Responds to NRC Re Violation Noted in IE Insp Repts 50-313/80-07 & 50-368/80-07.Corrective Actions: Junction Box Cover Replaced & Door on End Closed
ML19321B240
Person / Time
Site: Arkansas Nuclear  
Issue date: 06/27/1980
From: Trimble D
ARKANSAS POWER & LIGHT CO.
To: Seyfrit K
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
Shared Package
ML19321B238 List:
References
1-060-26, 1-60-26, 2-060-36, NUDOCS 8007300325
Download: ML19321B240 (2)


Text

A y

b b

ARKANSAS POWER & LIGHT COMPANY POST CFFICE box 551 UTTLE ROCK. ARKANSAS 72203 (501) 371-4000 June 27, 1980 1-060-26 2-060-36 Mr, K. V. Seyfrit, Director Office of Inspection & Enforcement U. S. Nulear Regulatory Commission Reg'on IV 611 Ryan Plaza Drive, Suite 1000 Arlington, Texas 76011

Subject:

Arkansas Nuclear One - Units 1 & 2 Docket Nos. 50-313 and 50-368 License Nos. DPR-51 and NPF-6 Response to Inspection Reports 50-313/80-07 and 50-368/80-07 (File:

0232,2-0232)

Gentlemen:

In response to the Item of Noncompliance included in the subject report, the following is provided.

NOTICE OF VIOLATION Based on the results of an NRC inspection conducted during the period of April 22 through May 21, 1980, it appears that certain of your activities were not conducted in full compliance with NRC regulations and the conditions of your licenses DPR-51 and NPF-6, as indicated bel w:

The licensee failed to adhere to the procedural requirements relating to the use of Job Orders during the performance of maintenance on High Pressure Safety Injection (HPSI) valve 2CV-5076 (the normally shut valve that automatically opens on an Engineered Safety feature signal to allow HPSI flow to 'D' reactor coolant loop).

Specifically, elec-trical corrective maintenance was performed on valve 2CV-5076 under job order 2-2012-80 which was subsequently documented to be complete i

and the valve ready to be r1 turned to service on April 7, 1980.

On April 29, 1980, the electrical junction box cover (2TB 903) was found to be missing from valve 2CV-5076 and the junction box door on the supply end was open.

8007300325

_,,_ cm,c m,- m,,m,,,,,,,, _

Mr. K. V. Seyfrit June 27, 1980 This is an infraction (368/80-07-01).

RESPONSE

The junction box cover (2TB 903) was replaced and the door on the end was closed. This was done on J.0. #2-2045. All appropriate personnel were advised of the controls regarding use and compliance with procedures, and appraised of the necessary precautions for closing out job orders.

Full compliance has been achieved.

Very truly yours, b & $*

David C. Trimble Manager, Licensing DCT:GAC:ms cc: Mr. Victor Stello, Jr., Director Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission Washington, D.C.