Forwards Draft Info Notice, Failure of Ingersoll Rand Air Start Motors as Result of Pinion Gear Assembly Fitting Problems, for Review & Comment
ML19325F268
Person / Time
Issue date: 11/08/1989
From: Berlinger C
Office of Nuclear Reactor Regulation
To: Fry S
INGERSOLL-RAND CO.
References
NUDOCS 8911200033
Download: ML19325F268 (5)


Text

Nov nber 8, 1989 fb]

'sinuel Fry, Engineer in Charge 5

Engine Starting Systems Ingersoll Rand Corporation 7500 Shadwell Drive Roanoke, VA 24019

Dear Mr. Fry:

The Nuclear Regulatory Comission is in the process of preparing an information notice entitled " Failure of Ingersoll Rand Air Start Motors As a Result of Finion Gear Assembly Fitting Problems."

A copy of the latest draft of this information notice is enclosed for your review and comment.

Connents, particularly those dealing with the facts presented in the information notice, received by November 16, 1989, will be considered in the final version.

Sincerely, Original Signed By

~

"I H. Berlinger Carl H. Berlinger, Chief Generic Connunications Branch Division of Operational Events Assessenent Officer of Nuclear Reactor Regulation

Enclosure:

Draft Information Notice DISTRIBUTION w/ enclosure FJHiraglia, NRR CERossi, NRR CHBerlinger, NRR DCKirkpatrick, NRR CHaughney, NRR JACalvo, NRR PDR Central Files s DC5 '""

DOEA R/F OGCB R/F DKirkpatrick R/F l

l 1

OGCB:DOEA:NRR C/ GCB:00EA:NRR DCKirkpatAick CHPerlinger 11/J' /89 h/Q 11/ /89 f)k

,\\ \\

8911200033 891108 PDR ORG NRRB

i Enclosuro

\\

hO@j UNITED STATES

[

t....r NUCLEAR REGULATORY COMMISSION 0FFICE OF NUCLEAR REACTOR REGULATION WASHINGTON, D.C.

20555 i

November xx, 1989 NRC INFORMATION NOTICE NO. 89-XX:

FAILURE OF INGERSOLL RAND AIR START MOTORS AS A RESULT OF PINION GEAR ASSEMBLY FITTING PROBLEMS j

i Addressees:

All holders of operating licenses or construction permits for nuclear power plants.

4'

Purpose:

l This information notice is intended to alert addressees to the potential malfunctioning of Ingersoll Rand air start motors caused by the inadequate fitting of the pinion gear, the pinion gear retainer and the rotor shaft.

It is expected that recipients will review the information for applicability to i

their facilities and consider actions, as appropriate, to avoid similar prob.

lems.

However, suggestions contained in this information notice do not consti-i tute NRC requirements; therefore, no specific action or written response is

required, t

Description of Circumstances:

i On February 1,1989, during the performance of a surveillance test at Diablo Canyon Unit 1, the number one emergency diesel generator failed to start. Each diesel generator ct this plant is started by four Ingersoll-Rand air start motors, two of which are controlled by the primary de power source and the other two by the backup de power source.

In accordance with the normal test procedure, the backup de power source was disabled during the test. After repeated tests showed that the diesel generator could not be started with the primary de power source but could be started with the backup de power source, the two primary start motors were disassembled for inspection.

Both motors were found to have broken pinion gear retainers that allowed the start motor rotor shaft to turn without driving the pinion gear (see Figure 1).

In addi-tion, both motors had broken and bent retainer bolts and cracks in the rotor shafts.

During normal operation, the diesel generators are started using both dc power sources, and in an emergency the number one diesel generator would have been started by the still functional backup start motors.

However, many related problems were found on other air start motors as a consequence of this event, The Diablo Canyon site has a total of 20 air start motors, four on each of its five emergency diesel generators. All of the motors were disassembed and DM'T.

3 IN 89 %s.

1 N EI N November xx,1989 i

^

575 m g g Page 2 of 3 i

i inspected, and a total of 10 were found to have cracks in their rotor shafts, l

Many mctors had pinion gears or pinion gear retainers and retainer bolting that j

were loose. All of the motors with cracked shafts had well-developed wear 1

patterns on the retainers and on the tangs at the ends of the rotor shafts that t

engage slots in the retainers, indicating that the ) inion gears had been loose j

for a long time.

In two cases, the retainer bolts ind backed out until the retainer was on the point of becoming disengaged from the rotor shaft tang.

l t

Discussion:

When a diesel generator receives a start signal, solenoid valves open to admit air pressure (normally 150 psi) to the air motor rotor, which turns the shaft i

and pinion gear in question. This pinion gear meshes with and turns a larger drive gear that provides torque through a clutch to a Bendix drive.

