ML19329B368

From kanterella
Jump to navigation Jump to search
Notice of Violation from Insp on 780821-23
ML19329B368
Person / Time
Site: Davis Besse 
Issue date: 09/07/1978
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To:
Shared Package
ML19329B362 List:
References
50-346-78-22, NUDOCS 8002040785
Download: ML19329B368 (1)


Text

Oi v

3

)

Appendix A NOTICE OF VIOLATION Toledo Edison Company Docket No. 50-346 Based on the inspection conducted on August 21-23, 1976, it appears that certain of your activities were in noncompliance with NFC require-ments, as noted below. Both are infractions.

1.

Section 2.3.1 of the Appendix B Environmental Technical Specifi-cations limits " total residual chlorine in the effluent from the collection box... " to "A daily average concentration of 0.2 mg/l free available chlorine and a daily maximum concentration of 0.5 mg/l free available chlorine."

Contrary to the above, the 0.5 mg/l limit was exceeded between July 7, 1978 and July 10, 1978.

2.

Section 5.1.1 of the Appendix B Environmental Technical Specifi-catione requires in part that the Station Review Board's review responsibility will include.... results of th,e Environmental Monitoring Programs prior to their submission in each Environ-(N) mental Operating Report.

v Contrary to the above, the Station Review Board did not review the first Annual Environmental Operating Report for the Davis-Besse Nuclear Power Station Unit 1.

e d

,/~%

l

/

-/