ML19309G834

From kanterella
Jump to navigation Jump to search
EN-80-011:notice of Violation & Notice of Proposed Imposition of Civil Penalties to Be Issued on 800404.Action Based on Noncompliance Re Plant Operation W/Portions of ECCS in Degraded Condition
ML19309G834
Person / Time
Site: Rancho Seco
Issue date: 04/01/1980
From: Brockett T, Thompson D
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE)
To:
References
EN-80-011, NUDOCS 8005070637
Download: ML19309G834 (1)


Text

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

-p 80 050 70 fok L

April 1, 1980 0FFICE OF INSPECTION AND ENFORCEMENT EN 11 NOTIFICATION OF SIGNIFICANT ENFORCEMENT ACTION

_ Licensee.

Sacramento Municipal Utility District, Sacramento, CA

~

(Rancho Seco Nuclear Generating Station)

Docket No. 50-312 (License No. DPR-54)

Subject:

PROPOSED IMPOSITION OF CIVIL PENALTIES - $25,000 This is to inform the Commission that a Notice of Violation and a Notice of Proposed Imposition of Civil Penalties in the amount of Twenty-five Thousand Dollars will be issued on or about April 4,1980, to Sacramento Municipal Utility District.

This action is based on an alleged violation and two alleged infractions of the Commission's regulations and/or license conditions relating to the operation of the Rancho Seco Nuclear Generation Station during the period December 17, 1979 to January 10, 1980, with certain portions of the Emergency Core Cooling System in degraded conditions which could have resulted in serious consequences in the event certain postulated faults had occurred.

These degraded conditions appear to have resulted from personnel errors in irrplementing operating procedures and in the failure of the licensee to main-tain effective procedures and controls to preclude such occurrences.

In addition, M the proposed civil penalties, an Order Modifying License Effective-Immediately is being issued which requires the licensee to adopt and implement administrative procedures for independent verification of valving line ups and equipment operability whenever safety related equipment is removed frorn or placed in service, and also requiring that existing procedures and controls be reviewed and revised as necessary.

A news release has been prepared and will be issued about the time the licenses receives the Notices and Order.

The State of California will be informed.

It should be noted that the licensee has not been specifically informed of the enforcement action.

The schedule of issuance and notification is:

Action signed April 1, 1980 Mailing of Notices April 4, 1980 Telephone Notification of Licensee April 4, 1980 Telephone Notification of State April 4, 1980 NRC News Release April 7, 1980 The licensee has 20 days from the date of receipt of the Notice in which to respond.

Following NRC staf f evaluation of the response, the civil penalties may be remitted, mitigated or imposed by Order.

Contact:

TWBrockett, IE x27246 DThompson, IE x27246 Distribution:

Transmitted H St 3'09 Chairman Ahearne Commissioner Hendrie S. J. Chilk, SECY Comaissioner Gilinsky Commissioner Bradford C. C. Kammerer, CA Commissioner Kennedy ACRS (For Distribution)

Transmi tted:

MNSB f cS P. Bldg 9:0s-V. Stello, IE W. J. Dircks, EDO H. R. Denton, NRR Region I C. Michelson, AE00 R. J. Mattson, NRR Region II J. J. Fouchard, PA

0. Vassallo, NRR Region III N. M. Haller, MPA D. Eisenhut, NRR Region IV R. G. Ryan, OSP Region V ?cao tj. K. Shapar, ELD SS Bldg o'CS J. G. Davis, NMSS Landow (MAIL)

S. Levine, RES J. J. Cummings, OIA R. Minogue, SD PRELIMINARY NOTIFICATION NOT FOR PUBLIC DISCLOSURE UNTIL APRIL 7, 1980

-_v_______.