RO 50-313/77-08:on 770218,reactor Bldg Chilled Water Inlet Isolation Valve CV-6202 Failed to Remain Closed During Local Leak Rate Testing of Penetration 51.Caused by Foreign Matl in Solenoid Valve.Valve Replaced
ML19319E570
Person / Time
Site: Arkansas Nuclear 
Issue date: 03/18/1977
From: Mardis D
ARKANSAS POWER & LIGHT CO.
To:
Shared Package
ML19319E563 List:
References
NUDOCS 8004110824
Download: ML19319E570 (4)


Text

.

y 3

UCENSEE EVENT REPC,.<

O cONTROi. 8tOCx:l 1

I I I I

I

- m nr nu.am8u =8m use8m8a m ur 1

8 LCENet NUMGER lAIRlAIRIK1)I lo lo 1-101 o lolo lol-lo lo l 14l1111IIIl 10 13 t

l 7 89 14 15 25 28 30 31 3E

" pE CAfteomr TY souRct occx(T NUMSEA EVENT oATE RapORT o4TE O CONI l l

l

[LJ l1.l 1015 l01-10131113 l 1012 lI 17 l1 Il [

1013 ll l t 17 l !

7 8 57 S8 59 80 81 88 89 74 75 8'

Ev.ENT OEsCwnON sE I bsm exmw.ua smsroow. m 9aroemm toca \\ uv. om Testi a i

7 89 IE b-b702.. kocTest. bst os.wm l

h I WF It%ElkA7iod MS). \\T WAs bwnVElt%B T6.t AT ALUE 7 89 80 h Ib.to %. bsv b=iew be. u.us. we uw ei. essa.L %.m. o bx l

7 89 E

h lwun was ws,1. ace, wo Tne. % mv s,.wuse me mv. eem,co %mw J 7 89 80

@D8 Iw k owe e w wm. h su r wasa ase virioe eCco.=ews. (so-wh,-d i

7 89 20

,,ug oY c

COMPONENT Coot Mea #ACTtsER WOLATCN E Iwlal Lt.]

lv I A It. lv j a Ix I LAJ I E l a. l - l a l LHJ 7 89 10 11 12 17 43 44 47 48 CAUSE DESCRIPTION h { T%4 kne. %ews oosO W h.s #ouen OtaTV kNO 0.t.ggiato 0F Vots%d teAmi AL. MT Tu(*

I 7 89 80 32 I %< t.

. wonomo..% s.,o v ~x auss ves e.mm 8.o vatus J

C'N89 80 1Ic.v-42o2. u=s tiin. xm %.o w em.e,= soce u vo u v.

'OS "c'EcTvEE s powta orwta status oecovem oEscaeTON LwJ lololol 1 m

i lhJ l

uk I

7 8 9

10 12 13 44 45 48 80 S$o

$ASE RE o

AMouMS OF ACTMTV LMTON OF RELEASE E

liEl LEJ l

uA I

I an I

7 8 9

10 11 44 45 80 PERSONNEL EXPOSURES NUM8ER TYPE DESCAFTON lololol L2]

I na I

i 7 89 11 12 13 80 PERSONNEL INJUAtES NUMOER oESCAPTON E lololol I

uk J

7 89 11 12 OFFSITE CONSEQUENCES l

El Nk 7 89 LOSS OH DAMAGE TO FACIUTY tveE CEscA* TON hb!

NA l

7 89 10 I

80 PUBUCITY l

Mk I

1

/ 89 80 8004-110 @ y ADDITIONAL FACTOAS

~

ujl MA I

7 89 gg DE I I

7 89 l

NauE:-j h41e G. bana Soi/ 3 11-4 W PsONe

r 1.

Reportable Occurrence Report No.

50-313/77-8 2.

Report Date: 3/18/77 3.

Occurrence Date: 2/18/77 4

Facility:

Arkansas Nuclear One-Unit 1 Russellville, Arkansas 5.

Identification of Occurrence:

Reactor Building Chilled Water System Isolation Valve (CV-6202) was found to be inoperative.

6.

Conditions Prior to Occurrence:

Steady-State Power Reactor Power o

MWth Hot Standby Net Output o

NWe Cold Shutdown Percent of Full Power n

Refueling Shutdown X

load Changes During Routine Power Operation Routine Startup Operation Routine Shutdown Operation Other (specify) 7.

Description of Occurrence:

At approximately 1100 hours0.0127 days <br />0.306 hours <br />0.00182 weeks <br />4.1855e-4 months <br /> on February 18, 1977, while performing local leak rate testing of penetration #51, it was discovered that Valve CV-6202, Reactor Building Chilled Water Inlet' Isolation Valve, would not remain closed. The air solenoid was found to be dirty.

~

9 U

r q

j

\\

Reportable Occurrence Report No.

50-313/77-8, 8.

Designation of Apparent Cause of Occurrence:

j Design Procedure Manufacture Unusual Service Condition Including Environmental Installation /

Construction Component Failure X

(See Failure Data)

Operator Other (specify)

Foreign material was found in the solenoid valve which prevented positive actuation.

9.

Analysis of Occurrence:

Even though the isolation valve was found to be inoperative, the check valve would have isolated the Reactor Building inlet line, therefore no hazard to the health and safety of the public existed.

O a

7 9

O Reportable Occurrence Report No.

50-31?/77-8,

10. Corrective Action:

After the solenoid and supply lines were cleaned of the foreign material, the va!.ve remained inoperative. The two solenoid block valves were replaced and again the valve was tested. The test indicated the velve operated properly; hence, it was returned to t<e service at 1522 hours0.0176 days <br />0.423 hours <br />0.00252 weeks <br />5.79121e-4 months <br /> on 2/21/77.

i

. 11.

Failure Data:

A failure to CV-6202 was reported in Reportable Occurrence Report 50-313/76-32.

I e

6 U

~,,, - -. -. -... --,

e--

,