Forwards Response to Violations Noted in Insp Repts 50-295/89-23 & 50-304/89-21.Corrective Actions:Procedure Change to Procedure ZAP-04, Station Housekeeping/Fire Protection, Will Include Tracking Method for Matls
ML19327B645
Person / Time
Site: Zion  File:ZionSolutions icon.png
Issue date: 10/13/1989
From: Kovach T
COMMONWEALTH EDISON CO.
To: Davis A
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
0332T, NUDOCS 8911030084
Download: ML19327B645 (3)


Text

?

Q sf

=

N

commonwomh Emeon

/ 't' l

' 72 West Adams Creet, Chicapo. Onois

  • \\'

/ KadissiWpTyTo7osi'Offic~e B'oT767~

L

'w/'

Chicago, Hhnois GD690 0767 l

October 13, 1989 Mr. A. Bert Davis i

Regional Administrator U.S. Nuclear Regulatory Commission i

Region III i

799 Roosevelt Road i

Glen Ellyn, IL' 60137 l

2

Subject:

Zion Nuclear Power Station, Units I and 2 l

License Nos. DPR-39 and DPR-48 i

Response to Inspection Report Nos. 50-295/89023 and 50-304/8902)

MRC Docket NoldQ-295 and 50-304

[

Reference:

September 14, 1989 letter from RN Cooper to Cordell Reed I

l

Dear Mr. Davis:

+

The letter referenced above transmitted the results of a routine safety inspection of the fire protection program, conducted by Mr. J. Holmes of your staff, at the Zion Nuclear Power Station.

During the course of this inspection. It was determined that certain activities appeared to be in violation with NRC requirements. Our response to the violation is provided in the Attachment to this letter.

i Please direct any questions that you may have regarding this matter to this office.

Very truly yours, t

ylr T.J.

ovach Nuclear Licensing Manager

[

}

i l

GET/scl:03321:1 OCT 161999 Attachment I\\

cc: Resident Inspector-Zion Chandu Patel-NRR pipoR888eBM8@p

'/ l0 a

p L m.4 t_

i

~

ATTACHMENT t

ylDLATION i

i Technical Specification Section 6.2, entitled." Plant Operating Procedures",

requires that detailed written procedures be prepared, approved, and adhered to for the Fire Proter. tion Program.

Section G.8 and G.9 of the Itcensee's station housekeeping / fire protection procedure require that in areas where transient fireload is excessive and presents a possible hazard to the plant equipment, an increased surveillance of the area may be required.

The station fire marshal shall be consulted regarding areas of concern and the fire marshal will determine if additional i

fire equipment and increased surveillance are required.

j Contrary to the above, on July 17, 1989, the licensee failed to adhere to the

)

housekeeping / fire protection procedure in that the fire marshal was not

)

contacted to determine if increased surveillance of elevation 579 of the auxiliary building was required due to the existance of a transient j

combustible (acetelyne/ oxygen welder's cart) that presented a possible hazard i

to redundant plant safe shutdown equipment (auxiliary feedwater pumps and cabling).

The licensee had previously requested an exemption in this area (Fire Area / Fire Zone 11.3) from full automatic supression, full automatic detection, and 20 feet separation between redundant components and cabling for redundant safe shutdown equipment.

This condition existed from July 17-19, 1989.

This is a Severity Level IV violation (Supplement 1).

i i

l 1

I

/sc1:0332T:2

h F

r

^

1 g

Cotttctive Actionlattn_ind_Reuttilchlered The Fire Marshall immediately removed the acetelyne/ oxygen welder's cart from i

i the vicinity, once it was brought to this attention.

The Fire Marshal j

discussed the violation with both maintenance supervisors and the foreman in charge of the specific jobs, and advised them of their responsibilities to l

prevent future violations.

t In addition, written guidance was forwarded through several letters. A l

July 24, 1989, letter was written to the Department Heads regarding the "The i

t Control of all Flammable / Combustible Compressed Gas Cylinders in Safety Related Areas" to heighten the awareness of the subject concsrn.

An August 9, 1989, letter was written to the Licensed Shift Supervisors (LSS) regarding "The Control of Transient Flammable and Combustible Materie.ls Including Flammable Compressed Cylinders such as Acetelyne, Hydrogen, etc.".

l This letter delineated the resp'ansibilities of the LSS, who acts as fire r

Chief, regarding control of flammable transient materials within safety related areas.

i A September 5, 1989, letter was written to the Security Supervisor regarding

" Interim Firewatch Post in Safety Related Areas".

This letter required the Security Supervisor to post continuous firewatches in the Unit One Containment and a roving firewatch throughout the Auxiliary Building during the current refueling outage.

These activities have increased the awareness of plant personnel toward control of transient flammable / combustible materials.

Contettive Aciloni_IhtLW111 be_latefLtolycid future Violttions Additional activities that will be taken to prevent future violations include a procedure change to Zion Administrative Procedure (ZAP-04) " Station Housekeeping / fire Protection".

The procedure change will include a tracking method for all transient flammable and combustible materials being transported throughout fire areas in the plant.

Additional manpower resources and training will be required to accomplish the implementation of the revised procedure.

DateMealRlLComplia nceli1LDelchie te d Zion Station will be in full compliance by February 1, 1990.

/sc1:0332T:3