ML19309E779
| ML19309E779 | |
| Person / Time | |
|---|---|
| Site: | Big Rock Point File:Consumers Energy icon.png |
| Issue date: | 04/21/1980 |
| From: | Hoffman D CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.) |
| To: | Ziemann D Office of Nuclear Reactor Regulation |
| References | |
| NUDOCS 8004240372 | |
| Download: ML19309E779 (1) | |
Text
s c,-;.,
Consumers n
J
!! Power V
,s-
,7 Company D
General Offices: 212 West Michigan Avenue, Jackson, Michigan 49201 e Area Code S17 788 0530 k
U April 21, 1980 Director, Nucletr Reactor Regulation Att Mr Dennis L Ziemann, Chief Operating Reactors Branch No 2 US Nuclear Regulatory Commission Washington, DC 20555 DOCKET 50-155 - LICENSE DPR BIG ROCK POINT PLANT - QUALITY ASSURANCE REQUIREVENTS REGARDING DIESEL GENERATOR FUEL OIL By NRC letter dated January 7,1980, (Quality Assurance Requirements Regarding Diesel Generator Fuel Oil), Consumers Power Company was requested to review our Quality Assurance (QA) Program with regard to diesel fuel oil for the Big Rock Point Plant.
Diesel fuel oil is not included in the Big Rock Point Plant QA Program. However, diesel fuel oil vill be included by May 31, 1980. Based on Part D (implementation) of Regulatory Guide 1.137, Big Rock Point Plant is exempt from the testing require-ments of this Regulatory Guide.
However, testing requirements are outlined in the Big Rock Point Plant Technical Specifications 4.7.11.1.l(c) which requires that a sample of diesel fuel from the fuel storage tank be tested in accordance with ASTM-D270-65 and is within the acceptable limits specified in Table 1 of ASTM-D975-7h with respect to viscosity, water content and sediment. This test is conducted at least once per 92 days.
David P Hoffman (Signed)
David P Hoffman Nuclear Licensing Administrator CC JGKeppler, USNRC 8 0042 4 0 37L