Maine Yankee Monthly Statistical Report Gentlemen:
Enclosed you will find the Monthly Statistical Report for the Maine Yankee l
Atomic Power Station for October, 1989.
j Very truly yours, l
b/N!
u G. D. Whittier, Manager i
Nuclear Engineering and Licensing l
r l
GDW:SJJ i
r l
Enclosure i
i l '
i Mr. Richard H. Wessman c:
L Mr. William T. Russell l
Mr. Eric J. Leeds Mr. Cornelius Holden i
i'
$AY
'l GDW89364.LTR 8911200083 891031 PDR ADOCK 05000309 R
.~
+
l 1
\\
l 1
i I',
b l
r i
Malne Wankee i
l i..
i t
\\
I-
?
i 1
l t
l r
t l
l M o n t: h l y Statistical Report i
s For October 1989 o
l i
J
?
P r
i t
l
(-
3 3
CPERATIN3 DATA REPORT D00kOt N3.
50-309
)
Date:
06/Nov/89 L-h Completed By -
S. L.
HALL Telephone:
207-622-4868 f
i l
1 Unit Name.......................................
_ Maine, Yankee I
- 2. Reporting Period................................
_0ctober 1989 3
Licensed Thermal Power (MWt)....................
2700
- 4. Nameplate Rating (Gross MWe)....................
890 i
S. Design Electrical Rating (Net MWe)..............
840
(
9
- 6. Maximum Dependable Capacity (Gross MWe).........
870
[
L
~7 Maximum Dependable capacity (Not MWe)...........
830 i
f S. If Changes in capacity Ratings (Items Number 3-7)
-Since.Last Report, Give Reasons:
NO CHANGES I
- 9. Power Level to Which Restricted, if Any (Net MWe)
- 10. Reasons for Restrictions, if Any j
THIS MONTH YEAR-TO-DATE CUMULATIVE
- 11. Hours In Reporting Period 745.00 7,296.00
[
- 12. Number of Hours Reactor i
Was C.ritical...........
613.20 6,962.39 119,765.38
- 13. Reactor Reserve Shutdown Ho'rs..................
0.00 0.00 0.00 14, Hours Generator On-line..
608.70 6,904.74 116,447.23
- 15. Unit Reserve Shutdown Hours................,.
0.00 0.00 0.00 l
- 16. Gross Thermal Energy Generated (MWH)........
1,587,609.00
_17,960,755.00 269,033,468.00
- 17. Gross Electrical Energy i
Generated (MWH)........
538,340.00 6.099,680.00 88.148,040.00
- 18. Net Electrical Energy r
Generated (MWH)........
5.1,851.00 5.898,809.00 84,386,983.00
- 19. Unit Service Factor......
81.70 94.64 78.29,
- 20. Unit Availabilty Factor..
81.70 94.64 78.29
- 21. Unit Capacity Factor (Using MDC Het)........
84.39 99.09 71.40 28.~ Unit Capacity Factor (Using DER Net)........
83.39 97.48 69.65 l
,23. Unit Forced Outage Rate..
2.12 3.74 6.88 l
- 24. Shutdowns Scheduled over Next 6 Months Date Type Duration f
4/14/90 Refuelinc 8 weeks i-
- 2 5. If Shutdown at End of Report period, Estimated Date of Startup N/A
7 y
Docket No 50-309 Unit'. Name Maine Yankee Date 891103 Completed Bye B.L. Hall
[
Telephone:
207-622-4868
}
R: port Month: October, 1989 i
NARRATIVE
SUMMARY
OF OPERATING EXPERIENCES
[
[
At the beginning of the month the unit was at 100% power.
i.
On October 10th, the containment purge supply valve penetration failed c type C Containment Leakage Rate Test.
The unit was taken off line l-upon exceeding t he Technical Specification Remedial Action Statement.
The unit remained shutdown for a scheduled Reactor coolant pump Sealm Outage.
L On October 16th, the unit was returned to 100% power.
On-October 30th, the unit war reduced to 94% power to retrieve a dropped rod.
The unit returned to 100% the same day.
The unit was maintained at 1001 power for the remainder of the month.
i I
' AVERAGE' DRILY UNIT. POWER LEVEL J
- FOR OCTOBER 1989 Docket No.
50-309 1
1 Unita Maine Yankee Date:
03/Nov/89 Completed By:
S. L. HALL
[
Telephone:
207-622-4868 l
1 e
5 Day!
Avg. Daily Power Level Day Avg. Daily Power Level.
(MWe-Nat)
(MWe-Net) j i
.1 871 16 254 l
2 872 17 819 3
871 18 869
<4 874 19 873 5
874 20 871
[
6 873' 21 873 i
t 7
874 22 872 8
873 23 874 j
t 9
872 24 872 e
10 569 25 871 i
11 0
26 873 l
12 0
27 872 7
13 0
28 874 873 14 0
29 15~
0 30 873 31 875 l
l 5
f 1
l l
l-l1 l
l l
7-
' ' UNIT.. SHUTDOWNS AZD POTER REDUCTIONS D:ekct No.:
50-309
/.? F FCR CCTOBER 1C89' Unit Maino YcnkCO 4, '
Dato:
03/N v/89 i
Completed By:
S. L. HALL i
Telephone:
207-622-4868 Page 1 of 1 i
Number 10-89-11 Date 891010 l
891011 p
.T l
I Type (1) ll P
Jl S
]
4 l
l l
Duration j
(Hours) l 13.2 123.1 f)
Reason (2) l F
B l
Method (3)
[
1 ll 4
j h
LER #
l 89-004 l
N/A
~
System Code (4)
SD CB l
Component Code (5)
VALVEX-B PUMPXX-B I
i i
~'
The unit was taken Scheduled Reactor off line due to Coolant Pump exceeding Tech.
Seals Outage.
The Specs. on a Typt C unit was returned Cause and Containment to 100% power.
Correctivo Leakage Rate Test.
Action The unit remained down for a planned RCP Seals Maintenance Outage.
1.
TYPE:
2.
REASON: (cont) 4.
SYSTEM CODE:
(F)orced F-Administrative Exhibit G-Instructions (S)cheduled G-Operational Error for Preparation of Data :
H-Other (Explain)
Entry Sheets for 2.
REASON Licensee Event Report A-Equipment Failure 3.
METHOD:
(LER) File (NUREG.0161)
B-Maintenance o'r Test 1-Manual C-Refueling 2-Manual Scram 5.
COMPONENT CODE:
D-Regulatory Restriction 3-Automatic Scram Exhibit I-Same source E-operator Training &
4-Other (Explain) an above.
License Examination 1.