ML19309E487

From kanterella
Jump to navigation Jump to search
Provides Clarification Re Test to Show Effects of Various Single Power Failures.Subsequent to Power Supply Upgrade, Test Will Be Performed to Verify non-nuclear Instrumentation Sys Design & Power Supply Design Mod
ML19309E487
Person / Time
Site: Arkansas Nuclear 
Issue date: 04/16/1980
From: Trimble D
ARKANSAS POWER & LIGHT CO.
To: Reid R
Office of Nuclear Reactor Regulation
References
1-040-11, 1-40-11, NUDOCS 8004220471
Download: ML19309E487 (1)


Text

.

ARKANSAS POWER & LIGHT COMPANY POST OFFICE BOX 551 LLTTLE ROCK, ARKANSAS 72203 [501) 371-4000 April 16, 1980 1-040-11 s

Director of Nuclear Reactor Regulation ATTN:

Mr. R. W. Reid, Chief Operating Reactor Branch #4 U. S. Nuclear Regulatory Commission Washington, D. C. 20555

Subject:

Arkansas Nuclear One-Unit I Docket No. 50-313 License No. DPR-51 Followup Actions As A Result of The Crystal River - Unit 3 Event on February 26, 1980 (File:

1510)

Gentlemen:

Pursuant to the verbal request of your Mr. Guy Vissing, Arkansas Power &

Light Company provides the following clarification regarding the test for Arkansas Nuclear One - Unit I to show the effects of various single power supply failures. This letter supplements our response to Item 2 in our letter dated March 24, 1980.

An analysis of single power supply failures for the NNI-X and NNI-Y cabinets has been previously provided in our March 12, 1980 letter.

Subsequent to the A.C. power supply upgrade described in our March 24, 1980 letter, a test will be performed to verify the design of the NNI system.

The test will include a simulated single failure at the most likely location for the following loss of power events:

24 VDC NNI-X power, 24 VDC NNI-Y power, 118 VAC-X power, and 118 VAC-Y power. Also, testing will include verification of the power supply design modifica-tion.

Following completion of the test, a review will be done to determine its acceptability. The test procedure and results will te available for review by the NRC Resident Inspector.

Very truly yours, l

h v e.5 C d David C. Trimble Manager, Licensing DCT:DGM:nak 80042209y MEMBER MiOOLE SOUTH UTiuTIES SYSTEM