system shall be installed.

a.

b.

An isolation emergency plan implementing procedure to cope with weather conditions which require personnel to remain at the station for un-

' determined periods shall be developed. This procedure shall alsu sddress provisions for transportation of emergency personnel to the station when' needed during these periods.

Pursuant to a telephone conversation with a licensee representative on c.

February 23, 1977, it is out understanding that the following topic will be studied for incorporation into the Eacrgency Plan Implementing Prece-dures. These topics relate to those areas where there is a high degree of inaccessibility:

D '"'lQ cak g

OK-Q~T

~

u

.5U b

..}L

~

a

/

9

., March 29, 1977 (1) Evacuation of personnel t'o d aimize exposure to a hazard'.

(2) Personnel accountability to assist the person in charge of emergency response actions to account for missing persons.

(3) Reentry into previously evacuated areas for the purposes of saving lives, search and rescue of missing and injured persons.

Safety equipment to be worn depending on areas or conditions shall be addressed.

Enclosure G Items to be done not associated with an Operational Mode 1.

Records Management The licenses has consnitted to finalize details of his operations phase records management program by April 1,1977,. with full implementation to be co=pleted by August 1, 1977.

2.

Surveillance Procedure All remaining surveillance test procedures not required to be completed by Mode 6 and 5 shall be developed in a timely fashion to permit their adequate review prior to implementation.

3.

Polar Crane Gear Teeth __P_roblem Cear teeth found with excessive wear, matter currently under TECO Engineering Review. This item has no impact on f acility startup critical path. Manu-facturer and engineering permit use of crane until af ter fuel load.

4.

Completion of the gaseous release procedure and revision of the liquid release procedure before any need to use either procedure. The licensee must be capable of quantifying unplanned releases even if these procedures are not finalized.

5.

Verification of tank volumes and flow monitor outputs used to quantify gaseous and liquid radioactive releases. These items have the same completion restric-tions as item 4.

6.

Verification of the isokinetic sampling properties of all ventilation systes particulate samplers. This item shculd be completed in conjunction with tha specific process monitor calibrations.

7.

Review of respiratory protection program to conform to 10 CFR 20.102 'ihI"~--"

a Regulatory Guide 8.15.

Notification of IE:III of fice must be made 30 days before initial use of' respiratory protection equipment pursuant to 10 CFR 20.103.

D@O D