Forwards Response to IE Insp Rept 50-320/79-15.Corrective Actions:Superintendent of Const Instructed to Ensure Compliance W/Welding & Cutting Procedure for Fire Safety & Welding & Cutting Permit Program Reinforced
ML19322A494
Person / Time
Site: Crane 
Issue date: 09/14/1979
From: Herbein J
Metropolitan Edison Co
To: Grier B
NRC Office of Inspection & Enforcement (IE Region I)
Shared Package
ML19322A493 List:
References
GQL-1180, NUDOCS 7911060186
Download: ML19322A494 (2)


Text

__ __ _ _ -___ _

e s

~

Metropolitan Edison Cornpany

-(

e Post Office Box 542 Reading Pennsylvania 19640 215 929 3601 Writer's Direct Dial Number September 14, 1979 GQL 1180 Office of Inspection and Enforce =ent Mr. B. H. Grier, Director Region 1 il. S. Nuclear Regulatory Co==ission 631 Park Ntenue King of Prussia, Pennsyltania 19h06

Dear Sir:

Three Mile Island Nuclear Station, Unit 2 (DII-2)

Operating License No. DPR-73 Docket No. 50-320 Inclosed please find our respcase to Inspectica Report 50-320/79-15 Sincere 17, s

J.

. Eerhein f

Vice President-Nuclear Cperations JGH:EAL:tas Inclosure

(

7911060

  • } Tb Metrcccican Eisen Ccercany s a Vemcer f the Generai %che U**tes SysMrn

s.

RESPCNSE TO INSPECTICN REPORT 50-320/79-15 e

Notice of Violation Infraction A 10 CFR 50, Appendix 3, Criterion V, stater: " Activities affecting quality shall be pr, scribed by documented instructions...and shall be accocplished in accordance with these instructions..."

Licenum Procedure lkl0-Y-26 states in parag.aph 6.2.1:

" Area Preparation:

Shall be clear of a.

umulations of ec=bustitles such as trash, rags, etc."

Contrary to the above on May 30, 1979 co=bustible trash and unnecessary.

lumber vere accu =ulated in the fuel storage area while major modifications vere undervay.

This item is considered to be an infraction.

Corrective Action A The Superintendent of Construction, during this phase of Unit II recovery, has been instructed to ensure eccpliance with Maintenance Procedure lh10-Y-26,

"'4elding and Cutting Procedure for Fire Safety".

The area identified in the Lafraction was restored to acceptable conditions when identified by Mr. Koltay.

Subsequent inspections by plant personnel have shown this situation to be acceptable.

Ir. fraction B 10 CFR 50, Appendix 3, Criterion V, states: " Activities affecting quality shall be prescribed by docu=ented instructions...and shall be acco=plished in accordance with these instructions..."

Licensee Procedure lkl0-Y-26 states in paragraph 6.2.7: " Appropriate fire extinguishers shall be readily accessible at the work location".

Contrary to the above on May 30, 1979 velding operations vere in progress in the fuel storage area without fire extinguishers in the area.

This item is considered to be an irfraction.

Corrective Action 3 Responsible personnel have reinforced the velding and cutting permit program in the plant. Subsequent inspections of welding and cutting operations show this ites to be in co=pliance. To further reduce the possibility.of reccurance, fire extinguishers are now issued with 'the veld rod for velding jobs.