Submits Final Response to 800723 Request for Addl Info Re Proposed Tech Spec Changes to Support Fuel Cycle 2 Operation.Describes Evaluation of Effect of Ramp Rate Correlations & Performance of ECCS Analysis
ML19327A548
Person / Time
Site: Davis Besse Cleveland Electric icon.png
Issue date: 07/30/1980
From: Crouse R
TOLEDO EDISON CO.
To: Novak T
Office of Nuclear Reactor Regulation
References
639, NUDOCS 8008060364
Download: ML19327A548 (1)


Text

-

TOLEDO EDISON RcsAno P. CROUSE vee pres am M&ew Docket No. 50-346 maing3n, License No. NPF-3 Serial No. 639 July 30, 1980 Director of Nuclear Reactor Regulation Attention: Mr. Thomas M. Novak, Assistant Director Operating Reactors Division of Licensing United States Nuclear Regulatory Commission Washington, D. C. 20555

Dear Mr. Novak:

This letter provides the final response to your July 23, 1980 request for additional information related to the proposed technical specification changes to suppset fuel cycle 2 operation of the Davis-Besse Nuclear Power Station, Unit 1. Items 1 and 3 of your request were addressed by our letter of July 29,1980 (Serial No. 638).

Item 2 of your letter reads:

"Please confirm that the ECCS analysis for Davis-Besse Unit 1 Cycle 2 would continue to be in compliance with the criteria of 10CFR50.46 if the staff cladding swelling and rupture models of NUREG-0630 (D. G. Eisenhut (NRC) letter to All Operating Light Water Reactors dated November 9, 1979) were used in your ECCS evaluation model."

A generic evaluation of the effect of ramp rate correlations contained in Draft NUREG-0630 was made using Babcock & Wilcox's (B&W) currently approved ECCS model.

These results were summarized in a letter to the Director, Division of Licensing from B&W (Mr. J. Taylor) dated November 20, 1979. This letter stated that based on B&W's estimates, compliance with 10CFR50.46 is maintained.

The Davis-Besse Unit 1, Cycle 2 ECCS analysis was performed utilizing the currently approved ECCS code (TAFY). Based on this analysis, the previous evaluation provided in the B&W letter of November 20, 1979 is appropriate to the Davis-Besse Unit 1 Cycle 2 operations. This indicates continued compliance with 136FR50.46.

Very truly yours, A j'f 001 WWk; = -_ .5

~

RPC:TJM: cts //()

THE TOLEDO EDISON COMPANY EDISON PLAZA 300 MACISON AVENUE TOLEDO, OHIO 43652 A008060