ML19316B109

From kanterella
Jump to navigation Jump to search
Forwards LER 80-012/03L-0
Date released: 11/26/2019 Download: ML19316B109


LER 80-012/03L-0:on 800428,reactor Water Conductivity Exceeded 10 Umhos/Cm Tech Spec Limit.Caused by Depleted Demineralizers.Unit Shutdown Initiated.Demineralizers Regenerated & Low Conductivity Coolant Added to Reactor
ML19316B115
Person / Time
Site: Quad Cities 
Issue date: 05/27/1980
From: Vahrenwald J
COMMONWEALTH EDISON CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
Download: ML19316B115 (2)
Forwards LER 80-012/03L-0
ML19316B108
Person / Time
Site: Quad Cities 
Issue date: 05/27/1980
From: Kalivianakis N
COMMONWEALTH EDISON CO.
To: KEPPLER J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
Download: ML19316B108 (1)