Accepts NEDO-10905-3,Amend 3, High Pressure Core Spray Sys Power Supply Unit, Qualification Test Results of High Pressure Core Spray Diesel Generator for Described Generator
ML19323G883
Person / Time
Issue date: 04/07/1980
From: Parr O
Office of Nuclear Reactor Regulation
To: Sherwood G
GENERAL ELECTRIC CO.
References
NUDOCS 8006090146
Download: ML19323G883 (2)


Text

5

(,5 b

pM t 20 9'o,,

UNITED STATES

~

8 NUCLEAR REGULATORY COMMISSION n

h WASHING TON, D. C. 20555

%, *.. +,of Central Files - Topical Reports l

l Dr. G. G. Sherwood, Manager i

Safety and Licensing General Electric Company 175 Curtner Avenue San Jose, California 95114

Dear Dr. Sherwood:

SUBJECT:

GENERAL ELECTRIC TOPICAL REPORT NED0-10905-3 AMENDMENT 3, "HIGH PRESSURE CORE SPRAY SYSTEM POWER SUPPLY UNIT" In a letter dated December 20, 1979, you provided copies of NED0-10905-3 Amendment 3, "High Pressure Core Spray System Power Supply Unit." This amendment presents the results of the prototype qualification testing of the HPCS Diesel Generator: Diesel Engine GM-EMD Model 20-64SE4; Generator Ideal Electric Company Type - SAB, Frame - M636PB.

The topical report includes a prototype qualification test plan, test pro-cedures, acceptance criteria and test results.

The purpose of this test was to demonstrate the capability and reliability of the diesel generator (2600 kw) to attain and to stabilize voltage and frequency within acceptable limits while starting the HPCS pump motor (3000 HP) under load and carrying all auxiliary loads in accordance with design requirements.

Our evaluation is summarized as follows:

(1) The testing was performed in situ (preoperationally) in a nuclear power plant installation, with engine start performed from both cold ambient and hot engine temperature conditions, (2) The HPCS pump motor and auxiliary loads automatically started.

During loading, the system voltage dipped to about 65% and recovered to 73%

within 0.5 seconds.

The voltage recovered to 80% within 3.5 seconds and rated voltage within 6 seconds. Also, the HPCS pump motor came up to rated speed in 6 seconds and rated flow was achieved within about 8 seconds. The frequency dropped to 87% of rated frequency at starting loads and recovered to rated condition within 2.5 seconds.

Y GE pe. -

8006090lb

Dr. G. G. Sherwood, Manager APR 0 71980 RG 1.9 requires that the diesel generator unit design should be such that at no time during the loading sequence should the frequency and voltage decrease below 95 percent of nominal and 75 percent of nominal, respectively. However, the HPCS diesel generator unit carries a single large HPCS motor-pump load, more than 90 percent of the design load on the HPCS bus, and therefore, a larger decrease in frequency and voltage is acceptable for the HPCS diesel generator unit provided acceptable performance on a system basis is demonstrated.

During the testing the motor starting transient voltage dipped to 65% and recovered to '73%

within 0.5 seconds and to 80% within 3.5 seconds; the frequency drop was 13% of rated and recovered to rated condition within 2.5 seconds.

System operation was acceptable throughout.

The HPCS power supply system has performed its start and load design function within 23 seconds from the time of the actuation signal.

It fully met the design requirement of establishing rated flow within 27 seconds.

(3) The D-G, with the actual pump and motor, was operated at its continuous rating with the HPCS pump operating at the maximum bhp flow condition.

To simulate as close as practical the actual HPCS system configuration, the pump received water supply from the condensate storage tank.

Since the reactor was not pressurized, the water flow was returned back to the condensate tank after passing through a set of valves that were set to simulate the reactor pressure. Additional runs were made over a range of flow conditions. A comparison of these runs with the manufacturers' pump-head flow curve is in agreement.

Therefore the HPCS has the head-flow characteristics designed for.

(4) The reliability of starting and accepting design load in the required time was fully demonstrated by starting and carrying design load 69 times without failure from both hot and cold engine conditions.

This met the objective of establishing a 0.99 reliability for the particular DG design.

On the basis of this review, we conclude that the qualification test results of the HPCS diesel generator unit are acceptable.

It is noted that this acceptance is only for the particular design generator unit identified above.

Each of the other diesel generators listed in NED0-10905 (Table 3-1) must undergo similar prototype qualification testing to be acceptable.

Sincerely, ar'r,CIef Light Water Reactors Branch No. 3 Division of Project Management cc: Mr. L. Gifford General Electric Company 7910 Woodmont Building Bethesda, Maryland 20014 s