Responds to IE Bulletin 80-16 & Forwards List of Model 1151 Transmitters within MSIV Leakage Control Sys.Final Response to Be Submitted After GE Analysis of Process & Sys Design Data
ML19327A484
Person / Time
Site: Hatch  
Issue date: 07/29/1980
From: Widner W
GEORGIA POWER CO.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
0088, IEB-80-16, NUDOCS 8008060248
Download: ML19327A484 (4)


Text

July 29, 1980 GeorgiaPower w w a xsawn 00BB United States Nuclear Regulatory Commission Office of Inspection and Enforcement

REFERENCE:

Region II - Suite 3100 RII - JP0 101 Marietta Street, NW 50-321/50-366 Atlanta, Georgia 30303 I&E Bulletin 80-16 ATTENTION: Mr. James P. O'Reilly Gentlemen:

Hatch site technical personnel, along with its architect engineer, have conducted a review of all the Rosemount pressure transmitters being used in safety-related systems at Hatch Units 1 and 2.

The review revealed that the Unit 1 safety-related systems do not employ any of the transmitters which were specified in the bulletin. On Unit 2 it was discovered that several of the transmitters within the MSIV Leakage Control System (2E32) are of the Model 1151 transmitter specified in the bulletin. Attached is a listing of the affected transmitters along with their associated process and service data.

. Five of these transmitters have "E" type output which were not mentioned in the bulletin; however, they are similar to the "A"

and "D" output transmitters in that they all supply 4 to 20 milliamp linear output signals. The other ten transmitters are all Rosemount 1151 with "A" type outputs.

Presently the General Electric Company is reviewing process and system design data which relates to the affected Model 1151 transmitters. Their response is needed to adequately respond to action item numbers 2 and 3 of the bulletin. When GE submits their analysis to the plant site a final response to the bulletin will be submitted.

Since there are no data available which indicates that the existing trans-mitters have ever been subjected to over or reverse pressures, we plan to continuenormal operation of the Unit 2 reactor at least until we receive the GE response. The Unit 1 reactor is not affected since its safety systems do not employ any of the aforementioned types of transmitters.

If you have any questions in this regard, please ~. tact my office.

Sincerely,

$Y/

W. A. Widner pir

'JAE/JLS/mb 06/

Attachment 3

xc: Director of the Office of Inspection and Enforcement Director of the Division of Operating Reactors, Office of Nuclear Reactor Regulation 8008000 298

ATTACHMENT TO RESPONSE TO I&E BULLETIN 80-16 Georgia Power Company, Edwin I.

Hatch Nuclear Plant, Units 1 & 2 Docket Numbers 50-321 & 50-366 MPL No. - 2E32 - N050 Model No. - 1151 GP6A52MB Element Range 100 PSIG Calibrated Range - 14.6 - 114.6 PSIG Process Fluid - Steam Design Temp. - 5750F Design Press. - 1250 PSIG Normal Temp. - 5450F Normal Press. - 1000 PSIG Service - Inboard Reactor Vessel Pressure Function - Signal to 2E32 - N650 alarm unit which is used for system initiation MPL No. - 2E32 - N0518, F, K, & P Model No. - 1151AP5E52MB Element Range 55" Hg Calibrated Range - 8.61" Hg - 20.48 PSIG Process Fluid - Steam Design Temp. - 5750F Design Press. - 1250 PSIG Normal Temp. - 5450F Normal Press. - 1000 PSIG Service - Main Steamline Pressure Function - Signal to 2E32 - N651 B, F, K, & P alarm units which are used for system time delay logic.

MPL No. - 2E32 - N054 Model No. - 1151DP4A52MB Element Range 150" H 0 g

Calibrated Range 100 HO 2

Process Fluid - Air 0

Design Temp. - 150 F Design Press. - 150 PSIG Normal Temp. 40-1500F during normal power operation Nomal Press. - (-).25" H O during normal power operation 2

Service - Inboard Oilution Air Flow Function - Signal to 2E32 --N654 alarm unit which is used for dilution air flow logic and alarm annunciation MPL No. - 2E32 - N055 i

Model No. - 1151GP6A52MB Element Range 100 PSIG Calibrated Range 100 PSIG Process Fluid - Steam Design Temp. - 5750F i

Design Press. - 1250 PSIG Normal Temp. - 5450F Normal Press. - 1000 PSIG Service - Outboard Steamline Pressure Function - Signal to 2E32 - N655 alarm unit which is used for outboard system initiation c4C

\\

/JAE/mb

~

MPL No. - 2E32 - N056 Model No. -~ll51AP5E52MB Element Range 30 PSIA Calibrated Range - 30" Hg - 10 PSIG

-Process Fluid - Steam Design Temp. - 5750F Design Press. - 1250 PSIG Nonnal Temp. - 5450F

~

Normal Press. - 1000 PSIG Service - Outboard Steamline Pressure Function - Signal to 2E32 - N656 alarm unit which is used for outboard system initiation and alarm annunciation MPL No. - 2E32 - N058 Model No. - 1151GP6A52MB Element Range 100 PSIG Calibrated Range - 14.6 - 114.6 PSIG Process Fluid - Steam Design Temp. - 5750F Design Press 1250 PSIG 0

Normal Temp. - 545 F Normal Press. - 1000 PSIG Service - Outboard Reactor Vessel Pressure Function - Signal to 2E32 - N658 alarm unit which is used for outboard system initiation MPL No. - 2E32 - N059 Model No. Il510P4A52MB Element' Range 150" H 0 g

Calibrated Range 100 HO 2

Process Fluid - Air0 Design Temp. - 150 F Design Press. - 150 PSIG Normal Temp. 150 F during normal power operation Normal Press. - (-).25" H 0 during normal power operation 7

Service - Outboard Oiluti5n Air Flow Function - Signal to 2E32 - N059 alarm unit which is used for alarm annunciation only MPL No..- 2E32 - N060 Model No. - ll51GP6A52 MB Element Range 100 PSIG Calibrated Range - 14.6 - 114.6 PSIG Process Fluid - Steam Design Temp. - 5750F Design Press. 1250 PSIG 4

Normal Temp. - 5450F Normal Press. - 1000 PSIG Service - Inboard Reactor Vessel Pressure Function - Signal to 2E32 - N660 alarm unit which is used for system initiation 0 43

'JAE/mb

MPL No. - 2E32 - N061B F. K, & P Model No.

ll51GP6A52MB Element Range 100 PSIG Calibrated Range - 10.48 - 110.48 PSIG Process Fluid - Steam 0

Design Temp. - 575 F Design Press.u-1250 PSIG Normal Temp. - 545 F

~

Normal Press. 1000 PSIG Service - Inboard Main Steamline Pressure Function - Signal to 2E32 - N661B, F, K, & P alann units which are used for system

~

initiation -