,3 4
,e
(
NSI'- 10 V
ATTACl! MENT "B" NON-ROUTINE REGULATORY REPO!1T REVIEW SilEET Plant:
Unit:
Report
Title:
d
/
f> m Report Number:
Reviewed and Approved by:
Plant Safety Committee Y'ES ()
NO (4
Plant Superintendent YES ()
N0 f<J
&,' d ('
Reference:
PG A-3 2_O Date:
Reviewed by:
)
Date:
7 f
Licensing Supervi:;or CN f/
Approved by: _ '
f4nagerofSucleafSsrvices Date: /
7f~~
Approved by:
///d/
VM4 rr[
[' [- M Date:
5
' ' ' Director of Powei Production
~
~
i
^-
r's
'\\,/
Attachment "B" April 23, 1975 NSP-10, Rev. 3 Page 1 of 1 80041107
,s
_e
\\j 1.
Non-Routine, Non-Radiological Environmental Report No.
50-313/75-42 2.
Report Date:
nugust 1, 1975 3.
Occurrence Date:
July 30, 1975 4.
Facility:
Arkansas Nuclear One-Unit 1 l
Russellville, Arkansas i
S.
Identification of Occurrence:
Chemical concentration of sodium nitrite in condenser circulating water increased across plant in excess of Environmental Technical Specification limits.
6.
Conditions Prior to Occurrence:
Steady-State Power X
Reactor Power 2388 MWth i
Hot Standby Net Output 786 Mwe Cold Shutdown Percent of Full Power 93 g i
Refueling Shutdown Load Changes During Routine (f-s,\\
Power Operation-
- 7. Gl Routine Startup Operation Routine Shutdown Operation Other (specify) i 7.
Description of Occurrence:
}-
Samples were taken from the intake and' discharge canals on July 28, 1975, and lab analysis indicates that sodium nitrite concentration in the plant discharge canal was 0.069 mg/l greater than sodium nitrite concentration in the intake canal. ETS limit is 0.005 mg/1.
0 v
r.-..
-w
a 5*
\\s_,/
Non-Routine, Non,-Radiological Environmental Report No.
50-313/75-42 8.
Designation of Apparent Cause of Occurrence:
Design Procedure Manufacture Unusual Service Condition Including Environmental Installation /
, Construction Component Failure Operator Other (specify)'
X Neutralizing. tank was being drained into the discharge fiume at the time of this occurrence.
9.
Analysis od Occurrence:
Samples were taken when the neutralizing tank was being drained into the discharge fiume.
Four circulating water pumps were in operation provid-ing approximately,750,000 gallons per minute dilution flow. The neutralizing tank contains water impurities renaining after regenerating s;
condens, ate demineralizers.
i L:
4 9
6 9
'~
8 9
l
.l.
c.
4
-\\
4 Non-Routine, Non-Radiological Environmental Report No.
50-313/75-42 J
f
- 10. Corrective Action:
'A revision to the Environmental Technical Specification concerning j-chen:ical discharges has been submitted to the NRC for approval.
l i