ML19309D894

From kanterella
Jump to navigation Jump to search
RO 50-313/77-14:on 770612,penetration Room Ventilation Sys Circuit Breakers 52-6313 & 52-6314 Tripped.Caused by Thermal Overload Settings for Circuit Breakers Set to Low.Circuit Breaker Setting Reset to Higher Value
ML19309D894
Person / Time
Site: Arkansas Nuclear 
Issue date: 07/08/1977
From: Mardis D
ARKANSAS POWER & LIGHT CO.
To:
Shared Package
ML19309D889 List:
References
NUDOCS 8004110728
Download: ML19309D894 (4)


Text

UCENSEE EVENT RER IT g

c0NTRot 8toCx:l l

l 1

I I

I cum

, erau n8mun e seammanvi8mn 1

6 LCENSE NUMGER Tv 1417141f1#1/l lolo l-lolo lo lolol-lolol 141/ I / l / I / l lo 13 7 89 14 15 25 28 30 31 33' EE EmE occx(T NUMSER (VENT oATE AEpost? oATE cArtoony O 1 CON'T l l

l L4 }

[4_l lo 15161-1013 l t l 31 10 l(, l /1217171 1017l ole 17l71 7 8 57 58 59 60 61 88 89 74 75 M

EVENT DESCRIPTON 8E $ rrwisv. s,seTe sourns (M 96 rr)

-r1.a Pase;~rnerise faan Va rnen,,aw Sn,anre 1

7 89

~'

80 BE Ic,m,

amma a n, mm.. L = =nnwar.T mr = rus e v mw, e

ru. vet 1 7 89 80 Et I.,1,u--

1

  • . vur w.

sv<, wor w er avusr. 77. ecouu m v av.Tvra uu.,

7 89 M

OE lheN.nnlLC hin OPERABLE. & oc A EGFmT*tisvE occ annsact. Tuc 11mnMAt. auens esen l 7 89 80 dant.1 sNeAt9&s&3 JM AOTW C/Ef,.M /T A9 M EEsffo.1/3f71~/4 l

h l ser,*me 7 89 80 m

oY COMPONENT Coat VOLATUN as Ls l.d_1 ts J Ic It ! ris i e I x'l idJ Irl.l l

1 lHJ 7 89 10 11 12 17 43 44 47 48 CAUSE DESCRIPTON O8 lb resurgjg.,uwwr e I

e ws or N esac us r-enth="* y - we riso tM 7 89 80 m l n,a -rue marsuu.y aar s m u u a m,- Tua c,aca,,-

naamar a..a s l

89 80 Iwar marr-rs a

aiana a va aa.

I "O!&#

s,owta orNea sr.rus o cov av o c-roN igJ lol,Iel l un I

()J l

un i

i 7 8 9

10 12 13 44 45 46 80

  1. 2., l E?J7o

.MouNr o,.cor, toc roN c,.uA.,

lzJ so l

l we 1

M (Z

7 8 9

10 11 44 45 80 i

PERSONNEL EXPOSUAES 1

NUMBER TYPE otsCA* TON E lololol (2J l

v4 I

7 89 11 12 13 80 PERSONNEL INJUAIES NUMSER oESCAIPTON E lololo l I

w I

7 89 11 12 80 g

0FFSITE CONSEQUENCES 3E I we I

7 89 80 i

LOSS OR DAMAGE TO FACIUTY

[3 g

l.

7 89 10 80 i

PUBUCITY

@l NA I

7 89 80 8004110 77 &

A00! TONAL FACT 0AS I

so I

B9 80 1

1 i

NAME:-

AF'@

4X'ZP/.T*

PHCNE. IT##

37/*4494 l

spo see.sey

1.

Reportable Occurrence Report No. S0-313/77-14 2.

Report Date: July 8, 1977 3.

Occurrence Date:

June 12,1977 4

Facility:

Arkansas Nuclear One-Unit 1 P. O. Box 608 Russellville, AR 72801 S.

Identification of Occurrence:

Standby. circuit of the. Penetration Room Ventilation System was found to be inoperative.

6.

Conditions-Prior to Occurrence:

Steady-State Power X

Reactor Power 2542 MWth Hot Standby Net Output 797 MWe Cold Shutdown Percent of Full Power 99 %

Refueling Shutdown Load Changes During Routine O

Power Operation Routine Startup

~

Operation Routine Shutdown Operation Other (specify)

/

i 7.

Description of Occurrence:

At approximately 0232 hours0.00269 days <br />0.0644 hours <br />3.835979e-4 weeks <br />8.8276e-5 months <br /> on June 12, 1977, while performing a surveillance test on the Penetration Room Ventilation System, Circuit Breakers S2-6313 and S2-6314 tripped. These two breakers are for Valve CV-2133 (Standby System Filter Discharge) and Valve CV-2126 (Lead System Filter bype,s).

O l

~-

m

.~

D Reportable Occurrence Report No.

S0-313/77-14 8.

Designation of Apparent Cause of Occurrence:

Design Procedure Manufacture Unusual Service Condition x

Including Environmental Installation /

Construction Component Failure (See Failure Data)

Operator 1

Other (specify)

The themal overload settings on the circuit breakers were set too

. low for the abnomally hot environment.

9.

Analysis of Occurrence:

Since both circuits were proven operable during the last surveillance test and the lead circuit wcs proven operable on June 12, 1977, there was no hazard to the health and safety of the public.

4 4

6 I

i i

I

3 a

l m

Reportable Occurrence Report No.

50-313/77-14

10. Corrective Action:

j

' The themal overload setting was increased in both of the circuit breakers and the surveillance test was reperformed. The circuit proved to be operable.

i l

l 11.

Failure Data:

i A similar occurrence was reported in ROR 76-18 and ROR 77-9 i

l c

O O

O ww,-,,,,--

v r,

rv.,

, --~,- -., - --,-,--n----

---..,------.,,--w.

w,--

...-,ne.--

.,,,,n,,,,., --