Kr 1

hk

. : Geotoia'P$ mar Company 3

)

% @#$ <t i

L 333 Padmont Avenoo N

' # knta, Georgia 30308.

'.j h hl.h ',*. @neO W E'

,j ~

e-i Ma.finDAddrone 4J' 40 invertwss Center Parkway

. Post Offce Box 1295 4, /..,...

.. Srmingham. Nabama 35201, f, 'W

' Telephone 205 068 b581 '

.tv wat%w ele ttrc m!ern

'f i,

" W. G. H'airston til Senior Vce President

+

+

l Nt. dear Operatens

't l>

HL-787 0343V october 23, 1989 l

,t;

'U.S. Nuclear Regulatory Commission ATTN:; Document Control Desk 3

Hashington, D.C.~

20555

.A.

. PLANT HATCH - UNIT 2 NRC DOCKET 50-366 OPE.t*, TING LICENSE NPF-5.

.' C REPLACEMENT OF DRYNELL' PENETRATION BELLOHS L'

c l(,

Gentlemen:

l w

- OnL October.4,1989, ' a-conference call' was held among representatives

]

from Georgia'. Power Company (GPC), 'Bechtel Power. NRR, and Region.II to l l' discuss ' activities surrounding the replacement of Unit Two drywell penetration bellows. assembly 2T23-X9A.

As discuss &d, replacement of-the i

bellows' was necessary following --failure of its' local leak rate '. test since the: configuration of the-bellows assembly made repair of the inner 77, seal impossible. At the conclusion of the conference call, participating NRC-- staff members ' concurred with the use of Pathway Corp. as the replacement bellows vendor.

o The purpose 'of this letter is to document NRC agreement with the GPC justification for: the use of Pathway Corp. as the replacement bellows vendor.

As presented in the conference call, GPC contacted 13 utilities and ?

.[

1 suppliers in an effort to obtain a replacement be170ws with an ASME Section III' N-Stamp.

Due to the fact that the bellows assemblies at Plant. Hatch were custom made, it was determined that none of the companies contacted had an "off the shelf" assembly suitable for our I

application.

Generic Letter 89-09 permits a licensee to use a non

' N-stamped ~ vendor as long as it has been determined that an equivalent ASME Section III stamped replacement is not available.

In the course of our investigation it was identified that only one vendor, Metal Bellows Corp., currently holds an N-Stamp.

However, as discussed during the October 4th conference call, GPC believes that, in this situation, it is more prudent to obtain a replacement component from Pathway Corp. for the

[m following reasons:

bool 891oao0122 891023 1

{DR ADOCK c5000366

' \\

PDC

{

\\

w

\\b,

  • r

... C00Pglh POWfr AL.

~'.

L.S. Nuclear Regulatory Commission U

october 23, 1989, I

Page Two

-l'. ' Pathway is.the supplier of. the original bellows -and has all the i

assembly / subassembly drawings and engineering analysis /

4 calculations.

N 2.

All new engineering calculations / designs will be verified and approved by a Professional Engineer who is knowledgeable of the o

ASME Code.

Pathway is in possession of the original calculations and as such can readily assure that the original design 1 intent'is fully satisfied by the replacement design.

1. x L',

3.

All materials ' are ASME and have Material Test Reports, Heat I

Numbers.:and traceability.

]

k 4.

All Pathway-~ welders'are qualified per ASME Section IX and will be l

qualified again under the GPC procedures and QA' program.

)

5.

Pathway QA

manual, weld procedures, and non-destructive J

examination (NDE) procedures will be reviewed and approved.

6. -All NDE will be in accordance with American Society of l-Non-Destructive Testing Standards.

1 7.

A. Bechtel inspector shall perform all hold point and final inspections at the vendor facilities.

I 8'.

An Authorized Nuclear Inspector will perform the final inspection L

of the haroware and paperwork and ' sign an equivalent of tu ASME Data Report, At the conclusion of the phone call NRC staff personnel stated that, based on the information provided by GPC, the use of Pathway Corp. as the l

replacement bellows vendor is acceptable and that the intent of Generic Letter 89-09 is satisfied.

Consequently, we are proceeding with the procurement of a replacement bellows for Unit Two drywell penetration 2T23-X9A from Pathway Corp.

Installation and testing will be completed prior to startup from the current refueling outage.

?J If you have any questions in this regard, please contact this office.

4 Sincerely, y),). l$x.c H. G. Hairston, III SJB/eb

?

c:

(See next page.)

L

_ h.

m j

, Gebigia Power A U.S. Nuclear Regulatory Commission ec october 23, 1989 Page.Three.

c: Georaia Power Comoany l

Mr. H. C. Nix, General Manager - Nuclear Plant Mr. J. D. Heidt, Manager Engineering and Licensing - Hatch GO-NORMS

.q U.S. Nuclear Reaulatory Commission. Washinaton. D.C.

Mr._L. P. Crocker, Licensing Project Manager - Hatch t

U.S.' Nuclear Regulatory Commission. Region II Mr. S.'D. Ebneter, Regional Administrator

,Mr. J. E. Menning, Senior Resident Inspector - Hatch i