ML19312E545

From kanterella
Jump to navigation Jump to search
Informs That Licensee Submitted Addl Info on 800408 Re Fire Protection Review.Evaluation Encl Re Item 3.1.5,water Suppression
ML19312E545
Person / Time
Site: Dresden  Constellation icon.png
Issue date: 06/02/1980
From: Randy Hall
BROOKHAVEN NATIONAL LABORATORY
To: Ferguson R
Office of Nuclear Reactor Regulation
References
NUDOCS 8006050276
Download: ML19312E545 (2)


Text

I BROOKHAVEN NATIONAL LABORATORY ASSOCIATED UNIVERSITIES, INC.

Upton. New Ycrk 11973 Depcrtment cf Nuc!ect Er.ergy (516) 345-2144 June 2, 1980 Mr. Robert L. Ferguson Chemical Engineering U.S. fluclear Regulatory Commission Washington, D.C.

20555 RE: Dresden 2 a 3, Fire Protection Review, Item 3.1.5 Water Surpression

Dear Bob:

The referenced item was addressed in our letter to you on February 28, 1980. However, since that time the licensee (on April 8,1980) submitted ad-ditional information.

The attached letter addresses this lice isee letter.

Respectfully yours,

-- r ~.

y ?w i___ ?.,' ',,

Robert E. Hall, Group Leader Reactor Engineering Analysis REH:EAM:sd attachment cc.:

V. Benaroya W. Kato M. Levine E. MacDougall Obl s

/!/

8006050 2)(o

[

DRESDEN 2 & 3 Fire Protection Review Item 3.1.5 - Water Suppression Systems Information on item 3.1.5, Water Suppression Systems, was submitted in Sep-tomber of 1978. Upon review of this information, additional details were requested on a number of subitems. This additional information was submitted on November 30, 1978, January 4,1979, March 7,1979, June 11,1979, July 13, 1979, July 24,1979 and December 4, 1979.

All the items urMer 3.1.5 for review were acceptable except for the preaction system on the mezzanine. This system protects the cable concentration con-taining redundant divisions.

On April 8,1980 the licensee submitted additional information concerning the redundant divisions of safety related cabling in this area.

The licensee indicated that the entire area may be lost in a fire and the plant would still be able to achicre a safe shutdown.

Based upon the new information submitted in the April 8,1980 letter the de-sign of the preaction deluge sys'. ems is acceptable.

l f

i l

l l

l