The j

rotetton through the Bendix drive forces a second pinion gear to engage the ring gear on the diesel engine flywheel, causing tie diesel engine to turn.

The pinion gear retainers, which were broken during)this event, consist of a di.sk bolted to the end of the rotor shaf t (Figure 1.

The retainer has a transverse slot that engages both a flat-sided tang on the end of the shaf t and lugs on the pinion gear. Thus, the shaft cannot turn relative to the pinion gear without breaking the retainer. However, this retainer is not designed to i

transmit the main torque from the drive shaft to the pinion gear. The torque i

is intended to be transmitted directly from the shaft to the pinion by means of a press fit between the tapered shaft and the matching tapered pinion bore.

The retainer is only designed to maintain the press fit by keeping a clamping force on the outside end of the pinion.

l The basic cause of the air start motor problems at Diablo Canyon was loss of i

the pinion gear to shaft press fit as a result of an inadequate fitting of the j

shaft, pinion gear retainer, and bolting. This loss allowed the pinion gear toslipontheshaft,forcingtheretainertotransmitthefulltorqueofthe motor. This situation caused abnormal wear of the retainer and of the tang on the end of the shaft, cracking and deformation of the tang, and the loosening and backing out of the retainer bolts.

Eventually two retainers for the start motors on diesel generator 1-1 failed completely, preventing the diesel genera-r tor f rom starting.

The loss of contact was attributed to a number of subsidiary problems, includ-i ing poor fit between the pinion gear and the shaft surfaces, dirt on the surf aces, lack of " setting" pressure on the pinion gear during assembly onto the shaft, and incorrect torouing of the retainer bolts. However, the main i

problem appears to have been improper fit between the retainer and the pinion As shown in the detail on tie lower half of Figure 1, there is a sharp gear.

angle at the transition between the retainer inner surface and its slot wall.

l On the mating surface of the pinion gear, however, there is a radius between l

the side of the lug and the outer flat surface of the gear.

As a consequence, l

the sharp edge of the retainer slot presses on the curvature of the radius at the base of the pinion gear lug. This small contact area eventually degener-i ates as a reruit of shock loading, relieving the pinion retainer clamping force. This problem was identified on 13 of the air start motors at Diablo l

Canyon.

l l

IN 89-XX November xx, 1989 l

g Page 3 of 3 l

3, A possible contributory cause to the failure of one of the two air start motors that feiled on February 1 was the fact that the air supply to this motor was higher than normal on that day.

Records indicate that the pressure supplied to this motor was 190 psi compared to a normal value of 150 psi. The vendor indicated that a pressure in excess of 160 psi would begin to be of concern.

l It has been suggested that the unusually high pressure caused the first motor to fail, which lef t the second motor to carry the full load, causing it to fail also. However vendor tests show that only one air start motor is required to start a diesel, generator within the required time limit.

Furthermore, the clutch in the start motor drive train should have limited the torque in the train to the design limits.

l The corrective actions for this problem included the replacement of all of the damaged parts, using revised reassembly procedures. The reassembly procedures included lapping and blueing checks to ensure the correct fit. The procedures also specified the correct retainer bolt torque and the use of lock washers and In lock wiring to raintain the correct retainer force on the pinion gears.

measures were taken to ensure that the start motor air header pres.

addition,ld be maintained below 160 psi.

sures wou This information notice requires no specific action or written response.

If you have any questions about the information in this notice, please contact the technical contact listed below or the appropriate NRR project manager.

i Charles E. Rossi, Director Division of Operational Events Assessment Office of Nuclear Reactor Regulation i

Technical

Contact:

D. C. Kirkpatrick, NRR (301)492-1152 Attachments:

1.

Figure 1 2.

List of Recently Issued NRC Information Notices

,_.--..--r

-..c n

C

+*'

mWaher seis m Crack in

~!

mmor shen maaher ll(k\\

k l lE w///

9 I

l l l

Crack in y

M

shen l

m osar Press 1,wnh press a lost A

y RoiorShen c:""

,.she, o,a. 4

2. Retainer halves ward causing

,w,an in iension o

Normal Assembly Assembly During Failure Lug on Phlon Gear l

i l

Engages RWainer

[ Cross Slot j

Sharp Outside

/ Comer shwp une Contact Provides All of Clar@ing

[

'g

  1. G4P

\\

n s

y

\\

/

\\

Radius at Base s

f

%d ofLug Detall of Contact I

l Assembly Showing Poor Rt Between Retainer and Gear Figure 1 Rotor Shaft and Pinion Gear Assembly t

.