r 9

O APPENDIX A NOTICE OF VIOLATION Tennessee Valley Authority License No. CPPR-152 Hartsville A-2 Based on the NRC inspection March 31 - April 25,1980, certain of your activities were apparently not conducted in full compliance with NRC requirements as indi-cated below. These items have been categorized as described in correspondence to you dated December 31, 1974.

As required by Criterion V of Appendix B to 10 CFR 50, and as implemented by PSAR Section 17.la.5, " Activities affecting quality shall be prescribed by documented instructions, procedures,...and shall be accomplished in accordance with those instructions, procedures,...". TVA Procedure RIS&PM Interim Procedure Mechanical M-650, Rev. O dated 10-24-79 entitled Reactor i

Pressure Vessel (NSSS)-QA-ASME Section III-MPL No. B13-D001 set forth requirements as follows for storage and maintenance of the RPV:

1.

Procedure M650-Rev.1, Section B, Storage, paragraph 1.

Horizontal Position - Storage Yard, subparagraph i states "The.cem shall not be stored in areas adjacent to: unpaved roads heavily traveled by site j

vehicles or other than dust making operations.

Contrary to the above, a frequently traveled haul road was opened adjacent to the vessel stora'ge area and the area has become showered with dust.

2.

Procedure M650-Rev.1, Section C Preventive Maintenance paragraph 3 states "For heated vessels, the temperature of the heated surfaces shall be checked at three equally spaced locations at least once a day".

Contrary to this lequirement, temperature measurements were not being taken as of April 25, 1980.

This is a deficiency.

8007240 3

2

..