ML19318A596

From kanterella
Jump to navigation Jump to search
Forwards Updated LER 79-017/03X-1
Date released: 11/28/2019 Download: ML19318A596


Updated LER 79-017/03X-1:on 790911,during Monthly Test, Diesel Generator 1 Tripped on Low Oil Pressure After Approx 3 Minutes of Operation.Caused by Inadequate Corrosion Inhibitor Resulting in Exfoliation Type Solder Corrosion
ML19318A598
Person / Time
Site: Arkansas Nuclear 
Issue date: 05/22/1980
From: Shively C
ARKANSAS POWER & LIGHT CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
Download: ML19318A598 (1)
Forwards Updated LER 79-017/03X-1
ML19318A595
Person / Time
Site: Arkansas Nuclear 
Issue date: 05/22/1980
From: Trimble D
ARKANSAS POWER & LIGHT CO.
To: SEYFRIT K V
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
Download: ML19318A595 (1)