ML19309D901

From kanterella
Jump to navigation Jump to search
Forwards RO 50-313/77-20
Date released: 11/19/2019 Download: ML19309D901


RO 50-313/77-20:on 771023,diesel Generator 1 Failed to Start During Monthly Test.Caused by Starter Failure Due to Time Delay Relay Setpoint Drift & Diode Shorting Out.Diode Replaced & Jumpered.Relay Setpoint Reset
ML19309D903
Person / Time
Site: Arkansas Nuclear Entergy icon.png
Issue date: 11/01/1977
From: Kinsey V
ARKANSAS POWER & LIGHT CO.
To:
References
Download: ML19309D903 (1)
Forwards RO 50-313/77-20
ML19309D900
Person / Time
Site: Arkansas Nuclear Entergy icon.png
Issue date: 11/17/1977
From: Rueter D
ARKANSAS POWER & LIGHT CO.
To: HOWARD E M
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
Download: ML19309D900 (2)