7pw.J7dy &
PRELIMINARY NOTIFICATION July 25, 1980 PRELIMINARY NOTIFICATION OF EVENT OR UNUSUAL OCCURRENCE--PNO-TMI-80-38J This oreliminary notification constitutues EARLY notice of events of POSSIBLE safety or public interest significance.
The information presented is as initially received without verification or evaluation and is basically all that is known by NRC staff on this date.
Facility: Metropolitan Edison Company Three Mile Island, Unit 2 Middletown, Pennsylvania Docket Number 50-320
Subject:
REACTOR BUILDING PURGE STATUS From July 10 to July 24, 1980, the reactor building atmosphere Kr-85 concentration increased from 1.9x10-4 uCi/cc to 1.54x10-3 uCi/cc based on periodic sampling with no purging evolutions in progress.
The water in the reactor building sump is suspected to be off-gassing Kr-85.
On Friday, August 1,1980, the licensee intends to purge the reactor building using the modified purge system in accordance with Environmental Technical Specification (Appendix B to License No. DPR-73) release rates.
Subsequent periodic purges of the reactor building are also being planned.
In addition, the licensee _ intends to issue a technical report on the differences in calculated curies released as a result of the purge operat'an. A pre-purge inventory of approximately 57,000 curies is assumed based on t aactor building samples, but approximately 43,000 curies is calculated to be released using the plant effluent monitor (HPR-219A) data.
Media interest has been expected because the licensee plans to issue a press release.
The Comonwealth of Pennsylvania has been infomed. The NRC has not made plans to issue a press release.
This preliminary notification is issued for information only. The NRC intends to review the subject technical report and continue to monitor events as they occur.
The NRC TMI Program Office received notification of this occurrence by monitoring events as they occurred.
M.M.Sh(anbaky b&
Contact:
6e 590-3950 590-a950
,I a
QTCA%u
. N.
asano 590-3950 T. Collins 590-3955 8008060 22G
PN0-TMI-80-38J (cont) 2 July 25, 1980 Distribution:
(Facsimile Transmission Times Noted)
H St Bldg 4' Fib Chairman Ahearne Commissioner Bradford S. J. Chilk, SECY Commissioner Gilinsky Commissioner Hendrie C. C. Ka.mmerer, CA ACRS (For Distribution)
MNB Bldg M.*MP P. Bldg S:M IE:X00S 3'50 (IE:HQ Dist.)
W. J. Di rcks, EDO H. R. Denton, NRR C. Michelson, AED0 D. Ross, NRR J. J. Fouchard, PA R. J. Mattson, NRR' Landow Bldg (Fax by HQ)
N. M. Haller, MPA S. Hanauer, NRR (6 min /page)
W. Kerr, OSP D. Eisenhut, NRR J. J. Cummings, 01A H. K. Shaper, ELD R. H. Vollmer, NRR B. J. Snyder, NRR (MAIL)
Region I
$'!(o R. Minogue, SD Region II __L :01.
Willste Bldg (/:31 IE:X005 Region III _Jg 4/ 3;/
J. G. Davis, NMSS '
Document Ebnagement Br Region IV I/fr R. Budnitz, RES (For PDR/LPDR)
Region V 4fai PRELIMINARY NOTIFICATION M
-