THE CINCINNATI GAS & ELECTRIC COMPANY ywf,es CINCINN AT1.OMIO 4 5201 Y/ 6 June 30,1980 QA-1311
' Ago;, %^,NN U. S. Nuclear Regulatory Commission Region III 799 Roosevelt Road Glen Ellyn, Illinois 60137 Attention: Mr. R. F. Heishman, Chief Reactor Operations and Nuclear Support Branch RE: WM. H. ZIMMER NUCLEAR POWER STATION UNIT I NRC INSPECTION REPORT NO. 50-358/80-12 DOCKET N0. 50-358, CONSTRUCTION PERMIT CPPR-88, W. O. #57300-957, JOB E-5590 Gentlemen:
This letter constitutes our fortnal reply to the subject inspection report.
It is our opinion that nothing in the report or in this reply is proprietory in nature.
Our response to the item of noncompliance cited in Appendix "A" of the report is as follows:
Miscellaneous Material in Reactor Building Cable Pans a) Corrective Action Taken and Results Achieved Foothill Electric cable pulling procedure FEC INI-007, requires cables to be installed in cable pans which are free of debris and rubbish.
Prior to every cable installation, the inspector must verify a clean cable route in the pan system prior to placing the cable in the cable pan.
Imediately after the plant tour of the Reactor Building and Cable Spreading Room, in which debris was found in the cable pans, clean-up crews were dispatched to remove the debris and rubbish which had accumulated after the last cable pull.
b) Corrective Action to be Taken to Avoid Further Noncompliance Cable tray cleaning crews have been assigned to the Reactor Building and Auxiliary Building, including the Cable Spreading Room, on a continuing fixed weekly schedule so that each area and location containing cable pans are inspected and cleaned at)t,7 8 0 0 7 210 3/J
4
~
Mr. R. F. Heishman U. S. R:gulatory Commission R;gion III June
. 1980 - QA-1311 Page 2 if necessary on a specific day of the week.
c) Date When Full Compliance Will be Achieved This item will be considered to be in compliance by July 11, 1980, at which time a complete cycle of all areas will have been inspected and cleaned of debris if necessary.
We trust that the above will constitute an acceptable response to the subject inspection report.
Very truly yours, THE CINCINNATI GAS & ELECTRIC COMPANY hfrs.cz -
E. A. BORGMANN SENIOR VICE PRESIDENT RPE:ec
-