ML19326D627

From kanterella
Jump to navigation Jump to search
Forwards IE Bulletin 80-15, Possible Loss of Emergency Notification Sys (ENS) W/Loss of Offsite Power. Written Response Required
ML19326D627
Person / Time
Site: Framatome ANP Richland
Issue date: 06/18/1980
From: Engelken R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION V)
To: Estey H
SIEMENS POWER CORP. (FORMERLY SIEMENS NUCLEAR POWER
References
NUDOCS 8007030008
Download: ML19326D627 (1)


Text

___

)Ithg

[#. 4*

o UNITED STATES F,. O

) 3,

\\

NUCLEAR REGULATORY COMMISSION i

REGION V 1990 N. CALIFORNI A BOULEVARD o ' ' w' SUITE 202, WALNUT CREEK PLAZA o

e,,,e WALNUT CR E E K, CALIFORNI A 94596 June 18,1980 Docket No. 07001257 Exxon fluclear Company 2101 Horn Rapids Road Richland, WA 99352 Attention:

Mr. H. P. Estey, Manager, Licensing and Compliance, Operating Facilities Gentlemen:

Enclosed is TE Bulletin flo. 80-15 which requires action by you with regard to your power reactor facility (ies) and/or fuel facility (les) with an operating license.

In order to assist the flRC in evaluating the value/ impact of each Bulletin on licensees, it would be helpful if you would provide an estimate of the manpower expended in conduct of the review and preparation of the report (s) required by the Bulletin.

please estimate separately the manpower associated with corrective actions necessary following identification of problems through the Bulletin.

Should you have any questions regarding this Bulletin or the actions required by you, please contact this office.

Sincerely, Wmid$-

R. H. Engelken Director

Enclosures:

1.

IE Bulletin flo. 80-15 2.

List of Recently Issued IE Bulletins i

l 800703-0#g

VillTED STATES SSIflS flo. :

6820 i

flVCLEAR REGULATORY COMMISSI0ft Accessions flo.:

0FFICE OF IflSPECTI0ft Afl0 EllFORCEMEf1T 8005050072 i

WASHIf1GT0ft, D.C.

20555 June 18, 1980 IE Bulletin flo. 80-15 POSSIBLE LOSS OF EMERGENCY NOTIFICATION SYSTEM (Ells) WITH LOSS OF 0FFSITE POWER In the past year, there have been two occurrences where a loss of off-site power has resulted in a loss of communications between a power reactor facility and the f1RC Operations Center via the Emergency Notification System (ENS).

The most recent occurrence was at Indian Point Unit 2 on June 3,1980.

The earlier event occurred at the Davis Besse facility on October 15, 1979 and resulted in the issuance of IE Circular 80-09.

The installation of the ENS requires a station package which operates on 110 VAC.

In some cases, the station package is located at the local telephone company which supplies the required power for normal operation and emergency power for operation during abnormal occurrences, but in many cases, the package is located at the site and is served by on-site power.

In some cases where the station package is served by on-site power, the station package has not been backed up by emergency power.

NRC data indicates that the station packages for each facility are powered in the manner described in the two enclosures.

Actions to be taken by all licensees:

1.

Within 10 days of the date of this Bulletin, verify by direct inspection, in conjunction with the appropriate telephone company representative, that the Ells at your facility is powered in the manner described in the two enclosures.

2.

Those facilities.which have station packages requiring on-site power, but which are not connected to a safeguards instrumentation bus which is brcked up by batteries and an inverter or equally reliable power supply, shall make necessary modifications and provide such a connection.

3.

All facilities are to develop and conduct a test, within 60 days of the issuance of this Bulletin, to verify that all extensions of the Ells located at your facility (ies) would remain fully operable from the facility (ies) to the NRC Operations Center in the event of a loss of offsite power to your facilit les to mean that an actual DUPLICATE DOCUMENT Entire document previously enteredintoWsstemunder:q oo oSb O7sl wO l

No. of Pages:

l l