LPDR Coossopus nc "
" " ' " " =
The Light COMPMy Houstor Lighting & Power P O. Box 1700 Houston. Texas 77001 (713) 228-9211 March 17, 1980 ST-HL-AE-430 SFN: V-0540 Director, Region IV Nuclear Regulatory Commission 611 Ryan Plaza Drive, Suite 1000 Arlington, Texas 76102
Dear Sir:
South Texas Project Units 1 & 2 Docket Nos. STN 50-498, STN 50-499 IE Bulletin No. 80-03 Bulletin No. 80-03, received February 7,1980, has been reviewed by Houston Lighting and Power Company.
Charcoal adsorber cells have been purchased for the South Texas Project; however, a visual inspection is not possible since the cells have not yet been manufactured.
Problems of the sort described in the Bulletin are not expected at the South Texas Project due to di fferences in adsorber cell construction.
Rather than attaching the perforated screens with rivets spaced 6 inches apart, the South Texas Project adsorber cell screens will be spot welded at 1-3/4 inch spacing.
This will ensure adequate contact between the adsorber cell casings and screens.
If you have any questions, please contact us.
Very truly yours, f=2w E. A. Turner Vice President Power Plant Construction
& Technical Services PLW:bf l
1
\\
"5& * %
ST-HL-AE-430 Page.2 cc:
Director, Division of Fuel Facility and Materials Safety Inspection Office of Inspection and Enforcement M. D. Schwarz (Baker & Botts)
R. Gordon Gooch (Baker & Botts)
J. R. Newman (Lowenstein, Newman, Reis, Axelrad & Toll)
D. G. Barker A. J. Granger R. A. Frazar G. B. Painter R. L. Waldrop H. R. Dean l
.