ML19320C892

From kanterella
Jump to navigation Jump to search
Notice of Violation from Insp on 800507-09
ML19320C892
Person / Time
Site: Phipps Bend  
Issue date: 05/21/1980
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML19320C879 List:
References
50-553-80-08, 50-553-80-8, 50-554-80-07, 50-554-80-7, NUDOCS 8007180220
Download: ML19320C892 (1)


Text

.

I APPENDIX A NOTICE OF VIOLATION Tennessee Valley Authority License Nos. CPPR-162 Phipps Bend

& CPPR-163 Based on the NRC inspection May 7 through 9,1980, certain of your activities '

were apparently not conducted in full compliance with NRC requirements as indi-cated below. These items have been categorized as described in correspondence ~

to you dated December 31, 1974.

As required by Criterion V of Appendix B to 10 CFR 50, implemented by PSAR Section 17.1A.5, " Activities affecting quality shall be prescribed by docu-mented instructions, procedures or drawings...and shall be accomplished in accordance with these instructions, procedures, or drawings." TVA specifi-cation G-2 requires delivery of materials from the batching equipment to be within the following limits of the mix design proportious determined in laboratory and field adjusted mixes: Flyash, I percent; sand, 2 percent; and 3/8 inch aggregate, 2 percent. Quality Control Instruction (QCI) C-212 requires the concrete batch plant inspector to visually inspect all scale dials as they weigh up and make or witness adjustments if scale dials indicate weights other than design mix weights. QCI-C-212 also requires the batch plant inspector to verify visually that the continuous recorder chart readings coincide with scale readings.

Contrary to the above:

1.

In batching of concrete for placement in safety related structures, flyash quantity exceeded the specified mix design quantity by 8 percent, the sand quantity exceeded specified mix design quantity by 4 percent, and the 3/8 inch aggregate exceeded specified six design quantity by 6 percent.

2.

The batch plant inspector did not visually inspect the scale dials as they weighed up and make or witness adjustments when scale dials indi-cated weights other than design mix weights.

3.

The batch plant inspector did not verify visually that the continuous recorder chart readings coincided with dial scale readings.

This is a deficiency.

8007180 oLBJ3