ML19327A102

From kanterella
Jump to navigation Jump to search
Responds to IE Bulletin 80-06 Re Engineered Safety Features Reset Controls.Circuits Being Redesigned & Modified to Ensure That safety-related Components Remain in Emergency Mode.Item 2 Tests Will Be Completed by 800901
ML19327A102
Person / Time
Site: Sequoyah 
Issue date: 07/14/1980
From: Mills L
TENNESSEE VALLEY AUTHORITY
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
IEB-80-06, IEB-80-6, NUDOCS 8008010156
Download: ML19327A102 (2)


Text

TENNESSEE LLEY AUTHORITh 3

CH ATTA'NY>67,g-h2EE, 374o t 400 Chestnut Str'eet Tower II o

Ju I42(980 t

Mr. James P. O'Reilly, Director Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission Region II - Suite 3100 101 Marietta Street Atlanta, Georgia 30303

Dear Mr. O'Reilly:

OFFICE OF INSPECTION AND ENFORCEMENT BULLETIN 80 RII:JP0 50-327 -

SEQUOYAH NUCLEAR PLANT UNIT 1 In response to your letter to H. G. Parris dated March 13, 1980, which transmitted Inspection and Enforcement Bulletin 80-06 on Engineered Safety Features (ESF) Reset Controls, we submitted the preliminary results of our investigation for Sequoyah Nuclear Plant unit 1 on June 12, 1980.

TVA is evaluating safety-related components, identified by the Jrawing review required by item 1 of the bulletin, which do not remain in the emergency mode after reset of the ESF actuation signal to determine where undesirable safety consequences might occur. As components are identifiad where reset of the ESF actuation signal causes undesirable consr.quences, the circuits are being redesigned or modified to ensure the component remains in its emergency mode.

TVA is in the process of preparing the procedures for the tests required by item 2 of the bulletin. The tests are-expected to be completed by September 1, 1980.

We expect to submit a complete response to the bulletin by August 1, 1980. This response will include a description of required modifica-tions, confirmation of the test schedule, and a description of any additional problems identified by the test program.

l i

An Equal Opportunity Employer 8008010}$(,

' Mr. James P. O'Reilly, Director July 14, 1980 If you have any questions concerning thi with D. L. Lambert at FTS 857-2581.

s matter, please get in touch

~

Very truly yours, TENNESSEE VALLEY AUTHORITY L. M. Mills, Mansger Nuclear Regulation and Safety cc:

Office of Inspection and EnforcementDirector nspections U.S. Nuclear Regulatc,ry Commission Wasington, DC 20555 Sworn to and subscr ed before me,this/

day o L'f980 jwf Notqp Public My Commission Expires Y

[2/

/ /