Advises of Actions Taken in Response to Open Item 25 in NRC Concerning Control Room Habitability Sys. Commitments Resolve NRC Concerns & Provide Sufficient Basis for Closure of Open Item
ML19309H493
Person / Time
Site: LaSalle  
Issue date: 05/06/1980
From: Delgeorge L
COMMONWEALTH EDISON CO.
To: Bournia A
Office of Nuclear Reactor Regulation
References
NUDOCS 8005130387
Download: ML19309H493 (1)


Text

/

N Commonwealth Edison

[ i ) one First Fttional Plata, Chicigo. Illinois 8005130377

\\ v 'J Addttss RIply to: Post Offica Box 767 A

'(,/

Chicago. Illinois 60690 n

May 6, 1980 Mr.

A. Bournia Division of Project Management U.S. Nuclear Regulatory Commission Washington, DC 20555

Subject:

LaSalle County Station Units 1 and 2 Control Room Haoitability System NRC Docket Nos. 50-373 and 50-374 Reference (a):

0. D.

Parr letter to L.

O.

DelGeorge dated January 22, 1980

Dear Mr. Bournia:

As the result of discussions between Commonwealth Edison and the NRC Staf f regarding Open Item 25 in Reference (a),

Commonwealth Edison commits to the following action:

1.

The control room shall receive a high radiation alarm from the outside air intakes.

This commitment is documented in FSAR Section 6.4.1-(i).

2.

Provision will be made to manually initiate the Control Room HVAC Supply Air Filter (" Odor Eater") on receipt of a high radiation alarm from the outside air intake.

3.

The supply air filter train will be tested at each refueling autage (approximately once every 18 months) in conjunction with testing the once through charcoal filter.

The efficiency for this filter train will be confirmed tc be no less than 70% as part of this test.

It is our understanding that these commitments resolve the concerns held by the NRC and provide sufficient basis for closure of the open item referenced.

If you should have any further questions, please direct them to this office.

Unless you can suggest a specific FSAR section which can be amended to document these commitments, this letter with subsequent approval of the LaSalle County Technical Specification which addresses the supply air filter will serve as the formal documentation.

Bool Sincerely, sg

//b a

L. O. DelGeorge Nuclear Licensing Administrator 3599A