NPDES Noncompliance Notification:On 800630,daily Max Limit for Oil & Grease of Less than 20 mg/1 Was Exceeded.Weekly Grab Sample Indicated 26.2 mg/1 Oil.Caused by Failure of F20/M13 Filter Elements.Filters Replaced
ML19321A118
Person / Time
Site: Palisades 
Issue date: 07/14/1980
From: Fobes R
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To:
Shared Package
ML19321A116 List:
References
PAL-80-06-NC37, PAL-80-6-NC37, NUDOCS 8007220484
Download: ML19321A118 (1)


Text

,g L )

File No P10.2.1

'^'

Incident No:

PAL-80-06-NC37 NPDE3 NONCOMPLIANCE NOTIFICATION Possibic Noncompliance With Daily Average / Maximum Limitation July 14, 1980 Plant: Palisados Permit No: MI 0001457 Outfall

Description:

Turbine Sump 011 Separator Outfall No:

800218 Waste (00G)

~ Parameter: Oil and Grease Parameter No:

00556 1.

Date of Incident:

6/30/80 2.

Identification of' specific effluent limitation exceeded:

Daily maximum limit for oil and grease of less than 20 mg/1.

3.

Description of Incident: The weekly grab sample for oil and grease collected, 6/30/80 indicated 26.2 mg/l oil.

/

4.

Apparent Cause: Failure of F20/M13 filter elements.

5.

If not immediately corrected, the anticipated time the condition is expected to continue: NA 6.

Corrective Action - The following corrective action was taken or will be taken to reduce, eliminate and prevent recurrence: The suspect filters were replaced on 6/30/80.

7.

Additional Comments: NA 8.

Signed: R L Fobes