ML19321A159

From kanterella
Jump to navigation Jump to search
Interim Deficiency Rept Re Notification by Comsip of Pump Malfunction on Similar Containment Gas Monitoring Sys. Caused by Deadheading,Resulting in Excessive Pressure. Vendor Has Agreed to Provide Kit for Adding by-pass
ML19321A159
Person / Time
Site: Fermi 
Issue date: 07/10/1980
From: Fahrner W
DETROIT EDISON CO.
To:
References
EF2-49-018, EF2-49-18, NUDOCS 8007220545
Download: ML19321A159 (1)


Text

a*t\\\\

,J b % *'S o n m m r..nu.

roco secona A July 10, 1980

C a>2' EF2-49,018 s

Mr. James C. Keppler Directorate of Regulatory Operations Region III U.S. Nuclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, Illinois 60137

Subject:

Interim Report of 10CFR50.55(e) Item on Containment Gas Monitor-ing System.

Dear Mr. Keppler:

On June 23, 1980, Mr. H.A. Walker of Detroit Edison's Quality Assurance Department, telephoned Mr. Van Dell of NRC-Region III to report that we had received notification from Comsip, Inc., the Supplier of the Fermi 2 Con-tainment Gas Monitoring System, that they had reported problems to NRC-Region V under 10CFR21 requirements.

It was reported that a pump malfunc-tion during a test at Consip on a similar system had created excessive pressure which could conceivably rupture the diaphram, and breach the con-tainment integrity of the system.

The correspondence from Comsip, Inc. stated that a kit will be made avail-able to add a by-pass on the discharge of the pump to prevent deadheading, which will eliminate excessive pressure and the possibility of this type of failure or damage. This kit and associated documentation have been requested by Detroit Edison.

A final report on this item is scheduled to be submi.tted to you before October 23, 1S80.

If you have any questions concerning this matter, please contact Mr. H.A. Walker, Supervisor - Construction Quality Assurance.

Sincerely, yg.w W.J. Fahrner, Manager Enrico Fermi 2 i

WJF/ HAW /pn cc:

Mr. Victor Stello Jr., Director Office of Inspection and Enforcement Division of Reactor Inspection Programs U.S. Nuclear Regulatory Commission Washington D.C.

20555 Mr. Bruce Little, Resident Inspector U.S. Nuclear Regulatory Commission Resident Inspectors Office 6450 North Dixie Highway Newport, Michigan 48166 g

h

- 80 072 2 0 ft/f f

1@

k l