ML19310A240
| ML19310A240 | |
| Person / Time | |
|---|---|
| Site: | Trojan File:Portland General Electric icon.png |
| Issue date: | 05/20/1980 |
| From: | Axelrad M LOWENSTEIN, NEWMAN, REIS, AXELRAD & TOLL |
| To: | Mccollom K, Mark Miller, Paxton H Atomic Safety and Licensing Board Panel |
| Shared Package | |
| ML19310A241 | List: |
| References | |
| NUDOCS 8006060348 | |
| Download: ML19310A240 (2) | |
Text
_
Law CFFICES LoWENSTEIN, NEWM AN, REIs, AXELRAD & TOLL so25 CON N ECTICUT AVENUC. H. W.
WASHI NGTON. O.C. 20 0 3 6 lg no a.e towcmsegin saca. =cewa=
y 202*B62-8400 use et as one O
cavio..Yos6 DCCKETED
\\%
. 1-6ec s
- s....ou.
...e. s.
USNac
..c..<6a...w.c.
w pL_
MAY 2 21980 >
<o.. c........
n
.t...,..c..
s.
C(fl:e cf ggg $gg7,ga n ~s w.corrvea-a=
Yo'."n'$ ' ~.. 'c u's l OCAltIllZ 5 ECTVICs B*ch
',/f.
L'," M';;."..,,.
c
" g
... o n. c. c...
%,", o'2.'.,*.7,' ' '
May 20, 1980 Marshall E. Miller, Esq., Chairman Dr. Hugh C. Paxton Atomic Safety and Licensing Board 1229
.41st Street U.S. Nuclear Regulatory Commission Los Alamos, NM 87544 Washington, D. C.
20555 Dr. Kenneth A. McCollom, Dean Division of Engineering, Architecture & Technology Oklahoma State University Stillwater, OK 97074 Re:
Portland General Electric Company, et al.
(Trojan Nuclear Plant)
Docket No. 50-344 (Control Building Proceeding)
Gentlemen:
Enclosed is a copy of a letter dated May 19, 1980 from Portland General Electric Company to the NRC Region V Office of Inspection and Enforcement regarding discovery of a wall of the Auxiliary Building which is not adequately connected at its top to interfacing structural elements.
As pointed out in the letter, this wall was assumed to be connected and to participate as a minor structural shear-resistance element in the STARDYNE analyses.
However, since Jt is in close proximity to a parallel 4 ft. thick shield wall and its relative strength and stiffness are low, re-moval of the wall from the STARDYNE model or reduction of its shear capacity to zero will not reduce.the capability of the as-built structure below that required to resist the SSE.
In any event, prompt corrective action is being taken to connect the wall such that it will participate as assumed 17 in the STARDYNE analyses, g
80 060e 03@ G
LowENSTEIN, NEWMAN. REIM, AXELRAo & TOLL Marshall E. Miller, Esq.
Dr. Hugh C.
Paxton Dr. Kenneth A. McCollom Pasa Two May 20, 1980 In accordance with the letter, PGE will file additional information with the NRC, including a more detailed report as to the occurrence and its cause, the corrective action being taken, and the results of. reviews being undertaken to determine if similar conditions exist elsewhere.
Copies of all such information w ll, of course, be provided promptly to the Board and the parties.