ML19326A291

From kanterella
Jump to navigation Jump to search
Forwards LER 78-027/03L-0
Date released: 12/06/2019 Download: ML19326A291


LER 78-027/03L-0:on 780316,stop Valve AF3870 Failed to Open During Testing.Caused by High Differential Pressure Due to Check Valve AF39 & AF72 Leakage.Motor Operator Initially Not Adjusted for This Pressure,Causing Operator to Torque Out
ML19326A344
Person / Time
Site: Davis Besse Cleveland Electric icon.png
Issue date: 04/12/1978
From: Jerrica Johnson
TOLEDO EDISON CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
Download: ML19326A344 (3)
Forwards LER 78-027/03L-0
ML19326A284
Person / Time
Site: Davis Besse Cleveland Electric icon.png
Issue date: 04/12/1978
From: Jenny Murray
TOLEDO EDISON CO.
To: KEPPLER J G
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
Download: ML19326A284 (1)