ML19322E580

From kanterella
Jump to navigation Jump to search
Submits Comprehensive Evaluation on Three Util Fire Detector Analyses,Separately Evaluated by BNL on 800303,0212 & 791130.NRC Should Study Effects of Congestion,Ventilation/ Stratification on Detector Performance
ML19322E580
Person / Time
Site: Point Beach, Prairie Island, Yankee Rowe, Fort Calhoun
Issue date: 03/20/1980
From: Baccio J
BROOKHAVEN NATIONAL LABORATORY
To:
Office of Nuclear Reactor Regulation
References
NUDOCS 8003280455
Download: ML19322E580 (3)


Text

%

y.

]

.. J,j j j BROOKHAVEN NATIONAL LABORATORY

,, _,1'J l, ASSOCIATED UNIVERSITIES. INC.

i

.. J J

Lpton, New York 11973 Depcrtment of Nuclear Energy (510) 345 7690 March 20,1980 Mr. Robert L. Ferguson Plant Systems Branch U.S. Nuclear Regutatory Commission Washington, D.C.

20555

Dear Bob:

During the past 6 months part of my effort in fire safety entailed evalua-tions of fire detector analyses submitted to the Nuclear Regulatory Cowission by three utilities; namely, Wisconsin Electric Power Company for their Point Beach facility, Omaha Public Power District for their Fort Calhoun facility, and the smoke simulation prototypic tests conducted by NUTECH Corporation at the Yankee Rowe nuclear plant. My evaluation of each of these approaches were sent to you by letters respectively dated March 3,1980, February 12, 1980 and November 30, 1979.

The purpose of this letter is to provide a concerted sumary of the above approaches. Recall, that each of my appraisals of the licensee's approach had been based upon their responses to (1) the need for specifying the environment to which fire detectors are exposed, and (2) their development of means to predict the response of fire detectors to particular combinations of environ-mental properties generated by a fire, which includes assessment of the ef-fects of ceiling height and configuration a

e potential fire development and growth e detector sensitivity to liberated combustion products e room congestion e ventilation e stratification e detector selection At the outset, I must state that even with present day state-of-the-art technology in smoke detector siting, engineering judgement by responsible en-gineers is still required. Of course, advances have been made which alleviate to some extent the need for total qualitative assessment.

Suggested guide-lines as to the effect of ceiling height, combustible material, detector type, Aco6

.s do 8003280 4 s 5 A

To:

R.L. Ferguson March 20, 1980 fire size and growth rate, and response time alluded to in various codes (e.g.

NFPA 72E) can now be quantified due to the recent efforts of the Fire Detec-tion Institute.

Indeed, more research is required especially to assess the effects of ventilation, stratification and congestion; studies involving smoldering type fires involving electrical cables is also imperative.

The need for further research in this area notwithstanding, of the three submitted approaches, we consider the approach adopted by Wisconsin Electric Power Company in their report " Fire Detection System Selection Criteria" transmitted to NRC by letter dated December 20, 1979 to be the most suitable.

We have found the approach adequate since it contains a viable mix of sound engineering judgement, present day state-of-the-art smoke detector siting technology, and the use of visual smoke for siting assessment. All of the factors listed above are either considered directly or their consideration is inferred. This indicates to us that well informed individuals, congizant of the problems associated with detector siting technology, have prepared the noted document. Also, their fire detector location plan and the procedures used for generating such a plan, should be instituted by other utilities that are contemplating a fire detector analysis.

The Omaha Public Power District submittal entitled " Fire Detector Anal-ysis, Fort Calhoun Station, Unit 1," transmitted to NRC by letter, dated January 8, 1979 is also noteworthy in the effort used to generate their de-tector location scheme. However, when compared to the Point Beach Approach, it is not as comprehensive.

Its documentation and added comments lack the de-tail that is portrayed in the latter approach. And, it utilizes guidelines in some areas we consider as outdated when compared to those recently presented by the Fire Detection Institute.

Indeed, their guidelines of detector loca-tion in beamed ceiling areas may be questionaL;a. The effect of ceiling height on detector spacing has not been explicitly addressed in this analysis as well as possible effects of stratification.

The NOTECH approach described in their report " Smoke Simulation Prototype Test Conducted at Yankee Rowe Nuclear Plant" and submitted to NRC by letter dated October 3,1979 is, of the three, a truly in situ test scheme. The use of a tracer gas, e.g., SF, as a surrogate smoke, and the subsequent mea-6 surement of its concentration with time at select locations within the test enclosure (switchgear room at the Yankee Rowe facility) indeed can provide, with proper interpretation of the data collected, a more cogent picture of how smoke may disperse. Thus effects of congestion, ventilation, and possibly stratification, (although this has not been fully tested) on smoke movement may be implicitly assessed if the correspondence between gas movement and aer-osol movement has been established; however, the implementation of the ap-proach is considered impractical. Possibly its feasibility may become more attractive if sample collections could be automated thereby requiring less individuals for the conduction of the tests. Also the translation of the data recorded for direct application for smoke detector siting must be performed by individuals knowledgeable in the operations and problems associated with de-tector siting. The idea of siting detectors where " smoke" is first registered is tantamount to the idea that the convective flow in the proposed area is high. However, high flow velocity affects detector performance and hence strictly using maps of gas concentration with time may be insufficient.

5

'r To:

R.L. Ferguson March 20, 1980 0

Indeed, we feel that a practical in situ scheme is still required. And we also concur that the SF6 tracer gas technique which has found wide applica-tion for the determination of the gross movement of smoke is a viable ap-proach. There is still lacking a quantitative correlation between the mea-surements provided by this technique with the actual quantity and movement of smoke from actual fires that triggers a given detector.

In closing, we suggest that the NRC initiate efforts to study the effects of congestion, ventilation / stratification on detector performance. We further suggest that tests should be undertaken to establish whether the tracer gas technique (still considered as viable) can provide reliable and practical field data on the movement of smoke within a single large compartment. D i f-ferences between smoldering and flaming fires resulting from fuels indigenous to a reactor facility, notably electrical cables, must also be made and fact-ored into existing test standards design to assess individual detector perfor-mance.

Yours truly:

L_

eclo Dr. John Boccio Reactor Engineering Analysis JB:sd cc.:

R. Hall W. Kato M. Levine E. MacDougall V. Panciera E. Sylvester 5