._

e.:

3.

..'.,o t-p.

I.

Non-Routinc, Non-Radiolop,ical Eny'*enmental.~ Report No. 50-313/75-43 2.

Report Date: '8-12-75 3.

Occurrence Date: 8-4-75'

'4.

Pacility:

Arkansas Nucicar One - Unit 1 Russellville, Ark.

i 5.

Identification of Occurrence:

Chemical. concentration of sodium nitrite, ammonia and " chloride in condenser circulating water increase across plant in excess of ETS limits.

6.

Conditions Prior to Occurrence':

Steady-State Power X

Reactor' Power 2415 M11th Hot Standby Net Output 790 p.nve Cold-Shutdown Percent of Full Power 94 T Refueling Shutdown Load Changes During Routinc

' Power Operation Routine Startup

O-

' Operation.

g Routino Shutdown Operation Other (specify) 5 i

7.

Description of Occurrenec:

Sampics were taken from the intake and discharge canals and Point J20 on

~

Monday, 8-4-75.

Lab analysis ' indicated the following parameters in excess of ETS limits.

' Parameter Units Increase ETS Limit

^

. Sodium Nitrito intake' irs. discharge PPM 0.04 6 0.005 Sodisim Nitrite Point #20 vs. discharge PPM 0.04 6 0.005 Chloride Point #20 vs. discharge PPM' 37 25 Ammonia intake vs. dischargo PPM 0.25 0.05 At monia Point #20 vs. discharge PPM 0.25 0.05

'r%

U O

t 8004110 ) M

~

--4

,,m--.,,,r,grg rwe

[~...

t. '

" */. :

-f'.

r--

)

[V

,Non-Routinc, Non-Radiological linvirremnental Report No. 50-313/75-13 i

i 8.

Designation of Apparent Cause of Occurrence:

Design Proceduro Manufacture -

UnusualServiceContkition g

Including Environmental i

L Installation /

Construction Component Tailtire Operator Other (specify) Neutralizing tank draining'into discharge canal at time of sampling.

9.

ANALYSIS OF 0CCURRENCE:

The neutralizing tank, whicit centains impurities remaining after regenerating the' condensate demineralizers and plant make-up water domineralizers, was being dumped into the discharge flume when samples were taken.

~

liquid releases were in progress at time of sampling.

No other 1

' 10.

CORRECTIVE ACTION:

Revised ETS has b'ecn submitted to NRC and is currently under review.

11.

FAILURE DATA:

i

' Environmental Reports No.This occurrence is similar to those reported in 50-313/75/25 through 50-313/75-42.

~

W e

4 p

a.

G o

  • 4 2

g