Summary of NRC 761028 Meeting W/Util in Bethesda,Md Re Separation Criteria for safety-related Electrical Cable Routing in Facility Conduits.Notifies of NRC Position & Requests Statement of Compliance within Five Days
ML19319C037
Person / Time
Site: Davis Besse 
Issue date: 11/09/1976
From: Stolz J
Office of Nuclear Reactor Regulation
To: Roe L
TOLEDO EDISON CO.
References
NUDOCS 8001300767
Download: ML19319C037 (2)


Text

Distribu. 1 g

Docket FiI ELD' NOV 91976 flRC PDR

~

ACRS (16)

IE (3) i Local PDR LWR 1 File D. B. Vassallo F. J. Willians J. Stolz Docket tio. 50-346 L. Engle bec:

J. R. Buchanan, tiSIC E. Hylton T. B. Abernathy, TIC R. Heineman D. Ross Toledo Edison Company J. Knight, SS ATTil: Mr. Lowell E. Roe R. Tedesco Vice President, Facilities H. Denton Development V. A. Moore Edison Plaza R. H. Vollmer 300 F.adison Avenue M. L. Ernst Toledo, Ohio 436S2 W. P. Gammill Gentlemen:

SEPARATI0i1 CRITERIA FOR SAFETY RELATED ELECTRICAL CABLE ROUTI'1G Ifi

(,0llDUITS FOR DAVIS BESSE, UNIT 1 A meeting was held on October 28, 1976 in Bethesda, Maryland between the staff and representatives of the Toledo Edison Company where the subject of electrical cable separation criteria was discussed.

In that discussion, you stated that safety redundant electrical cable conduits are either in contact or in close proximity to each other which is in nonconformance to your present design criteria. We indi-cated at the meeting that we would ao.ise you on our position regarding tnese r. utters.

On ilovember 1,1976, '4r. L. Engle, Licensing Project "anager, notified Mr. L. Roe, Assistant Vice President and 'luclear Project "anager, that our position is that no safety redundant electrical cable conduits shall be in contact.

This letter is a followup to the events described above It is the staff position that safety redundant electrical cable conduits shall be separated by at least 1 inch. Where conduits are secarated by less than 1 inch a flame retardant barrier shall be provided such as 1/2 inch thick abestos free Marinite or Kawool thermal blankets (your criteria).

We request that you advise us of your conformance to our position as stated above within five days receipt of this letter. The Davis Besse.

Unit 1 FSAR should be revised to reflect conformance to our position.

G fp

/

OFFICE W SURM&MEM

... ~....

DATE M Forum AEC 51s (Rev. 9 53) ABCM 0240 W u. s. oovEnn,sur rninviene orriers seis.sas.see 800130 0 7f 7

e' 3

Toledo Edison Company Please call us if you have any questions concerning the matters iiscussed above.

Sincerely.

Original Signed Y hh t F. Stolz John F. Stolz, Chief Light Water Reactors Branch No. 1 Division of Project Management cc: Mr. Donald H. Hauser, Esq.

The Cleveland Electric Illuminating Company P. G. Box 5000 Cleveland, Ohio 44101 Gerald Cnarnoff, Esq.

Shaw, Pittm n, Potts and Trowbridge 1800 ;1 Street,:1. W.

Washington, D. C.

2003G Leslie Henry, Esq.

Fuller, Seney, Henry and Hodge 300 Madison Avente Toledo, Ohio 43604 LWR 1

,EIfSB LWR 1

.,,,e.

((ng

$ Mj lgr_

suwNau c h ll }[Q../ 76

_ll/h[76 $

ll

/J6 naru k Forsa AEC 318 (Rav. 7 53) A1CM 0240 L

  1. u.s. sovs'RNMENT PRINTING OPPICEE 1974 38810e